Electrical Specification
Show/hide table
General characteristics of the 60 Hz Battery UPS     | ||||
---|---|---|---|---|
Power in kVA     | 150     | 180     | 225     | |
Normal AC input     | ||||
Number of conductors     | Three phase or three phases plus neutral     | |||
Rated voltage and tolerances     | 480 V +/- 10% (adjustable to +/- 15%)     | |||
Rated frequency and tolerances     | 60 Hz +/- 10%     | |||
THDI     | < 10%     | < 8%     | < 7.5%     | |
Power factor     | up to 0.9     | |||
Bypass AC input     | ||||
Number of conductors     | Three phases plus neutral     | |||
Rated voltage and tolerances     | 480 V +/- 10%     | |||
Rated frequency and tolerances     | 60 Hz +/- 10%     | |||
Load Output     | ||||
Number of conductors     | Three phases plus neutral     | |||
Phase to phase voltages     | 480 V     | |||
Phase to neutral voltages     | 277 V     | |||
Voltage variation (Ph/Ph, Ph/N)     | +/- 1%     | |||
Adjustable frequencies and tolerance (on battery power)     | 60 Hz +/- 0.05 Hz     | |||
Synchronization with bypass     | +/- 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)     | |||
Transient voltage variation for 0 to 100% load step change     | +/- 2% (with battery), + 2%/-6% (without battery)     | |||
Permissible overloads     | 150 % for 1 minute or 125 % for 10 minutes     | |||
Isc Ph/Ph % of rated current     | 3.2     | 2.6     | 2.1     | |
Isc Ph/N % of rated current     | 5     | 4.1     | 3.3     | |
THDU Ph to Ph and Ph to N for linear load     | < 1.5% Ph to Ph, < 2% Ph/N     | |||
THDU Ph to Ph and Ph to N for nonlinear load     | < 2% Ph to Ph, < 3% Ph/N     | |||
Battery     | ||||
Floating voltage     | 512 V to 561 V     | |||
Standard battery technology     | Sealed lead acid battery (gas recombination)     | |||
UPS Characteristics     | ||||
Active power (kW)     | 135     | 162     | 202.5     | |
Efficiency at 50% Load (%) (values +/- 1%)     |
92     | 92.5     | 93     | |
Efficiency at 100% Load (%) (values +/- 1%)     |
93     | 93     | 93.5     | |
Heat losses in Btu     | 13870     | 18500     | 25490     | |
Storage temperature range     | -13°F to 113°F (-25°C to +45°C)     | |||
Relative humidity     | 20% to 95% non-condensing     | |||
Maximum operating altitude without derating     | 3281 ft (< 1000 m)     | |||
Operating temperature range at Pn     | 32°F to 104°F (0°C to 40°C)     |
Caterpillar Information System:
UPSB220 Uninterruptible Power Supply Component Location
UPSB220 Uninterruptible Power Supply Circuit Breaker Recommendation
UPSB220 Uninterruptible Power Supply Cable Routing
UPSB220 Uninterruptible Power Supply Product Location
C27 and C32 Engines Exhaust Manifold - Remove and Install
C1.5 and C2.2 Industrial Engines Plate Locations and Film Locations
2011/02/02 New Water Pump on 3024C, C1.1, C1.5 and C2.2 Engines {1355, 1361}
Assembly of 175-5507 and 361-3889 Nitrogen Charging Groups and 175-7410 Auxiliary Fitting Group{0647, 7200} Assembly of 175-5507 and 361-3889 Nitrogen Charging Groups and 175-7410 Auxiliary Fitting Group{0647, 7200}
C7.1 (Mech) Industrial Engine Reference Information
C1.5 and C2.2 Industrial Engines Product Lifting
C7.1 (Mech) Industrial Engine Sensors and Electrical Components
C7.1 (Mech) Industrial Engine Overspeed
UPSB220 Uninterruptible Power Supply Maintenance Interval Schedule
UPSB220 Uninterruptible Power Supply Modes Of Operation
UPSB220 Uninterruptible Power Supply Parallel UPS Connection
UPSB220 Uninterruptible Power Supply Parallel UPS Startup and Shutdown
UPSB220 Uninterruptible Power Supply Single UPS Connection
UPSB220 Uninterruptible Power Supply Single UPS Startup and Shutdown
C13 Tier 4 Final Engines Air Cleaner
C13 Tier 4 Final Engines Air Cleaner
349E, 349F and 352F Excavators and 349E MHPU Mobile Hydraulic Power Unit Tool Control System Solenoid Valve (Proportional Reducing) - Calibrate - Flow Limit Valves
C27 and C32 Engines for Caterpillar Built Machines Piston and Rings
XQP150 Rental Generator Set Belts - Inspect/Adjust/Replace
C7.1 (Mech) Industrial Engine Engine Air Cleaner Element (Dual Element) - Inspect/Clean/Replace