AC Filter Capacitor
Show/hide table
Illustration 1 | g03691886 |
(1) EMI board
(2) AC filter capacitors |
The AC filter capacitor bank is combined with a filter. The filter consists of inductors and capacitors to create an "LC" filter. The filter is located behind the left door panel on the SIO cabinet, next to the electromagnetic interface (EMI) board. The capacitor bank is made up of three sets of capacitors, one for each phase. The LC filter converts the output sine wave from the utility inverter into a low total harmonic distortion sine wave.
- Disconnect all AC filter L2-A1 leads from phase-A bus.
- Disconnect all AC filter L2-B1 leads from phase-B bus.
- Disconnect all AC filter L2-C1 leads from phase-C bus.
- Disconnect all AC filter neutral leads from neutral bus.
- Remove the three 3/8 inch bolt that connects the filter assembly to SIO cabinet.
- Remove the phase-A filter assembly from the SIO cabinet.
- Remove the phase-B filter assembly from the SIO cabinet.
- Remove the phase-C filter assembly from the SIO cabinet.
- Install the phase C filter assembly into SIO cabinet. Secure in place with a 3/8 inch bolt.
- Install the phase B filter assembly into SIO cabinet. Secure in place with a 3/8 inch bolt.
- Install the phase A filter assembly into SIO cabinet. Secure in place with a 3/8 inch bolt.
- Connect the neutral lead from each filter assembly to the neutral bus.
- Connect all AC filter L2-A1 leads to phase-A bus.
- Connect all AC filter L2-B1 leads to phase-B bus.
- Connect all AC filter L2-C1 leads to phase-C bus.
Caterpillar Information System:
UPS 750 Uninterruptible Power Supply Electromagnetic Interface
UPS 750 Uninterruptible Power Supply Breaker Controller Interface
UPS 750 Uninterruptible Power Supply Fuses
UPS 750 Uninterruptible Power Supply Bypass Contactor
UPS 750 Uninterruptible Power Supply Utility Contactor
UPS 750 Uninterruptible Power Supply APC Controller
UPS 750 Uninterruptible Power Supply Voltage Current Interface
UPS 750 Uninterruptible Power Supply Power Distribution PWA
UPS 750 Uninterruptible Power Supply Power Supply
C8.7 Marine Engines Turbocharger - Inspect
UPS 750 Uninterruptible Power Supply Customer Interface Board
UPS 750 Uninterruptible Power Supply Line Static Switch
UPS 750 Uninterruptible Power Supply Utility Busbar
UPS 750 Uninterruptible Power Supply Surge Trap
UPS 750 Uninterruptible Power Supply General Information (FPU Cabinet)
UPS 750 Uninterruptible Power Supply Internal Component Preremoval Steps (FPU Cabinet)
UPS 750 Uninterruptible Power Supply Internal Component Preremoval Steps (SIO Cabinet)
UPS 750 Uninterruptible Power Supply DC Capacitor Module
UPS 750 Uninterruptible Power Supply Flywheel Inverter Assembly
UPS 750 Uninterruptible Power Supply Flywheel Gate Driver Board
UPS 750 Uninterruptible Power Supply Utility Inverter Assembly
UPS 750 Uninterruptible Power Supply Utility Gate Driver Board
UPS 750 Uninterruptible Power Supply Flywheel Interface PWA
UPS 750 Uninterruptible Power Supply Flywheel Assembly