UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Graphics Master PWA (GM)

Usage:

ES12F CZE



Illustration 1g01279664

Graphics Master Board Location

(360) Display Interface Board

(361) Graphics Master Board




Illustration 2g01279665

(360) Display Interface Board

(361) Graphics Master Board

(361) SW1 Switch

The Graphics Master Board is located on the door of the Controls Cabinet above the Display Interface Board.

The Graphics Master Board controls the LCD touch-screen. The Graphics Master Board generates all graphics seen on the touch-screen.

The Graphics Master Board is the hub for all customer communication interfaces including the touch screen, databases, logfiles, and modem and ethernet connectivity.

Reset Display

To reset the front panel display, press the SW1 Switch (364) on the Graphics Master Board.

Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Controls Cabinet)" in order to de-energize the system and gain access to internal components.


    NOTICE

    Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. When not in use, keep the module in the static-shield bag. Follow these guidelines when you handle any module:

    Touch a grounded object to discharge static potential.

    Wear an approved wrist-strap grounding device.

    Do not touch the bus connector or connector pins.

    Do not touch circuit components inside the module.

    If available, use a static-safe work station.


  1. Disconnect all connectors from the board. The connectors locations in the unit are labeled. Verify each connector to make sure that the label is present and legible.

  1. Unscrew the four plastic cross tip screws from the four corners of the Board.

Installation


NOTICE

Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. When not in use, keep the module in the static-shield bag. Follow these guidelines when you handle any module:

Touch a grounded object to discharge static potential.

Wear an approved wrist-strap grounding device.

Do not touch the bus connector or connector pins.

Do not touch circuit components inside the module.

If available, use a static-safe work station.


  1. Position the board in the cabinet over the four plastic stand-offs that are connected to the back of the door panel.

  1. Attach the Board with four cross tip screws at the four corners of the Board.

    Note: Do not over tighten the plastic screws to prevent stripping the threads.

  1. Plug the wire connectors into the correct connectors on the board. Check the labels on each connector for proper placement.

    Note: Do not replace the plastic screws that hold the Graphics Master Board to the door with metal screws.

Caterpillar Information System:

C13 On-highway Engine Engine Oil Pan
C13 On-highway Engine Camshaft
2006/07/24 A New Speed-Timing Sensor Is Available {1912}
2006/07/24 A New Speed-Timing Sensor is Available {1912}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Display Interface PWA
C280 Marine Auxiliary Engines Emergency Stop Switch
2006/06/26 Hole in the Turbine Housing of the Turbocharger {1052}
TH48-E70 Petroleum Transmission Magnetic Screen (Transmission) - Clean
C13 On-highway Engine Exhaust Manifold
Storage and Troubleshooting for the Vacuum Pump {4287} Storage and Troubleshooting for the Vacuum Pump {4287}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Contactor (K3, K4)
C280 Marine Auxiliary Engines Fuel Injection Enable
C13 On-highway Engine Exhaust Extension
C13 and C15 On-Highway Engines Fire Prevention and Explosion Prevention
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Front Panel Display
C4.4 Industrial Engine Valve Depth - Inspect
C280 Marine Auxiliary Engines Engine Cranks but Will Not Start
C280 Marine Auxiliary Engines Engine Misfires, Runs Rough or Is Unstable
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Local EPO/EMO Button
C280 Marine Auxiliary Engines Intermittent Engine Shutdown
Metal Shavings in the Hydraulic Electronic Unit Injector (HEUI) Oil Passages{1250, 1274} Metal Shavings in the Hydraulic Electronic Unit Injector (HEUI) Oil Passages{1250, 1274}
2006/10/30 New Marine Software Is Now Available {1901, 1902, 7490, 7620}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Parallel Service Switch
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Remote EPO Button
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.