UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


System Shutdown

Usage:

UPS 750 CPM

Shutting Down the Single Module System (SMS)

  • SMS with a Bypass Cabinet

  • SMS without a Bypass Cabinet

Pre-Shutdown




    Illustration 1g00863047

  1. Connect a personal computer (PC) to the "RS-232/RS-485" port. The port is located on the bottom back corner of the System Input/Output Board. Refer to Illustration 1. The System Input/Output Board is located in the System Cabinet.

    Note: Refer to Systems Operation, Testing and Adjusting, RENR2476, "Component Location (System Cabinet)" for the location of the board.

  1. Rotate the switch to the corresponding MMU.

  1. Boot the PC.

  1. Run the UPS View software by double clicking over the icon on your PC.

  1. Click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.



    Illustration 2g00697157

  1. Enter a valid "User Name" and then enter a valid "Password". Refer to Illustration 9.

    After the password has been entered, the menu options will change. The menu bar will contain a "Calibrate" option.

  1. Depress the <Ctrl><X> keys and hold the <Ctrl><X> keys. This is done in order to bring the system to 0 RPM.

  1. The system will prompt you to confirm the option. Depress the <Y> key or select "Yes".

    Note: This procedure is only available once during a 24 hour period.

    Note: A minimum of 15 minutes is required in order to lower the speed of the flywheel to 0 RPM.

    Note: A minimum of 15 minutes is required in order to secure the rotor.

SMS with a Bypass Cabinet

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Single Module System (SMS)" section before proceeding with this procedure.



    Illustration 3g01831633

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "Bypass" position. Refer to Illustration 3.

  1. Remove the key from the keyswitch (1). Secure the key.



    Illustration 4g00948144

  1. Verify that the system enters the bypass mode. Hit the "Menu" button on the user interface panel of the Flywheel Cabinet. Verify that the system is in the "Bypassed" mode. Refer to Illustration 4.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.



    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 5g01797996

    Side view of the Bypass Cabinet

    (10) Bypass Switch

    (11) Output Switch

    (12) Input Switch

  1. Close the Bypass Switch (10) that is located in the Bypass Cabinet. Refer to Illustration 5.

  1. Open the Output Switch (11) that is located in the Bypass Cabinet. Refer to Illustration 5.

  1. Open the Input Switch (12) that is located in the Bypass Cabinet. Refer to Illustration 5.

  1. Remove facility power from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

SMS without a Bypass Cabinet

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Single Module System (SMS)" section before proceeding with this procedure.



    Illustration 6g01831633

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "Bypass" position. Refer to Illustration 6.

  1. Remove the key from the keyswitch (1). Secure the key.



    Illustration 7g00948144

  1. Verify that the system enters the bypass mode. Hit the "Menu" button on the user interface panel. Verify that the system is in the "Bypassed" mode. Refer to Illustration 7.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.



    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Remove the electrical input to the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Remove facility power from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Shutting Down the Multiple Module System (MMS)

  • Single Input without Switches

  • Single Input with Three Switches

  • Dual Input without Switches

  • Dual Input with Two Switches

  • Dual Input with Three Switches

Pre-Shutdown




    Illustration 8g00863047

  1. Connect a personal computer (PC) to the "RS-232/RS-485" port on the Parallel Cabinet Interface Board. The port is located on the bottom back corner of the Parallel Cabinet Interface Board. Refer to Illustration 8. The Parallel Cabinet Interface Board is located in the System Cabinet.

    Note: Refer to Systems Operation, Testing and Adjusting, RENR2476, "Component Location (System Cabinet)" for the location of the board.

  1. Rotate the switch to the corresponding MMU.

  1. Boot the PC.

  1. Run the UPS View software by double clicking over the icon on your PC.

  1. Click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.



    Illustration 9g00697157

  1. Enter a valid "User Name" and then enter a valid "Password". Refer to Illustration 9.

    After the password has been entered, the menu options will change. The menu bar will contain a "Calibrate" option.

  1. Depress the <Ctrl><X> keys and hold the <Ctrl><X> keys. This is done in order to bring the system to 0 RPM.

  1. The system will prompt you to confirm the option. Depress the <Y> key or select "Yes".

    Note: This procedure is only available once during a 24 hour period.

    Note: A minimum of 15 minutes is required in order to lower the speed of the flywheel to 0 RPM.

    Note: A minimum of 15 minutes is required in order to secure the rotor.

