Refer to table 1 for the available responses for this engine.
Cross-reference for System Response to an Event Warning Category Indicators (1) and (3) | ||
---|---|---|
Warning Category Indicator | System Response Shown on Cat ET | Description of the System Response |
(1) | "Least Severe" | Warning |
(2) | "Moderate Severe" | Impending Shutdown |
(3) | "Most Severe" | Shutdown |
Note: All severity levels may not be supported for a monitored parameters.
Use the Caterpillar Electronic Technician (ET) to perform the following activities:
- Select the available responses.
- Program the level for monitoring.
- Program delay times for each response.
The default settings for the parameters are programmed at the factory. To accommodate unique applications and sites, the parameters may be reprogrammed with Cat ET. The screens of Cat ET provide guidance for the changing of trip points.
Note: Some of the parameters are protected by factory passwords. Other parameters can be changed with customer passwords.
Changing the Settings of the Monitoring System
Use the following procedure to change settings of the parameters:
- Use Cat ET and select the "Monitoring System" screen.
- Highlight the desired parameter. Then click the "Change" button in the lower left corner of the screen.
The "Change Monitor System" screen will appear.
- Change the "State" to "On" or "Off".
- Set the "Trip Point" and the "Delay Time" according to the "Allowed Values" in the lower half of the screen.
- Click the "OK" button.
If a password is required, the "Enter Passwords" screen will appear. Enter the correct passwords and then click the "OK" button.
The new settings will be effective immediately.
Note: Factory passwords are only available to service technicians from an authorized Caterpillar Dealership. Customers of Caterpillar do not have access to the Caterpillar Factory Password System (FPS).
Default Settings of the Monitoring System
The default settings for the parameters are programmed at the factory. To accommodate unique applications and sites, the parameters may be reprogrammed with Cat ET. The screens of Cat ET provide guidance for changing trip points.
Separate timers are used in the ECM for each response that is associated with a parameter. If a trip point is exceeded, the timer for that event is started.
For example, the warning for "High Engine Coolant Temperature" can be set to 95° C with a five second delay. The timer starts counting if the coolant temperature exceeds 95° C. If the temperature is not reduced to less than 95° C within five seconds, the event becomes active and the event is logged.
Some of the programmable parameters depend on the status of an ECM output before the parameters are allowed to function. Some of the parameters are allowed to function after the crank terminate relay has been energized for more than 30 seconds. Other parameters are allowed to function after the output for the fuel control relay is energized. Some parameters are not dependent upon any conditions.
The conditions are designed to eliminate false events during start-up if the customer has programmed a delay time to zero.
Use care when you program the trip points and the delay times. Ensure that the response of the ECM is correct for the application. The monitoring system will accept any settings within the ranges.
If the trip point for a shutdown is programmed to activate before the trip point for a warning, the engine will shutdown and the warning will not be activated.
Default Settings for the Programmable Monitoring System | ||||||||
---|---|---|---|---|---|---|---|---|
Parameter
Description |
Event Code | System Response | State | Trip Point | Delay in Seconds | Security Level
Password |
Range of the Trip Point | Range of the Delay in Seconds |
"High Engine Coolant Temperature" | 110-15
Engine Coolant Temperature : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
113°C | 20 | 2 | 80°C
to 115°C |
1 to 60 |
"High Engine Coolant Temperature" | 110-0
Engine Coolant Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
Always
On |
117°C | 20 | 2 | 80°C
to 117°C |
1 to 60 |
"Low Engine Coolant Temperature" | 110-17
Engine Coolant Temperature : Low - least severe (1) |
Least Severe (1)
Warning |
On | 60°C | 20 | 2 | 60°C
to 85°C |
1 to 60 |
"Low Engine Coolant Pressure" | 109-1
Engine Coolant Pressure : Low - most severe (3) |
Most Severe (3)
Shutdown |
Off | MAP | 10 | 2 | MAP | 1 to 60 |
"Low Engine Coolant Pressure" | 109-17
Engine Coolant Pressure : Low - least severe (1) |
Least Severe (1)
Warning |
Off | MAP | 10 | 2 | MAP | 1 to 60 |
"High Eng Oil to Eng Coolant Differential Temp" | 4243-0
Engine Oil to Engine Coolant Differential Temperature : High - Most Severe (3) |
Most Severe (3)
Shutdown |
On | 11°C | 10 | 2 | 0°C
to 20°C |
1 to 60 |
"High Engine Oil Temperature" | 175-15
Engine Oil Temperature 1 : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
102°C | 20 | 2 | 85°C
to 115°C |
1 to 60 |
"High Engine Oil Temperature" | 175-0
Engine Oil Temperature 1 : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 104°C | 20 | 2 | 85°C
