The GSC+P (setpoint SP15) must be programmed. The programmable spare relay outputs are active or inactive. In an active state, the normally open contacts will close and the normally closed contacts will open.
The condition that triggers the programmable spare relay outputs to the active state must be programmed in the GSC+P (setpoint SP16). The possible trigger conditions that can activate the programmable spare relay outputs are listed in System Operation, "Spare Input/Output Programming OP6".
Refer to System Operation, "Spare Input/Output Programming OP6" for more information on programming the setpoints for this output.
Note: The GSC+P diagnoses a fault in the spare output circuit. Refer to Testing and Adjusting, "CID 448, FMI 12 Programmable Spare Relay Failed-Test" for more information.