Accelerometer
Show/hide table
Illustration 1 | g03694058 |
(1) Accelerometer location - top view of flywheel assembly |
Show/hide table
Illustration 2 | g03694066 |
Accelerometer |
The accelerometer (1) is located in the flywheel cabinet on top of the flywheel. The accelerometer reads vibrations of the flywheel. The accelerometer sends signals to the flywheel interface board which then gets sent to the APC3 board.
- Refer to Systems Operation, Test and Adjust, UENR4695, "Internal Component Pre-Removal Steps". Perform the internal component pre-removal procedure to shut down the system and to gain access to internal components.
Note: The flywheel cabinet must be de-energized before removal steps can be performed.
- Remove eight bolts from the top cover of the flywheel assembly.
- Remove bolt that holds the accelerometer plug in place.
- Unplug the cord for the accelerometer.
- Plug in the accelerometer cord.
- Tighten the bolt to secure the accelerometer cord.
- Attach the eight bolts to the top cover of the flywheel assembly.
Caterpillar Information System:
UPS 750 Uninterruptible Power Supply Cooling Fan
UPS 750 Uninterruptible Power Supply Vacuum Pump
UPS 750 Uninterruptible Power Supply Vacuum Gauge
UPS 750 Uninterruptible Power Supply Rotor Position Sensor Assembly
UPS 750 Uninterruptible Power Supply Flywheel Assembly
UPS 750 Uninterruptible Power Supply Flywheel Interface PWA
UPS 750 Uninterruptible Power Supply Utility Gate Driver Board
UPS 750 Uninterruptible Power Supply Utility Inverter Assembly
UPS 750 Uninterruptible Power Supply Flywheel Gate Driver Board
UPS 750 Uninterruptible Power Supply Flywheel Inverter Assembly
UPS 750 Uninterruptible Power Supply DC Capacitor Module
UPS 750 Uninterruptible Power Supply Internal Component Preremoval Steps (SIO Cabinet)
UPS 750 Uninterruptible Power Supply Field Coil Driver
UPS 750 Uninterruptible Power Supply Door
UPS 750 Uninterruptible Power Supply Front Screen and Air Filter
UPS 750 Uninterruptible Power Supply System Startup
UPS 750 Uninterruptible Power Supply System Shutdown
UPS 750 Uninterruptible Power Supply Service Tools
UPS 750 Uninterruptible Power Supply Flywheel Module - Remove
UPS 750 Uninterruptible Power Supply Flywheel Module - Install
UPS 750 Uninterruptible Power Supply Flywheel Power Unit Cabinet - Install
UPS 750 Uninterruptible Power Supply System Messages
C4.4 Engines for Caterpillar Built Machines Crankcase Breather - Install - Unfiltered Breather
C4.4 Engines for Caterpillar Built Machines Crankcase Breather - Remove - Filtered Breather