G3600 Human Machine Interface (HMI) Display Caterpillar


Display Module Software - Install

Usage:

G3612 BB2

Table 1
HMI Software Flash File(1) 
Part Number  Part Name  Description 
523-5208  Monitor Software Gp  G3600 COLOR HMI 
(1) Always check SIS web for the latest software updates.

First Time Configuration and Flash

It is recommended that the Display Interface Module IP address (DIM IP address) and the Controller IP addresses be recorded before flashing the display with updated software. The IP addresses found in the display software are set to a default address. These default addresses may or may not be used depending on the system requirements of the customer. Flashing new HMI software will return any custom IP addresses to the default IP addresses originally supplied with the software configuration. Refer to the "IP Address Configuration" section for further information on locating and programming addresses.



    Illustration 1g06141212
    HMI software flash files

  1. Download the HMI software flash file from SIS web (https://sis.cat.com) to a USB thumb drive.

    Note: Four files are downloaded in zipped format. If the PC does not automatically extract the files, Caterpillar recommends 7-Zip as the preferred application for unzipping. Keep the files separate on the thumb drive. Do not place the files in a folder.

  2. Power down the HMI.

  3. Plug the USB thumb drive into one of the USB ports.

    Note: There are three available USB ports.

  4. The screen appears with the following two prompts:

    • Copy the project

    • Back up existing project

    Select "Yes" when the screen prompts to copy the project. This will copy the files from the USB thumb drive to the HMI unit.

    Select "No" to the "Back up existing project" prompt.



    Illustration 2g06126468
    Flash file syncing

  5. Select the "SYNC" soft button when the flash is complete.

    Note: The HMI and the A5:M6 will be synced with the engine.

  6. Operation can begin once the sync is complete.

Update Configuration and Flash



    Illustration 3g06147561
    HMI flash files

  1. Download the HMI software flash file from SIS web (https://sis.cat.com) to a USB thumb drive.

    Note: Four files are downloaded in zipped format. If the PC does not automatically extract the files, Caterpillar recommends 7-Zip as the preferred application for unzipping. Keep the files separate on the thumb drive. Do not place the files in a folder.

  2. Power up the HMI unit.

  3. Select the "Technician Login" option from the "Settings" tab and login.

    Note: The user name is "Technician". The password is "12345" when using this option for the first time.

  4. Select the "DIM IP Settings" option.

    1. Record the current IP address and network mask.

    2. Select "Cancel" to exit.

  5. Select the "Controller IP Settings" option.

    1. Select the controller from the list.

    2. Press the settings soft button.

    3. Record the desired settings from the integrated controller.

  6. Power down the HMI unit.

  7. Plug the USB thumb drive into one of the USB ports.

    Note: There are three available USB ports.

  8. Power up the HMI unit.

  9. The screen appears with the following two prompts:

    • Copy the project

    • Back up existing project

    Select "Yes" when the screen prompts to copy the project. This will copy the files from the USB thumb drive to the HMI unit.

    Select "No" to the "Back up existing project" prompt.



    Illustration 4g06126468
    Flash file syncing

  10. Select the "SYNC" soft button when the flash is complete.

    Note: The HMI and the A5:M6 will be synced with the engine.

  11. Operation can begin once the sync is complete.

IP Address Configuration

Use the steps in this section to properly configure the Controller IP.

  1. Select the "Settings" button on the top of the controller screen.


    Illustration 5g06166620
    Login screen

  2. Select the "Technician Login" button on the "Settings" screen. The user will be prompted to enter a user name and password. The user name is "Technician". The default password is "1800118".


    Illustration 6g06166628

  3. Select the "Controller Settings" button to open the "Change Active Controllers" menu.

  4. Select the controller to be configured and click the "Settings" option.


    Illustration 7g06166633

  5. Select the "Stations" tab in the top of the "Settings" window.


    Illustration 8g06166636

  6. Set the IP address of the controller. Ensure that this address matches the IP address of the EMCP.

    Note: "EMCPX_DATA" and "EMCPX_DIAG" need to have the same IP address.

Caterpillar Information System:

G3600 Human Machine Interface (HMI) Display Communication Network
Installation Procedure for the Insulation Blankets on Certain Retrofit Aftertreatment{1067} Installation Procedure for the Insulation Blankets on Certain Retrofit Aftertreatment{1067}
C9.3 Marine Engine Fuel Injection Pump - Remove and Install - Left-Hand Simplex and Duplex
C32 Marine Engine Maintenance Interval Schedule
G3600 Human Machine Interface (HMI) Display Specifications
G3600 Human Machine Interface (HMI) Display General Information
C4.4 and C7.1 Engines Battery Problem
New Turbocharger Bearing Design Used On Certain 3512 And 3516 Engines {1052, 1053, 1307} New Turbocharger Bearing Design Used On Certain 3512 And 3516 Engines {1052, 1053, 1307}
C280-16 Marine Engines Filter Screen (DEF) - Inspect/Clean
Marine Selective Catalytic Reduction (SCR) Retrofit Aftertreatment Filter Screen (Air) - Inspect/Clean
C4.4 and C7.1 Engines ECM - Replace
Fleet Detect Onboard Displays Used On Certain Cat® Products Have Corruptions In Memory (MSTAR){7490, 7605} Fleet Detect Onboard Displays Used On Certain Cat® Products Have Corruptions In Memory (MSTAR){7490, 7605}
G3600 Human Machine Interface (HMI) Display Connector Contact Description
G3600 Human Machine Interface (HMI) Display Display Module - Replace
G3600 Human Machine Interface (HMI) Display Persistent Panel Screen
G3600 Human Machine Interface (HMI) Display Main Screen
G3600 Human Machine Interface (HMI) Display Control Panel Screen
G3600 Human Machine Interface (HMI) Display Home Screens
G3600 Human Machine Interface (HMI) Display Setting Screens
G3600 Human Machine Interface (HMI) Display Documentation Screens
G3600 Human Machine Interface (HMI) Display Diagnostic Screens
G3600 Human Machine Interface (HMI) Display Chart Screens
G3600 Human Machine Interface (HMI) Display OEM Screens
C280-16 Marine Engines Diesel Exhaust Fluid Pump - Replace
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.