- Parameter programming
- Response configuration
- Set delay times
The default settings for the parameters are programmed at the factory. To accommodate unique applications and sites, some of the parameters may be reprogrammed with Cat ET. The screens of Cat ET provide guidance for the changing of trip points.
Note: Some parameters require no password in order to be changed. Other parameters can be changed with customer passwords. Some of the parameters are protected by factory passwords. There are some parameters that cannot be changed.
Changing the Settings of the Monitoring System
Use the following procedure to change settings of the parameters:
- Select the "Service/Monitoring System" screen on Cat ET.
- Highlight the desired parameter. Then click the "Change" button in the lower left corner of the screen.
The "Change Monitor System" screen will appear.
- Change the "State" of the parameter.
- Set the "Trip Point" and the "Delay Time" according to the "Allowed Values" that are displayed in the lower half of the screen.
- Click the "OK" button.
If a password is required, the "Enter Passwords" screen will appear. Enter the correct passwords and then click the "OK" button.
Note: If a factory password is required, the "Enter Factory Passwords" screen will appear. Refer to Troubleshooting, "Factory Passwords" for information that is related to obtaining factory passwords.
The new settings will be effective immediately.
Default Settings of the Monitoring System
Examples of the default settings for the parameters are listed in Table 1. The values may have changed. Use the Cat ET to determine the programming for your engine. Many of the items can be reprogrammed in order to accommodate the requirements of individual sites.
Default Settings of the Programmable Monitoring System     | |||||||
---|---|---|---|---|---|---|---|
Parameter     | System Response     | State     | Security Level Password     |
Trip Point     | Range     | Delay in Seconds     | Range of the Delay in Seconds     |
E004 Engine Overspeed Shutdown     | Shutdown     | On     | Factory     | 1750 rpm     | 1200 to 2160 rpm     | 0     | 0     |
E015 High Engine Coolant Temperature Derate     | Derate     | Off     | Customer     | 111 °C     | 80 to 129 °C     | 20     | 1 to 60     |
E016 High Engine Coolant Temperature Shutdown     | Shutdown     | On     | 113 °C | ||||
E017High Engine Coolant Temperature Warning     | Warning     | On     | 109 °C | ||||
E019 High Engine Oil Temperature Shutdown     | Shutdown     | On     | Factory     | 104 °C     | 85 to 104 °C     | ||
E020 High Engine Oil Temperature Warning     | Warning     | On     | Customer     | 102 °C     | 80 to 102 °C     | ||
E025 High Inlet Air Temperature Derate (Low Engine Load)     | Derate     | Off     | Customer     | 100 °C     | 32 to 100 °C     | ||
E025 High Inlet Air Temperature Derate (High Engine Load)     | |||||||
E026 High Inlet Air Temperature Shutdown (Low Engine Load)     | Shutdown     | On     | 70 °C | ||||
E026 High Inlet Air Temperature Shutdown (High Engine Load)     | 80 °C | ||||||
E027 High Inlet Air Temperature Warning (Low Engine Load)     | Warning     | 69 °C | 32 to 85 °C | ||||
E027 High Inlet Air Temperature Warning (High Engine Load)     | 32 to 100 °C | ||||||
E038 Low Engine Coolant Temperature Warning     | 5 °C | 5 to 80 °C | |||||
E042 Low System Voltage Shutdown     | Shutdown     | On     | Read Only     | 18 VDC     | 18 to 24 VDC     | 10     | 1 to 60     |
E043 Low System Voltage Warning     | Warning     | 20 VDC | 20 | ||||
E050 High System Voltage Warning     | 34 VDC | 18 to 34 VDC | |||||
E053 Low Fuel Pressure Warning     | Customer | 105 kPa | 100 to 135 kPa     | 10     | |||
E096 High Fuel Pressure     | 135 kPa | ||||||
E127 Engine Oil Filter Diff Pressure Low Warning     | On | Customer     | 35 kPa     | 7 to 80 kPa     | 10     | 1 to 60     | |
E128 Engine Oil Filter Diff Pressure Low Shutdown     | Shutdown | Factory     | 7 kPa     | ||||
E129 Engine Oil Filter Diff Pressure High Warning     | Warning | Customer     | 103 kPa     | 80 to 138 kPa     | |||
E130 Engine Oil Filter Diff Pressure High Shutdown     | Shutdown | Factory     | 138 kPa     | ||||
E135 Low Jacket Water Pressure Shutdown     | This item cannot be programmed. | ||||||
E337 High Engine Oil to Engine Coolant Diff Temp     | Warning     | On     | Customer     | 14 °C     | 0 to 20 °C     | 20     | 1 to 60     |
Shutdown | On     | Factory     | 20 °C     |
Separate timers are used in the ECM for each response that is associated with a parameter. If a trip point is reached, the timer for that event is started.
For example, the warning for "High Engine Coolant Temperature E017(1)" can be set to 95 °C with a five second delay. The timer starts counting if the coolant temperature reaches 95 °C. If the temperature is not reduced to less than 95 °C within 5 seconds, the event becomes active and the event is logged.
Conditions for Parameters
Some of the programmable parameters are dependent on the status of an ECM output before the parameters are allowed to function. Some of the parameters are allowed to function after the crank terminate relay has been energized for more than 30 seconds. Other parameters are allowed to function after the output for the fuel control relay is energized. Some parameters are not dependent upon any conditions.
The conditions are designed to eliminate false events during start-up if the customer has programmed a delay time to zero. The conditions are listed in Table 2.
Conditions for Activation for Monitoring the Parameters     | |
Parameter     | Condition     |
Low System Voltage     | None     |
High Engine Coolant Temperature     | The crank terminate relay is energized for more than 30 seconds.     |
Low Engine Coolant Temperature     | None     |
Engine Overspeed     | None     |
High Engine Oil Temperature     | The crank terminate relay is energized for more than 30 seconds.     |
High Oil Filter Differential Pressure     | |
Low Oil Filter Differential Pressure     | |
High Fuel Temperature     | |
Low Fuel Pressure     | The fuel control relay is energized.     |
High Engine Oil to Engine Coolant Differential Temperature     | The crank terminate relay is energized for more than 30 seconds.     |
Low Gas Fuel Differential Pressure     | The fuel control relay is energized.     |
High Gas Fuel Differential Pressure     | |
High System Voltage     | None     |
High Inlet Air Temperature at Low Engine Load     | The crank terminate relay is energized for more than 30 seconds.     |
High Inlet Air Temperature at High Engine Load     | |
High Fuel Pressure     | The fuel control relay is energized.     |
Low Oil Pressure     | The run relay is energized.     |
Low Jacket Water Pressure     | The crank terminate relay is energized for more than 30 seconds.     |
High Jacket Water Inlet Pressure     | The crank terminate relay is energized for more than 30 seconds.     |
Driven Equipment Start Inhibit     | None     |
Low Engine Pre-Lube Pressure Start Inhibit     | None     |
Engine Overload     | The crank terminate relay is energized for more than 10 seconds.     |
Unexpected Engine Shutdown     | The crank terminate relay is energized.     |
Customer Fault     | None     |
Driven Equipment Shutdown Requested     | The crank terminate relay is energized.     |
Detonation     | None     |
Use care when you program the trip points and the delay times. Ensure that the response of the ECM is correct for the application. The monitoring system will accept any settings within the ranges.
The trip point for a shutdown may be programmed to activate before the warning. In that case, the engine will shut down and the warning will not be activated.