HMI Software Flash File(1) | ||
---|---|---|
Part Number | Part Name | Description |
523-5208 | Monitor Software Gp | G3600 COLOR HMI |
(1) | Always check SIS web for the latest software updates. |
First Time Configuration and Flash
It is recommended that the Display Interface Module IP address (DIM IP address) and the Controller IP addresses be recorded before flashing the display with updated software. The IP addresses found in the display software are set to a default address. These default addresses may or may not be used depending on the system requirements of the customer. Flashing new HMI software will return any custom IP addresses to the default IP addresses originally supplied with the software configuration. Refer to the "IP Address Configuration" section for further information on locating and programming addresses.
- Download the HMI software flash file from SIS web (https://sis.cat.com) to a USB thumb drive.
Note: Four files are downloaded in zipped format. If the PC does not automatically extract the files, Caterpillar recommends 7-Zip as the preferred application for unzipping. Keep the files separate on the thumb drive. Do not place the files in a folder.
- Power down the HMI.
- Plug the USB thumb drive into one of the USB ports.
Note: There are three available USB ports.
- The screen appears with the following two prompts:
- Copy the project
- Back up existing project
Select "Yes" when the screen prompts to copy the project. This will copy the files from the USB thumb drive to the HMI unit.
Select "No" to the "Back up existing project" prompt.
Show/hide tableIllustration 2 g06126468 Flash file syncing - Select the "SYNC" soft button when the flash is complete.
Note: The HMI and the A5:M6 will be synced with the engine.
- Operation can begin once the sync is complete.
Illustration 1 | g06141212 |
HMI software flash files |
Update Configuration and Flash
- Download the HMI software flash file from SIS web (https://sis.cat.com) to a USB thumb drive.
Note: Four files are downloaded in zipped format. If the PC does not automatically extract the files, Caterpillar recommends 7-Zip as the preferred application for unzipping. Keep the files separate on the thumb drive. Do not place the files in a folder.
- Power up the HMI unit.
- Select the "Technician Login" option from the "Settings" tab and login.
Note: The user name is "Technician". The password is "12345" when using this option for the first time.
- Select the "DIM IP Settings" option.
- Record the current IP address and network mask.
- Select "Cancel" to exit.
- Select the "Controller IP Settings" option.
- Select the controller from the list.
- Press the settings soft button.
- Record the desired settings from the integrated controller.
- Power down the HMI unit.
- Plug the USB thumb drive into one of the USB ports.
Note: There are three available USB ports.
- Power up the HMI unit.
- The screen appears with the following two prompts:
- Copy the project
- Back up existing project
Select "Yes" when the screen prompts to copy the project. This will copy the files from the USB thumb drive to the HMI unit.
Select "No" to the "Back up existing project" prompt.
Show/hide tableIllustration 4 g06126468 Flash file syncing - Select the "SYNC" soft button when the flash is complete.
Note: The HMI and the A5:M6 will be synced with the engine.
- Operation can begin once the sync is complete.
Illustration 3 | g06147561 |
HMI flash files |
Use the steps in this section to properly configure the Controller IP.
- Select the "Settings" button on the top of the controller screen.
Show/hide table
Illustration 5 g06166620 Login screen - Select the "Technician Login" button on the "Settings" screen. The user will be prompted to enter a user name and password. The user name is "Technician". The default password is "1800118".
Show/hide table
Illustration 6 g06166628 - Select the "Controller Settings" button to open the "Change Active Controllers" menu.
- Select the controller to be configured and click the "Settings" option.
Show/hide table
Illustration 7 g06166633 - Select the "Stations" tab in the top of the "Settings" window.
Show/hide table
Illustration 8 g06166636 - Set the IP address of the controller. Ensure that this address matches the IP address of the EMCP.
Note: "EMCPX_DATA" and "EMCPX_DIAG" need to have the same IP address.