Electronic Modular Control Panel II (EMCP II) Caterpillar


Engine Does Not Shutdown (for MUI 3306B, 3406C Engines)

Usage:

3306B 8NS
System Operation Description:

The engine does not shut down when a shutdown fault occurs.




Illustration 1g00531591

Fuel Control Relay For ETR Systems




Illustration 2g00531536

System Schematic For Air Shutoff Relay

Note: It is critical that GSC setpoint P23 is correct for the engine application. Ensure that setpoint P23 is programmed correctly for the engine application before continuing with this procedure.

There are several possible causes when a shutdown fault occurs and an engine does not shut down:

  • Operator Error: The operating conditions of the generator may not be understood by the operator. Ensure that the condition is one that should cause an engine shutdown.

  • Programming Error - Fault Is Overridden Or Disabled: It is possible to program the GSC in order to override certain shutdown faults. An overridden shutdown fault will be treated as an alarm fault. The YELLOW fault alarm indicator will be FLASHING instead of the RED fault shutdown indicator. If the GSC is programmed in order to disable a particular fault, there will not be any fault indicators or codes shown on the GSC. In these cases, it is a good idea to check any setpoints related to that fault. For example, if a genset is not shutting down when an overvoltage fault occurs, make sure setpoint P104 (Overvoltage shutdown enable) is programmed correctly. It is also possible to program the engine ECM to override or ignore certain shutdown faults. See Troubleshooting, SENR1003, "3500B EPG Engines" or Troubleshooting, RENR2227, "3406E EPG Engines" for more information on programming the engine ECM.

  • Programming Error - Setpoints Incorrect For Application Or Customer Needs: It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition. In this case, check the appropriate setpoints for correct values. For example, if the genset is not shutting down when a high coolant temperature condition occurs, make sure setpoint P15 (High Water Temperature Shutdown) is correct for the application.

  • Faulty Component: Some examples of faulty components that could prevent the GSC from shutting down the engine are: GSC and a broken or shorted harness wire.. In this case, the GSC will be issuing a command to shut down the engine due to a diagnostic code, but the engine remains running.

Test Step 1. CHECK FOR DIAGNOSTIC CODES

  1. Check the GSC for a diagnostic code on the upper display.

Expected Result:

The GSC should show a diagnostic code on the upper display.

Results:

  • YES - The GSC shows a diagnostic code on the upper display.

    Repair: See theTesting and Adjusting section of this book for the diagnostic code that is displayed on the GSC.

    Stop.

  • NO - The GSC does NOT show a diagnostic code on the upper display. Proceed to Test Step 2.

Test Step 2. CHECK THE YELLOW FAULT ALARM INDICATOR

  1. Check the display area of the GSC for the yellow fault alarm indicator.

Expected Result:

The yellow fault alarm indicator should be illuminated CONTINUOUSLY.

Results:

  • YES - The yellow fault alarm indicator is illuminated CONTINUOUSLY.

    Repair: The GSC has been programmed to override the normal shutdown response and the GSC treats the condition as an alarm fault. The engine will continue to run. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5".

    Stop.

  • NO - The yellow fault alarm indicator is not illuminated at all. Proceed to Test Step 3.

Test Step 3. CHECK FOR RED FAULT SHUTDOWN INDICATOR.

  1. Check the display area of the GSC for a red fault shutdown indicator.

Expected Result:

The red fault shutdown indicator should be FLASHING.

Results:

  • YES - The red fault shutdown indicator is FLASHING and the engine remains running. Proceed to Test Step 4.

  • NO - All fault indicators are OFF. A problem that is occurring should cause the GSC to shut down the engine. It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition.

    Repair: Check the appropriate setpoints for correct values. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5"

    Stop.

Test Step 4. CHECK THE SYSTEM BY USING THE ESPB.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. Push the emergency stop push button (ESPB).

Expected Result:

The engine should shut down.

Results:

  • OK - The engine does shutdown. The relay module has failed.

    Repair: Replace the relay module. See Testing And Adjusting, "Relay Module - Replace"

    Stop.

  • NOT OK - The engine does NOT shut down. Proceed to Test Step 5.

Test Step 5. CHECK FOR FUEL CONTROL SOLENOID AND ENGINE PROBLEMS.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. Remove F14 in the Junction Box.

Expected Result:

The engine should shut down.

Results:

  • YES - The engine shuts down. Therefore, the fuel control solenoid (FCS) has failed.

    Repair: Replace the fuel control solenoid. Verify that the repair corrects the problem.

    Stop.

  • NOT OK - The engine continues to run and the red fault shutdown indicator is FLASHING. There is a problem with the engine.

    Repair: Refer to the appropriate engine service manual in order to troubleshoot the engine.

    Stop.

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for MUI 3412C, 3508, 3512, 3516 Engines)
G3304 and G3306 Engines General Information (Cooling System)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for EUI and PEEC Engines)
G3304 and G3306 Engines General Information (Lubrication System)
Electronic Modular Control Panel II (EMCP II) System Communication Module (Customer)
Electronic Modular Control Panel II (EMCP II) Relay Driver Module
G3406 Engine Measuring Engine Oil Pressure
G3304 and G3306 Engines Engine Oil Pressure is Low
G3304 and G3306 Engines Engine Oil Pressure is High
Electronic Modular Control Panel II (EMCP II) Fault Log Viewing OP1
3500B Marine Engines Secondary ECM Assumes Control
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI 3412C, 3508,3512, 3516 Engines)
Electronic Modular Control Panel II (EMCP II) AC Offset Adjustment OP10
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for PEEC Engines)
Electronic Modular Control Panel II (EMCP II) GSC Operation Is Erratic
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current Is Zero
Electronic Modular Control Panel II (EMCP II) Normal Mode
Electronic Modular Control Panel II (EMCP II) Fault Log Clearing OP4
G3406 Engine Air Inlet and Exhaust System Components
G3406 Engine Finding the Top Center Position for the No. 1 Piston
Electronic Modular Control Panel II (EMCP II) SP Fault Codes
Electronic Modular Control Panel II (EMCP II) Indicators of Alarm Module or Remote Annunciator Are Constantly Flashing
Electronic Modular Control Panel II (EMCP II) Alarm Module Control (Custom)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.