to 115°C |
1 to 60 |
"Low Engine Oil Pressure" | 100-17
Engine Oil Pressure : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
MAP | 10 | 2 | MAP | 1 to 15 |
"Low Engine Oil Pressure" | 100-1
Engine Oil Pressure : Low - most severe (3) |
Most Severe (3)
Shutdown |
Always
On |
MAP | 0 | 2 | MAP | 0 to 0 |
"High Oil Filter Differential Pressure" | 99-15
Engine Oil Filter Differential Pressure : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
220 kPa | 20 | 2 | 120 kPa
to 240 kPa |
1 to 60 |
"High Oil Filter Differential Pressure" | 99-0
Engine Oil Filter Differential Pressure : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 240 kPa | 10 | 2 | 120 kPa
to 240 kPa |
1 to 60 |
"Low Oil Filter Differential Pressure" | 99-17
Engine Oil Filter Differential Pressure : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
5 kPa | 60 | 2 | 0 kPa
to 80 kPa |
1 to 60 |
"Low Oil Filter Differential Pressure" | 99-1
Engine Oil Filter Differential Pressure : Low - most severe (3) |
Most Severe (3)
Shutdown |
On | 0 kPa | 10 | 2 | 0 kPa
to 80 kPa |
1 to 60 |
"High Gas Fuel Differential Pressure" | 1391-15
Engine Fuel Valve Differential Pressure : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
35 kPa | 10 | 2 | 12kPa
to 40 kPa |
1 to 60 |
"Low Gas Fuel Differential Pressure" | 1391-17
Engine Fuel Valve Differential Pressure : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
5 kPa | 10 | 2 | 5 kPa
to 20 kPa |
1 to 60 |
"High Gas Fuel Pressure" | 1390-15
Engine Fuel Valve #1 Inlet Absolute Pressure : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
135 kPa | 10 | 2 | 100 kPa
to 135 kPa |
1 to 60 |
"Low Gas Fuel Pressure" | 1390-17
Engine Fuel Valve #1 Inlet Absolute Pressure : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
104 kPa | 10 | 2 | 68 kPa
to 104 kPa |
1 to 60 |
"High Fuel Temperature" | 174-15
Engine Fuel Temperature 1 : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
60°C | 20 | 2 | 0°C
to 60°C |
1 to 60 |
"High Intake Manifold Air Temperature" | 105-15
Engine Intake Manifold #1 Temperature : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
86°C | 20 | 2 | 75°C
to 90°C |
1 to 60 |
"High Intake Manifold Air Temperature" | 105-0
Engine Intake Manifold #1 Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 90°C | 20 | 2 | 80°C
to 95°C |
1 to 60 |
"High Compressor Inlet Air Filter Restriction" | 107-15
Engine Air Filter 1 Differential Pressure : High - least severe (1) |
Least Severe (1)
Warning |
Off | 3.75 kPa | 5 | 2 | 0 kPa
to 3.75 kPa |
1 to 10 |
"Engine Overspeed" | 190-0
Engine Speed : High - most severe (3) |
Most Severe (3)
Shutdown |
Always
On |
1750 rpm | 0 | 2 | 1500 rpm
to 1875 rpm |
0 to 0 |
"Low System Voltage" | 167-17
Charging System Potential : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
20 VDC | 20 | 2 | 18 VDC
to 24 VDC |
1 to 60 |
"Low System Voltage" | 167-1
Charging System Potential : Low - most severe (3) |
Most Severe (3)
Shutdown |
On | 18 VDC | 10 | 2 | 18 VDC
to 24 VDC |
1 to 60 |
"High System Voltage" | 167-15
Charging System Potential : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
34 VDC | 20 | 2 | 18 VDC
to 36 VDC |
1 to 60 |
"High Engine Ignition Transformer Secondary Output" | 1393-15
Engine Cylinder #1 Ignition Transformer Secondary Output : High - least severe (1)Charging System Potential : High - least severe (1) Through 1408-15 Engine Cylinder #16 Ignition Transformer Secondary Output : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
80 % | 0 | 2 | 1 %
to 100 % |
N/A |
Programmable Parameters of the Integrated Sensing Module
The Integrated Temperature Sensing Module (ISM) monitors the temperatures of the cylinder exhaust ports and of the inlets of the turbocharger turbine.
If a temperature exceeds an acceptable range, the ISM can initiate a "WARNING" or "SHUTDOWN". Both of the responses are available for all the parameters. Use Cat ET to perform the following activities:
- Select the available responses.
- Program the level for monitoring.
- Program delay times for each response.
Note: To initiate the responses, the ISM sends commands to the ECM via the CAN Data Link. If the connection between the ISM and the ECM is not correct, the ISM cannot initiate any response.
The default settings for the parameters are programmed at the factory. To accommodate unique applications and sites, the parameters may be reprogrammed with Cat ET. The screens of Cat ET provide guidance for changing trip points.
Use Cat ET to determine the programming for your engine. The items can be reprogrammed to accommodate the requirements of individual sites.
Use care when you program the trip points and the delay times. Ensure that the response of the ISM is correct for the application. The monitoring system will accept any setting within the ranges.
If the trip point for a shutdown is lower than the trip point for a warning, the warning will not be activated.
Separate timers are used in the ISM for each response that is associated with a parameter. If a trip point is exceeded, the timer for that event is started.
