Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


Alarm Module Control (Custom)

Usage:

C32 SXC



Illustration 1g00321237

Custom Alarm Module (CAM)

(1) Amber indicators. (2) Red indicators. (3) Lamp test switch. (4) Alarm silence switch. (5) Horn.

Table 1
Connections For Customer Alarm Module    
Screw Terminal     Signal Name    
1     "BATT+"    
2     Not Used    
3     Input 5 - Indicator 5 (Red)    
4     Input 6 - Indicator 6 (Red)    
5     Input 7 - Indicator 7 (Red)    
6     Input 8 - Indicator 8 (Red)    
7     "BATT-"    
8     Input 1 - Indicator 1 (Amber)    
9     Input 2 - Indicator 2 (Amber)    
10     Input 3 - Indicator 3 (Amber)    
11     Input 4 - Indicator 4 (Amber)    
12     Lamp Test    
13     Horn Silence    
14     Horn output    

The CAM is an attachment that can be mounted at a remote location. The CAM annunciates faults, alarms or other conditions. Customer supplied inputs give the CAM this information.

The CAM operates when the CAM is powered by a 24 DCV battery system or a 32 DCV battery system. The CAM is equipped with a horn, an alarm silence switch and a lamp test switch. 8 switched inputs are also provided for the customer to use.

Note: A basic version of the CAM also exists. The basic version does not have a horn, an alarm silence switch or a lamp test switch. The basic CAM should be used with an existing fully equipped CAM or an ALM.

Alarm Operation

A given switch input will correspond to 1 of 8 indicators on the face of the CAM. The indicators will FLASH at a rate of 2 hertz when the corresponding input is closed to the battery negative terminal. The red indicators are used to display shutdown conditions, and the amber indicators are used to display alarm conditions.

When an input that is corresponding to one of the red indicators is activated, the indicator will flash and the horn will sound. When the input is disconnected from the battery negative terminal, the horn will continue to sound and the red indicator will continue to flash until the alarm silence switch is pressed.

When an input that is corresponding to one of the amber indicators is activated, the indicator will flash but the horn does NOT sound. When the input is disconnected from the battery negative terminal, the amber indicator will turn off.

Alarm Silence Function

The alarm silence switch is activated by connecting the corresponding input to the battery negative terminal.

When an input is connected to the battery negative terminal, activating the alarm silence switch causes the horn to cease. The indicator stops flashing and the indicator changes to being ON continuously. The alarm silence function will be overridden if the following event occurs. The status of any of the eight switched inputs change. The change of status will cause additional inputs to be closed to the battery negative terminal.

The Alarm Silence Function will not be overridden if the change in status is the opening of any of the inputs from the battery negative terminal. The indicators will turn OFF when the corresponding input is disconnected from the battery negative terminal.

Lamp Test Function

Activating the "Lamp Test" switch results in sounding the horn and turning on all indicators continuously for 10 seconds or until the switch is deactivated. The "Lamp Test" input can be wired to the switch of another alarm module.

Customized Labeling

The condition that is being monitored by each indicator is determined by the customer. The 130-3326 Film provides a wide variety of labels in order to customize the CAM to an application.

Caterpillar Information System:

2007/12/24 Oil Suction Tube {1302}
3500B Locomotive Engines Belt Tension Chart
3516C Generator Set Engine Speed/Timing - Test
C7 and C9 On-Highway Engines Solenoid Valve - Test
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Injector Solenoid - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Alarm Modules
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module CAN Data Link - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Kilowatt Level Output
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Spare Output
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Spare Relay Outputs
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Diagnostic Codes
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) SP Fault Codes
2008/04/21 A New Wire Assembly is Used to Ground the Enclosure for the ECM {1901, 7556}
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Cat Data Link - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Customer Interface Module
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) System Communication Module (Customer)
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (AC Transformer Box) - Replace
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (Bus Transformer Box) - Replace
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Relay Module - Replace
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (Generator Set) - Replace
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Schematics and Wiring Diagrams
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Symbols
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (Generator Set) - Flash Program
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Typical Generator Abbreviations
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.