Generator Set Load Sensor Caterpillar


Droop - Adjust

Usage:

3406C 1LS

Droop Adjustment

This adjustment is only necessary for droop operation. The DROOP control sets the amount of speed regulation for the engine. The droop adjustment is only required when paralleling with utility bus or other units which are using hydromechanical governors. Since speed regulation is a function of load or power delivered, the DROOP function makes a reduction to the engine speed setting with an increase in load. The percent of speed droop is the difference between engine speed at "No Load" and engine speed at "Full Load". The percent of speed droop is expressed as a percentage of full load speed. It is calculated as follows.

(No Load Speed - Full Load Speed) ? 100 / Full Load Speed = Percent of Flow Loss

Example

(61.8 Hz - 60 Hz) ? 100 / 60 Hz = 3 Percent Droop

Normally, the percent of droop is known. The correction that is needed is the amount to increase the "No Load" setting. In this case, the "No Load" setting is calculated as follows.

(100 percent + Percent of Droop) ? Full Loading Setting = No Loading Setting

Note: If only 50 percent loading is possible, a "No Load" setting of 60.9 Hz would be an indication of three percent droop as shown in the Illustration 1.




Illustration 1g00617347

Droop Adjustment

Setting Droop On System Operating Into A Commercial Bus

  1. With the unit off the line, run the engine. Set the speed to 60 Hz ("No Load" setting). Mark this position.

  1. Set RATED SPEED or external Speed Trim potentiometer setting above the 60 Hz reference by the percent droop required. For example, three percent droop would mean raising the speed to 61.8 Hz. Mark this potentiometer position. Return the potentiometer to 60 Hz.

  1. Turn the "DROOP" potentiometer fully clockwise (maximum droop). Set the external Mode Switch to "DROOP".

  1. Bring the unit on the line.

  1. Return the RATED SPEED or external Speed Trim potentiometer to the point marked in 2.

  1. Now make adjustment to "DROOP" potentiometer in counterclockwise direction (decreasing Droop) until Full Load (Rated) is reached.

Setting Droop For An Isolated Load

  1. Run the engine and set the Mode Switch to the "DROOP" position.

  1. With the load removed from the engine, set RATED SPEED or external Speed Trim potentiometer to the "No Load" speed. For example, for three percent droop, speed setting would be 61.8 Hz.

  1. Apply 100 percent of the load to the engine.

  1. With the engine fully loaded, make an adjustment to the "DROOP" potentiometer until either 50 or 60 Hz is reached.

Caterpillar Information System:

G3304 and G3306 Engines Engine Support
3306C Engines for Caterpillar Built Machines Gear Group (Front)
G3304 and G3306 Engines Valve Cover
3126B and 3126E On-highway Engines Unit Injector Hydraulic Pump - Install
G3304 and G3306 Engines Valve Cover
3500B Engines Water Pump - Install
G3612 and G3616 Engines Generator - Remove and Install
3044C Industrial Engine Fuel Conservation Practices
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 447 FMI 12 Fuel Control Relay Failed - Test
SR4B Generators Generator - Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 446 FMI 12 Air Shutoff Relay Failed - Test
G3612 and G3616 Engines Air Starting Motor - Disassemble
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 560 FMI 11 CAT Data Link Failure Mode Not Identified - Test
Electronic Modular Control Panel II (EMCP II) For MUI Engines SP Fault Code - Troubleshoot
3512B Marine Auxiliary Engine MID 036 - CID 0289 - FMI 13 Unfiltered Fuel Pressure calibration required
3126B Engines for Caterpillar Built Machines Inlet and Exhaust Valves - Remove and Install
3512B Marine Auxiliary Engine MID 036 - CID 0542 - FMI 13 Unfiltered Engine Oil Pressure cal required
3512B Marine Auxiliary Engine MID 036 - CID 1335 - FMI 03 DLO Eng Filter In Press Sensor open/short to +batt
3126B Engines for Caterpillar Built Machines Turbocharger - Remove
3512B Marine Auxiliary Engine MID 036 - CID 1335 - FMI 04 DLO Engine Filter Inlet Press Sensor short to gnd
Generator Set Load Sensor Load Gain - Adjust
3512B Marine Auxiliary Engine MID 036 - CID 1336 - FMI 03 DLO Engine Inlet Press Sensor open/short to +batt
Generator Set Load Sensor Wiring Diagrams
3512B Marine Auxiliary Engine MID 036 - CID 1336 - FMI 04 DLO Engine Inlet Press Sensor short to gnd
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.