Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


Alarm Modules

Usage:

C32 SXC



Illustration 1g00321237

Alarm Modules

(1) Amber indicators. (2) Red indicators. (3) Lamp test switch. (4) Alarm silence switch. (5) Horn.

The ALM is an attachment. The ALM is located on the instrument panel. Red indicators (2) and amber indicators (1) are the visual indicators. The Horn (5) is the audible indicator. A 24 DCV battery system or a 32 DCV battery system powers the ALM.

The modules are either alarm modules or a remote annunciator. The versions are listed below.

  • NFPA 110 Alarm Module

  • EMCPII Remote Annunciator

The only difference between these modules is in the graphics film on the front of the panel and the jumper wires on the rear. The EMCP II remote annunciator has a lamp test switch. The following description of operation refers to the alarm/remote annunciator module as the annunciator module.

The Alarm Module (ALM) gives a warning of conditions that are becoming a problem. The warning occurs before conditions are severe enough to shut down the engine.

An alarm fault develops while the generator set is running and when the Engine Control Switch (ECS) is in the COOLDOWN/STOP position or in the AUTO position. An alarm fault develops when the generator set is not running and when ECS is in the COOLDOWN/STOP position or in the AUTO position. That fault is indicated by the optional alarm module or the remote annunciator.

Description Of Operation

Note: In the following paragraphs, the annunciator can refer to the alarm module, or the annunciator can refer to the remote annunciator module.

The annunciator receives data from the following items: switch inputs, internal circuitry and a serial data link from the GSC+PP.

Switch Inputs

Four switch inputs are available for the switch connections. Switch inputs that are connected to ground "BATT-"will be active. Refer to Table 1.

Internal Circuitry

Internal circuitry determines if the DC battery supply voltage is too low. The setpoint is set at the factory at 24 DCV.

Data Link

The annunciator module receives data from the GSC+P by a serial data link. The received data includes the following list.

  1. Coolant temperature has exceeded the high temperature alarm setpoint that is programmed into the GSC+P.

  1. Oil pressure is below the low oil pressure alarm setpoint that is programmed into the GSC+P.

  1. Coolant temperature is below the low temperature alarm setpoint that is programmed into the GSC+P.

  1. The ECS is not in the AUTO or MAN/START position.

  1. Oil pressure is below the low oil pressure shutdown setpoint that is programmed into the GSC+P.

  1. Coolant temperature has exceeded the high water temperature shutdown setpoint that is programmed into the GSC+P.

  1. The engine has failed to start(overcrank fault).

  1. The engine speed exceeded the engine overspeed setpoint that is programmed into the GSC+P.

  1. The engine is shut down due to a coolant loss fault.

  1. The engine is shut down due to a spare fault.

  1. The engine is shut down due to an emergency stop fault.

  1. The engine is shut down due to a diagnostic fault.

The first eight items control the operation of the indicators and horn. Refer to Table 1 for more information. The last four items control the operation of the horn only.

A maximum of three modules (alarm module, CIM, or RDM) can be connected to the serial data link. The maximum distance between a module and the GSC+P is 305 m (1000 ft).

The data link will malfunction under the following conditions with multiple modules:

  • One of the modules is powered down. "BATT+" or "BATT-" could be disconnected.

  • The module that is powered down remains connected to the data link.

Under these conditions the indicators controlled by the data link of the other module(s) that are powered up will flash at 0.5 hertz.

