Customer parameters may be changed repeatedly as operational requirements change.
The following information is a brief description of the customer specified parameters. The following parameter values are included with the descriptions:
- Minimum
- Maximum
- Default
The "Low Idle Speed" is the minimum engine rpm. The low idle speed is dependent on the engine rating.
The "High Idle Speed" is the maximum engine rpm. The high idle speed is dependent on the engine rating.
This parameter determines the acceleration rate when the throttle is increased.
Value | Default |
---|---|
0 to 2000 rpm/sec | 1000 rpm/sec |
Engine Speed Decelerating Ramp Rate
This parameter determines the deceleration rate when the throttle is decreased.
Value | Default |
---|---|
0 to 2000 rpm/sec | 1000 rpm/sec |
This parameter determines the amount of droop that is allowed when the engine load increases.
Value | Default |
---|---|
0 to 8 percent | 7 percent |
This parameter determines the number of installed throttles.
Value | Default |
---|---|
0-2 | 0 |
Throttle 1 Idle Validation Switch Enable Status
This parameter determines if a throttle 1 idle validation switch is installed.
Value | Default |
---|---|
Enabled
Disabled |
Disabled |
Throttle 2 Idle Validation Switch Enable Status
This parameter determines if a throttle 2 idle validation switch is installed.
Value | Default |
---|---|
Enabled
Disabled |
Disabled |
Limp Home Desired Engine Speed
This parameter determines the desired engine speed when the engine goes into limp home mode.
Minimum | Maximum | Default |
---|---|---|
800 rpm | 2000 rpm | 1200 rpm |
Limp Home Engine Speed Ramp Rate
This parameter determines the deceleration rate when the engine goes into limp home mode.
Value | Default |
---|---|
0 to 2000 rpm/sec | 1000 rpm/sec |
This parameter determines the shutdown strategy if a Level 3 fault is active.
Value | Default |
---|---|
Enabled
Disabled |
Enabled |
This parameter determines the engine location in a multi-engine application.
Value | Default |
---|---|
Engine #1
Engine #2 |
Engine #1 |
Automatic Idle Kickdown Enable Switch Configuration
This parameter determines whether the idle kickdown switch is normally open or normally closed.
Value | Default |
---|---|
Not Installed
Normally Closed (To Ground) Normally Open |
Not Installed |
Fuel Pump Actuator Calibration Code
This parameter is the calibration code for the fuel rack solenoid.
Value | Default |
---|---|
AxxxBxxxCxxx | AxxxBxxxCxxx |
This parameter determines the sensitivity of the governor solenoid on the fuel rack.
Value | Default |
---|---|
50%, 75%, 100% ,150%, or 200% of Factory Gain | 100% of Factory Gain |
J1939 Continuous Fault Handling
Remote Torque Speed Control Enable Status
The Remote Torque Speed Control Enable Status parameter controls the type of remote TSC input. If this parameter is "Enabled", the ECM expects a continuous signal from TSC1. If this parameter is "Disabled", the ECM does not expect a signal from TSC1. However, if a signal is transmitted, the ECM will respond.
Value | Default |
---|---|
Enabled
Disabled |
Disabled |