Illustration 1 | g00688554 |
Display Area Of Generator Set Control + (GSC+P) (1) Dedicated shutdown indicators (2) Spare fault indicators (3) Fault shutdown indicator (4) Fault alarm indicator (5) Upper display (6) Lower display (7) Keypad |
The dedicated shutdown indicators show the system that is responsible for an engine shutdown. The symbol and nomenclature that is located next to the indicator identifies the responsible system. Dedicated shutdown faults are activated automatically by the GSC+P. Dedicated shutdown faults depend on certain setpoints. When the GSC+P decides that operating conditions are critical, the GSC+P FLASHES the corresponding shutdown indicator. Then, the GSC+P shuts down the engine. The GSC+P does not record dedicated shutdown faults in the fault log.
The dedicated shutdown indicators (faults) are listed below.
- Low Oil Pressure
- Emergency Stop
- High Water Temperature
- Engine Overspeed
- Overcrank
To find the cause of a dedicated shutdown fault, perform the correct procedure.