Indicator And Horn Operation

Table 1
Indicator And Horn Function    
Indicator Color     NFPA 99 ALM     EMCP RAN    
1 Amber     High Coolant Temp Alarm
LI, H, LAT, TD    
High Coolant Temp Alarm
LI, H, LAT, TD    
2 Amber     Low Coolant Temp Alarm
LI, H, LAT    
Low Coolant Temp Alarm
LI, H, LAT    
3 Amber     Low Oil Press Alarm
LI, H, LAT    
Low Oil Press Alarm
LI, H, LAT    
4 Amber     Low Fuel Level
SW(1), H    
Not In Auto
LI, H    
5 Red     Not In Auto
LI, H    
High Coolant Temp Shutdown (1)
LI, H, TD    
6 Red     Low DCV
INT, TIM    
Low DCV
INT, TIM    
7 Red     Spare
SW(3)    
Overcrank Shutdown (1)
LI, H    
8 Red     Spare
SW(4)    
Overspeed Shutdown (1)
LI, H    
    SW(2) Not Used        
( 1 ) Latched by the GSC+P

The above table lists the following abbreviations.

ALM - Alarm Module

H - Horn is sounded.

INT - The signal source is internal to the module.

LAT - "LATCHED" alarm fault

LI - The data link from the GSC+P is the signal source.

RAN - Remote Annunciator

SW - One of 4 switches is the signal source. The number in parentheses indicates which switch is the signal source.

TD - A 10 second delay occurs before the fault is annunciated.

TIM - a 60 second time delay occurs before the fault is annunciated.

When an alarm fault occurs, the corresponding indicator flashes. The indicator flashes at two hertz and the horn sounds. If the alarm fault is NOT LATCHED the indicator turns off when the alarm fault ceases. The horn also turns off when the alarm fault ceases. If the alarm fault is LATCHED, the indicator continues to flash until the "acknowledge/silence" input is activated. Refer to Table 1for LATCHED alarm faults as well as the indicator and horn functions for each operating mode.

Normally, switch input (3) (terminal 10) and switch input (4) (terminal 11) only operate indicator (7) and indicator (8). However, switch input (3) and switch input (4) can also operate the horn. Connect terminal (10) (sw input 3) to terminal (3) and connect terminal (11) (sw input 4) to terminal (4).

Alarm Silence

Activating the alarm silence switch (4) causes the horn to cease. Also, activating the alarm silence switch (4) causes the indicator to light continuously.

Data Link Malfunction

If the data link malfunctions, the indicators that are controlled by the data link flash at 0.5 hertz. The indicators that are controlled by the switches function normally.

Lamp Test

Activating the lamp test switch (3) results in sounding the horn and turning on all indicators continuously for 10 seconds or until the switch is deactivated.

Mode Selection

Table 2
Mode Selection And Switch Input Connections (1)    
Input     Mode SEL1     Mode SEL2     Switch 1     Switch 2     Switch 3     Switch 4    
Terminal     5     6     8     9     10     11    
Mode                            
NFPA 99 Alarm     (Float)     (Float)     Low Fuel Level     (Float)     Spare     Spare    
EMCP RAN     (Float)     ("B-")     (Float)     ("B-")     (Float)     (Float)    
( 1 ) NOTE: Connections in parentheses are required to select the mode specified

The annunciator module operates in one of the two modes described in Table 2. The modes are selected by connections made to the mode select inputs (terminals 5 and 6) and switch (2) input (terminal 9) as shown in Table 2.

Caterpillar Information System:

3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module CAN Data Link - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Kilowatt Level Output
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Spare Output
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Programmable Spare Relay Outputs
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Diagnostic Codes
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) SP Fault Codes
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) AL Fault Codes
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Fault Description
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Coolant Level - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Parallel Setpoint Tuning OP-11
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) AC Offset Adjustment OP10
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Engine Setpoint Verification OP9
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Injector Solenoid - Test
C7 and C9 On-Highway Engines Solenoid Valve - Test
3516C Generator Set Engine Speed/Timing - Test
3500B Locomotive Engines Belt Tension Chart
2007/12/24 Oil Suction Tube {1302}
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Alarm Module Control (Custom)
2008/04/21 A New Wire Assembly is Used to Ground the Enclosure for the ECM {1901, 7556}
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Cat Data Link - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Customer Interface Module
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) System Communication Module (Customer)
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (AC Transformer Box) - Replace
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (Bus Transformer Box) - Replace
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.