Usage:

UPSB 220 JFA
The UPS must be installed in a room that is restricted to qualified personnel only.

The cabinet rests on four cylindrical feet that are 40 mm (1.6 inch) in diameter. The feet are positioned in the four corners of the cabinet to distribute the weight of the cabinet evenly.

The cabinets are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged through the roof. The cabinets can be positioned against a back wall. A minimum clearance of 400 mm (15.75 inch) is required above the unit for airflow. A minimum clearance of 850 mm (33.5 inch) is required in front of the unit to allow the door to swing fully open.

Note: The NEC requires a distance of 900 mm (35.5 inch) for access to electrical equipment. Individual site requirements for blast zone or arc flash may require greater distances and should be determined by an engineer on the site.




Illustration 1g02345716

(1) Air outlets

(2) Front panel

(3) Rear panel

(5) Air inlets

Caterpillar Information System:

C27 and C32 Engines Exhaust Manifold - Remove and Install
C1.5 and C2.2 Industrial Engines Plate Locations and Film Locations
2011/02/02 New Water Pump on 3024C, C1.1, C1.5 and C2.2 Engines {1355, 1361}
Assembly of 175-5507 and 361-3889 Nitrogen Charging Groups and 175-7410 Auxiliary Fitting Group{0647, 7200} Assembly of 175-5507 and 361-3889 Nitrogen Charging Groups and 175-7410 Auxiliary Fitting Group{0647, 7200}
C7.1 (Mech) Industrial Engine Reference Information
C1.5 and C2.2 Industrial Engines Product Lifting
C7.1 (Mech) Industrial Engine Sensors and Electrical Components
C7.1 (Mech) Industrial Engine Overspeed
C7.1 (Mech) Industrial Engine Monitoring System
C7.1 (Mech) Industrial Engine Welding on Engines with Electronic Controls
C7.1 (Mech) Industrial Engine Fluid Recommendations - Lubricant Information
C7.1 (Mech) Industrial Engine Fluid Recommendations - Fuel Recommendations
UPSB220 Uninterruptible Power Supply Cable Routing
UPSB220 Uninterruptible Power Supply Circuit Breaker Recommendation
UPSB220 Uninterruptible Power Supply Component Location
UPSB220 Uninterruptible Power Supply Electrical Specification
UPSB220 Uninterruptible Power Supply Maintenance Interval Schedule
UPSB220 Uninterruptible Power Supply Modes Of Operation
UPSB220 Uninterruptible Power Supply Parallel UPS Connection
UPSB220 Uninterruptible Power Supply Parallel UPS Startup and Shutdown
UPSB220 Uninterruptible Power Supply Single UPS Connection
UPSB220 Uninterruptible Power Supply Single UPS Startup and Shutdown
C13 Tier 4 Final Engines Air Cleaner
C13 Tier 4 Final Engines Air Cleaner
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.