  1. Repeat this procedure for each MMU.

Single Input without Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 10g01831939

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 10.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 11g00948144

  1. Hit the "Menu" button on the user interface panel of the System Cabinet. Verify that each MMU is in the "Bypassed" mode. Refer to Illustration 11.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 12g01831633

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 12.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.



    Illustration 13g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 13.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 13.

  1. Disconnect the utility from the input bus of the system.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Single Input with Three Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 14g01831939

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 14.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 15g00948144

  1. Hit the "Menu" button on the user interface panel of the System Cabinet. Verify that each MMU is in the "Bypassed" mode. Refer to Illustration 15.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 16g01831633

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 16.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 17g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 17.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.



    Illustration 18g01802293

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 18.



    Illustration 19g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 19.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 18.

  1. Open the Input Isolation Switch (5) that is located in the Input/Output Cabinet. Refer to Illustration 18.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input without Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 20g01831939

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 20.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 21g00948144

  1. Hit the "Menu" button on the user interface panel of the System Cabinet. Verify that each MMU is in the "Bypassed" mode. Refer to Illustration 21.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 22g01831633

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the Bypass position. Refer to Illustration 22.

  1. Remove the key from the keyswitch (1). Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Close the external maintenance bypass switch.



    Illustration 23g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 23.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 23.

  1. Disconnect the utility from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input with Two Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 24g01831939

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 24.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 25g00948144

  1. Hit the "Menu" button on the user interface panel of the System Cabinet. Verify that each MMU is in the "Bypassed" mode. Refer to Illustration 25.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 26g01831633

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 26.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 27g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 27.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.



    Illustration 28g01798373

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 28.



    Illustration 29g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 29.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 28.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 29.

  1. Disconnect the utility from the input bus of the system.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input with Three Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 30g01831939

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 30.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 31g00948144

  1. Hit the "Menu" button on the user interface panel of the System Cabinet. Verify that each MMU is in the "Bypassed" mode. Refer to Illustration 31.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 32g01831633

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 32.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 33g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 33.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.



    Illustration 34g01798373

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 34.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 34.



    Illustration 35g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 35.

  1. Open the Input Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 35.

  1. Open the Input Isolation Switch (5) that is located in the Input/Output Cabinet. Refer to Illustration 34.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Remove utility power from the input bus for the system.

  1. Allow the capacitor banks to purge down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Caterpillar Information System:

UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Startup
XQ175 Rental Generator Set Generator Operation
XQ175 Rental Generator Set Voltage Regulators
Failures of the Engine Vision on Marine Applications{1900, 7490} Failures of the Engine Vision on Marine Applications{1900, 7490}
725C, 725C2, 730C, 730C2 and 730C, 730C2 EJECTOR Articulated Truck Systems Pump Drive - PTO
2009/03/16 A New Control Module is Available {1900, 1901, 1920}
793F and 797F Off-Highway Trucks Power Train Electronic Control System Diagnostic Capabilities
XQ175 Rental Generator Set Control Panel
XQ175 Rental Generator Set Product Lifting
XQ175 Rental Generator Set Model View Illustrations
C175-16 Marine Engines Fuel System - Prime
CX31-P600 Petroleum Transmission Transmission Planetary
795F AC and 795F AC XQ Off-Highway Trucks Inverter Cabinet - Check/Clean
Procedure to Replace the Top Glass on the Cab of Certain Excavators and Mobile Hydraulic Power Units{7301, 7310, 7325} Procedure to Replace the Top Glass on the Cab of Certain Excavators and Mobile Hydraulic Power Units{7301, 7310, 7325}
C175-16 and C175-20 Generator Set Engines Fuel Pressure Is High - Fuel Supply System
C175-16 and C175-20 Generator Set Engines Turbocharger Speed Change Occurrence
789D, 793F, and 797F Off-Highway Truck Monitoring System MID 053 - CID 0168 - FMI 03
C12 Marine Engines Cooling System Supplemental Coolant Additive (SCA) - Test/Add
Surface Finishes of Cylinder Bores{7562} Surface Finishes of Cylinder Bores{7562}
Monitoring Parameters Are Not Activated Until the Engine's RPM Has Reached Low Idle{1000, 1901, 1920} Monitoring Parameters Are Not Activated Until the Engine's RPM Has Reached Low Idle{1000, 1901, 1920}
C4.4 Industrial Engine Idler Gear - Remove
C4.4 Industrial Engine Idler Gear - Remove
C4.4 Industrial Engine Idler Gear - Install
C4.4 Industrial Engine Idler Gear - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.