UPSB125 Uninterruptible Power Supply Caterpillar


Cable Size Requirement

Usage:

UPSB 125 SEP

表 1
UPS 额定功率     电缆最小规格,单位:mm2     蓄电池端子接头    
铜 负载电路    
< 100 m < 100 m     < 100 m     < 100 m     < 15 m    
20 kVA     10     16     16     16     16    
30 kVA     16     16     16     16     25    
40 kVA     16     16     16     16     35    
60 kVA     25     25     25     25     70    
80 kVA     50     50     50     50     95    
100 kVA     50     70     70     70     2 x 50    
120 kVA     70     70     70     70     2 x 70    

------ WARNING! ------

在维护或修理发电设备时:

确保装置在脱机状态(脱开公用电网或其它发电设备),并锁定或者系上标签不准操作(DO NOT OPERATE)。 拆下所有保险丝。


表 1 中列出的电缆规格适用于采用铜导体的电缆。 对于采用铝导体的电缆,规格增加 30%。 所列电缆规格的计算方法是基于 400 V 电压和四根电缆为一组。 通过预先钻孔的端子进行连接。 接地电缆连接至接地板。

对于 120 kVA 的系统,电缆穿孔的直径为 8.5 mm (0.33 in)。 对于所有其它系统,孔的直径为 6.5 mm (0.25 in)。

带外部旁路的并联 UPS




图 1g01945183

带外部旁路的三台并联 UPS 系统的典型安装方式

表 2
额定功率 (1)     总台数     总功率     总电流 (2)     电缆规格 (3)    
20 kVA     2
3
4    
40 kVA
60 kVA
80 kVA    
58 A
87 A
116 A    
16
35
50    
30 kVA     2
3
4    
60 kVA
90 kVA
120 kVA    
80 A
129 A
172 A    
25
50
70    
40 kVA     2
3
4    
80 kVA
120 kVA
160 kVA    
116 A
174 A
222 A    
35
70
120    
60 kVA     2
3
4    
1200 kVA
180 kVA
240 kVA    
174 A
261 A
348 A    
70
150
185    
80 kVA     2
3
4    
160 kVA
240 kVA
320 kVA    
232 A
348 A
464 A    
120
185
2 x 120    
100 kVA     2
3
4    
200 kVA
300 kVA
400 kVA    
288 A
432 A
576 A    
150
2 x 95
2 x 150    
120 kVA     2
3
4    
240 kVA
360 kVA
480 kVA    
348 A
522 A
696 A    
185
2 x 150
2 x 185    
( 1 ) 单台 UPS 的额定功率
( 2 ) 交流旁路输入或负载电流
( 3 ) 所列电缆规格单位为 mm2。

表 2 中所列额定功率值和额定电流值适用于最多包括四台 UPS 系统的典型安装型式。 所列电缆规格的计算方法是基于 400 V 电压和四根电缆为一组。 所列电缆规格适用于 U1000 R02V 型铜导体。 对于采用铝导体的电缆,在所列规格的基础上增加 30%。

在冗余 UPS 系统中,只计算给负载供电所需的 UPS 系统的数量。 示例如下:如果安装了三个 UPS 系统,其中包括一个单台冗余 UPS,则只计算其余两个系统。 此方法使你能够确定输入和负载电流。

表 2 适用于 400 V 输入和在功率因数为 0.8 的额定负载下的负载相间电压。 对于 380 V 系统,将电流值乘以 1.05。 对于 415 V 系统,将电流值乘以 0.96。 相应修改电缆规格。

Caterpillar Information System:

UPSB125 Uninterruptible Power Supply Circuit Breaker Recommendation
UPSB125 Uninterruptible Power Supply Communication Card Installation
UPSB125 Uninterruptible Power Supply Component Description
UPSB125 Uninterruptible Power Supply Component Location
UPSB125 Uninterruptible Power Supply Display Messages
UPSB125 Uninterruptible Power Supply Electrical Specification
UPSB125 Uninterruptible Power Supply External Battery Cabinet Connection
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Remove and Install
UPSB125 Uninterruptible Power Supply External Bypass Connection
UPSB125 Uninterruptible Power Supply General Hazard Information
UPSB125 Uninterruptible Power Supply General Information
UPSB125 Uninterruptible Power Supply Glossary
UPSB125 Uninterruptible Power Supply Cable Routing
UPSB125 Uninterruptible Power Supply Battery Service
UPSB125 Uninterruptible Power Supply Battery Packing Material Removal
UPSB125 Uninterruptible Power Supply Battery Circuit Breaker Installation
UPSB125 Uninterruptible Power Supply Auxiliary Connection
UPSB125 Uninterruptible Power Supply Alarm Operation
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Disassemble
Reuse and Salvage of Water Pumps {1361} Reuse and Salvage of Water Pumps {1361}
793F Off-Highway Truck Engine Supplement Modular Front End - Remove and Install
3508, 3512 and 3516 Generator Set Engines Air Starting Motor - Assemble
349F and 352F Excavators Indicators and Gauges - Test
349F and 352F Excavators Radiator Core - Clean
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.