For example, the warning for the "High Exhaust Temperature" can be set to 655 °C with a 30 second delay. The timer starts counting if the exhaust port temperature of the cylinder reaches 655 °C. If the temperature is not reduced to less than 655 °C within 30 seconds, the event becomes active and the event is logged.
Default Settings for the Integrated Sensing Module | ||||||||
---|---|---|---|---|---|---|---|---|
Parameter | Event Code | System Response | State | Trip Point | Delay in Seconds | Security Level
Password |
Range of the Trip Point | Range of the Delay in Seconds |
"High Turbo Turbine Inlet Temperature" | 1180-15
Engine Turbocharger #1 Turbine Intake Temperature : High - least severe (1) And 1181-15 Engine Turbocharger #2 Turbine Intake Temperature : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
680°C | 10 | 2 | 400°C
to 700°C |
1 to 60 |
"High Turbo Turbine Inlet Temperature" | 1180-0
Engine Turbocharger #1 Turbine Intake Temperature : High - most severe (3) And 1181-0 Engine Turbocharger #2 Turbine Intake Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
Always
On |
710°C | 10 | 2 | 500°C
to 710°C |
1 to 60 |
"Exhaust Port Temperature - Too High" | 1137-15
Engine Exhaust Gas Port 1 Temperature : High - least severe (1) Through 1148-15 Engine Exhaust Gas Port 12 Temperature : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
775°C | 10 | 2 | 700°C
to 780°C |
1 to 60 |
"Exhaust Port Temperature - Too High" | 1137-0
Engine Exhaust Gas Port 1 Temperature : High - most severe (3) Through 1148-0 Engine Exhaust Gas Port 12 Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 780°C | 10 | 2 | 700°C
to 780°C |
1 to 60 |
"Exhaust Port Temperature High Deviation" | 5686-15
Engine Exhaust Gas Port #1 Difference from Average Temperature : High - least severe (1) Through 5697-15 Engine Exhaust Gas Port #12 Difference from Average Temperature : High - least severe (1) |
Least Severe (1)
Warning |
Always
On |
50°C | 5 | 2 | 10°C
to 80°C |
1 to 60 |
"Exhaust Port Temperature High Deviation" | 5686-0
Engine Exhaust Gas Port #1 Difference from Average Temperature : High - most severe (3) Through 5697-0 Engine Exhaust Gas Port #12 Difference from Average Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 80°C | 5 | 2 | 10°C
to 100°C |
1 to 60 |
"Exhaust Port Temperature Low Deviation" | 5686-17
Engine Exhaust Gas Port #1 Difference from Average Temperature : Low - least severe (1) Through 5697-17 Engine Exhaust Gas Port #12 Difference from Average Temperature : Low - least severe (1) |
Least Severe (1)
Warning |
Always
On |
50°C | 5 | 2 | 10°C
to 100°C |
1 to 60 |
"Exhaust Port Temperature Low Deviation" | 5686-1
Engine Exhaust Gas Port #1 Difference from Average Temperature : Low - most severe (3) Through 5697-1 Engine Exhaust Gas Port #12 Difference from Average Temperature : Low - most severe (3) |
Most Severe (3)
Shutdown |
On | 80°C | 5 | 2 | 10°C
to 100°C |
1 to 60 |
"High Three Way Catalyst Inlet Gas Temperature" | 4289-15
Aftertreatment #1 Three Way Catalytic Converter Intake Gas Temperature : High - least severe (1) |
Least Severe (1)
Warning |
On | 550°C | 10 | 2 | 550°C
to 600°C |
1 to 60 |
4289-0
Aftertreatment #1 Three Way Catalytic Converter Intake Gas Temperature : High - most severe (3) |
Most Severe (3) | On | 600°C | 10 | 2 | 500°C
to 750°C |
1 to 60 | |
"High Three Way Catalyst Outlet Gas Temperature" | 4290-15
Aftertreatment #1 Three Way Catalytic Converter Outlet Gas Temperature : High - least severe (1) |
Least Severe (1)
Warning |
On | 670°C | 30 | 2 | 650°C
to 670°C |
1 to 30 |
4290-0
Aftertreatment #1 Three Way Catalytic Converter Outlet Gas Temperature : High - most severe (3) |
Most Severe (3)
Shutdown |
On | 705°C | 10 | None | 650°C
to 670°C |
1 to 10 | |
"High Three Way Catalyst Differential Gas Temperature" | 4779–15
Aftertreatment #1 Three Way Catalyst Differential Gas Temperature : High - least severe (1) |
Least Severe (1)
Warning |
On | 150°C | 30 | 2 | 35°C
to 250°C |
1 to 600 |
4779–0
Aftertreatment #1 Three Way Catalyst Differential Gas Temperature : High - most severe (3) |
Most Severe (3) | On | 170°C | 10 | 2 | 50°C
to 300°C |
1 to 600 | |
"Aftertreatment Catalytic Converter Intake Gas Temp - Too Low" | 4289-17
Aftertreatment #1 Three Way Catalytic Converter Intake Gas Temperature : Low - least severe (1) |
Least Severe (1)
Warning |
On | 400°C | 300 | 2 | 100°C
to 400°C |
1 to 600 |