Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


GSC CID 0445 - FMI 12

Usage:

C32 SXC
Conditions Which Generate This Code:

The Run Relay (RR) is located within the relay module. The GSC+P activates the RR during engine cranking and running.

Note: Whenever the GSC+P activates or the GSC+P attempts to activate the RR, "K5" is shown on the lower display. When the RR is not activated, "K5" is not shown.

The possible cause of a CID 0445 FMI 12 is an open coil or a shorted coil of the RR.

The system responses to this fault are listed below.

  • If a CID 0445 FMI 12 occurs and the RR is activated, any customer's equipment on RM-24 of the relay module will be disabled. The customer's equipment that is connected to RM-23 will be activated.

  • If a CID 0445 FMI 12 occurs and the RR is not activated, any customer's equipment on RM-24 of the relay module will not be activated. The customer's equipment that is connected to RM-23 will remain activated.

Note: The GSC+P treats a CID 0445 FMI 12 as an alarm fault. Active alarm faults are shown on the display when the "Alarm Codes" key is pressed. Also, the Engine Control Switch (ECS) must be in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.

This troubleshooting procedure is for an active CID 0445 FMI 12 or the troubleshooting procedure is for an inactive CID 0445 FMI 12.

Test Step 1. CHECK THE STATUS OF THE DIAGNOSTIC CODE.

  1. Turn the ECS to the OFF/RESET position and then turn the ECS to the STOP position.

  1. Press the "Alarm Codes" key.

  1. Observe the upper display. Check that the CID 0445 FMI 12 is active.

  1. If the diagnostic code is not active, enter the Service Mode. View the fault log for a OP1. Check that the diagnostic code is inactive.

Expected Result:

A CID 0445 FMI 12 is displayed as an active diagnostic code or CID 0445 FMI 12 is displayed as an inactive diagnostic code.

Results:

  • OK - The CID 0445 FMI 12 is active or the CID 0445 FMI 12 is inactive. Proceed to Test Step 2.

  • NOT OK - The CID 0445 FMI 12 has not occurred. The diagnostic code is not active and the diagnostic code is not inactive.STOP

Test Step 2. CHECK THE INTERNAL CABLE OF THE RELAY MODULE.

Note: Only open the relay module in a dry environment. If the inspection and repair takes more than approximately twenty minutes replace the desiccant bag in the GSC+P housing. Refer to Testing And Adjusting, "Relay Module - Replace".

  1. Turn the ECS to the OFF/RESET position.

  1. Disconnect the negative battery cable.

  1. Temporarily, remove the relay module from the GSC+P. Refer to Testing And Adjusting, "Relay Module - Replace".

  1. Check the cable that attaches the relay module to the GSC+P.

Expected Result:

The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged.

Results:

  • OK - The cable is firmly seated in the connector. The clamp is in place. The cable is not damaged. Reassemble the relay module to the GSC+P. Proceed to Test Step 3.

  • NOT OK - One or more of the components are damaged or the components are missing.

    Repair: Replace the clamp if the clamp is missing. If the cable is damaged, replace the GSC+P. Refer to Testing and Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    STOP

Test Step 3. FUNCTIONAL CHECK OF THE RUN RELAY IN THE OFF/RESET POSITION

  1. Turn the ECS to the OFF/RESET position.

  1. Reconnect the negative battery cable.

  1. Disconnect all wires from RM-23 and RM-24 of the relay module.

  1. Remove fuse "F6" from the relay module.

  1. At the relay module, measure the resistance from RM-24 to RM-8. Make a note of the resistance measurement.

  1. At the relay module, measure the resistance from RM-23 to RM-9. Make a note of the resistance measurement.

Expected Result:

The resistance measurement from RM-24 to RM-8 should be greater than 5000 ohms. The resistance measurement should be less than 5 ohms at RM-23 to RM-9.

Results:

  • OK - The resistance measurements are correct. The problem does not exist at this time. The initial problem was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal operation and watch for a recurrence.STOP

  • NOT OK - Either one of the resistance measurements are NOT correct. The relay module has failed.

    Repair: Replace the relay module. Refer to Testing And Adjusting, "Relay Module - Replace".

    STOP

Test Step 4. FUNCTIONAL CHECK OF THE RUN RELAY IN THE START POSITION

  1. Turn the ECS to the START position.

  1. The wires from RM-23 and RM-24 remain disconnected.

  1. At the relay module, measure the resistance from RM-23 to RM-9. Make a note of the resistance measurement.

  1. Measure the resistance from RM-24 to RM-8. Make a note of the resistance measurement.

Expected Result:

The resistance measurement from RM-23 to RM-9 should be greater than 5000 ohms. The resistance measurement should be less than 5 ohms at RM-24 to RM-8.

Results:

  • OK - The resistance measurements are correct. The problem does not exist at this time. The initial problem was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal operation and watch for a recurrence.STOP

  • NOT OK - Either one of the resistance measurements are NOT correct. The relay module has failed.

    Repair: Replace the relay module. Refer to Testing And Adjusting, "Relay Module - Replace".

    STOP

Caterpillar Information System:

Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0770 - FMI 09
G3600 Engines Fuel Actuator - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0590 - FMI 09
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0500 - FMI 12
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0448 - FMI 12
C13 and C15 On-highway Engines ARD Stationary Regeneration Does Not Activate
G3600 Engines Electrical Power Supply - Test
Shifting Automated Manual Transmissions{1901} Shifting Automated Manual Transmissions{1901}
2008/09/29 An Improved Three-Piece Oil Pan Gasket is Now Used {1302, 7555}
2008/02/01 Update on the Factory Password System {1901, 7620}
2008/02/18 Update on the Factory Password System {1901, 7620}
G3600 Engines Ignition Secondary - Test
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Configuration Parameters
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0441 - FMI 12
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0447 - FMI 12
C175-16 Locomotive Engine Piston and Rings
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0566 - FMI 07
G3600 Engines Choke Actuator - Test
G3520C and G3520E Generator Set Engines Fuel Control Valve - Remove and Install
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0858 - FMI 03
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1038 - FMI 03
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1038 - FMI 04
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1167 - FMI 04
2008/01/21 A New Lubricator for the Air Starting Motor is Now Used {1451}
Back to top