Electronic Modular Control Panel II (EMCP II) For MUI Engines Caterpillar


CID 560 FMI 11 CAT Data Link Failure Mode Not Identified - Test

Usage:

3304 02B



Illustration 1g00614651

System Schematic For CAT data link

System Operation

On generator sets with the proper equipment, the GSC uses the CAT data link to communicate with other electronic control modules on the machine. The CAT data link consists of two wires that connect the GSC to at least one other electronic control module.

The possible causes of a CID 560 FMI 11 diagnostic code are listed below:

  • There is a short from the wire that connects to contact "19" of the CAT data link to the battery ("B+").

  • There is a short from the wire that connects to contact "20" of the CAT data link to the battery ("B+").

  • There is a short from the wire that connects to contact "19" of the CAT data link to ground ("B-").

  • There is a short from the wire that connects to contact "20" of the CAT data link to ground ("B-").

The GSC cannot detect an open in the circuit of the CAT data link. Troubleshoot the wiring and repair the wiring. See Testing And Adjusting, "Schematic and Wiring Diagrams".

The GSC treats a CID 560 as an alarm fault. Active alarm faults are shown on the display when the alarm codes key is pressed. Also, the ECS is in any position except the OFF/RESET position. Clear the fault from the fault log after troubleshooting is complete.

Caterpillar Information System:

Generator Set Load Sensor Droop - Adjust
G3304 and G3306 Engines Engine Support
3306C Engines for Caterpillar Built Machines Gear Group (Front)
G3304 and G3306 Engines Valve Cover
3126B and 3126E On-highway Engines Unit Injector Hydraulic Pump - Install
G3304 and G3306 Engines Valve Cover
3500B Engines Water Pump - Install
G3612 and G3616 Engines Generator - Remove and Install
3044C Industrial Engine Fuel Conservation Practices
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 447 FMI 12 Fuel Control Relay Failed - Test
SR4B Generators Generator - Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 446 FMI 12 Air Shutoff Relay Failed - Test
Electronic Modular Control Panel II (EMCP II) For MUI Engines SP Fault Code - Troubleshoot
3512B Marine Auxiliary Engine MID 036 - CID 0289 - FMI 13 Unfiltered Fuel Pressure calibration required
3126B Engines for Caterpillar Built Machines Inlet and Exhaust Valves - Remove and Install
3512B Marine Auxiliary Engine MID 036 - CID 0542 - FMI 13 Unfiltered Engine Oil Pressure cal required
3512B Marine Auxiliary Engine MID 036 - CID 1335 - FMI 03 DLO Eng Filter In Press Sensor open/short to +batt
3126B Engines for Caterpillar Built Machines Turbocharger - Remove
3512B Marine Auxiliary Engine MID 036 - CID 1335 - FMI 04 DLO Engine Filter Inlet Press Sensor short to gnd
Generator Set Load Sensor Load Gain - Adjust
3512B Marine Auxiliary Engine MID 036 - CID 1336 - FMI 03 DLO Engine Inlet Press Sensor open/short to +batt
Generator Set Load Sensor Wiring Diagrams
3512B Marine Auxiliary Engine MID 036 - CID 1336 - FMI 04 DLO Engine Inlet Press Sensor short to gnd
3512B Marine Auxiliary Engine MID 036 - CID 1337 - FMI 03 DLO Pump Discharge Press Sens open/short to +batt
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.