Electronic Modular Control Panel II (EMCP II) Caterpillar


GSC CID 0269 - FMI 03

Usage:

3406B 4JK
Conditions Which Generate This Code:


Illustration 1g00596717

The EMCP II has a sensor supply voltage of 8 DCV from the GSC that powers the engine sensors. The sensors that are displayed in 1 illustration may vary. The sensors may vary according to the engine. See table 1 in order to determine the sensors that are on your engine.

Table 1
Sensor     MUI Engines     EUI Engines    
Coolant Temperature     Yes     No    
Oil Pressure     Yes     No    
Coolant Loss     Yes     Yes    

The sensor power supply functions whenever power is applied to the GSC.

The GSC is usually programmed in the factory. The GSC deals with a problem with the sensor power supply CID 0269 FMI 03 as an alarm fault. P04 = 0. If the GSC is programmed to shutdown, P04 is equal to 1 for a problem with the sensor power supply. It is not necessary to press the "Alarm Codes" key in order to view the CID 0269 FMI 03. The CID 0269 FMI 03 is automatically shown on the upper display.

Diagnostic codes are created when the harness connector is disconnected from the GSC during these troubleshooting procedures. Clear these created diagnostic codes after the particular problem is corrected and the particular diagnostic code is cleared.

The possible cause of a CID 0269 FMI 03 happens when the voltage of the sensor power supply is greater than 8.5 DCV.

Begin performing these procedures only when CID 0269 FMI 03 is showing and the "DIAG" indicator is FLASHING on the upper display. The GSC treats a CID 0269 FMI 03 as an alarm fault. Active alarm faults are shown on the upper display when the "Alarm Codes" key is pressed and the engine control switch (ECS) is in any position except the OFF/RESET position. For an inactive diagnostic code, the problem may be intermittent. To troubleshoot an inactive diagnostic code, use the preceding system schematic and see Testing And Adjusting, "Electrical Connector - Inspect". Clear the diagnostic code from the fault log after the troubleshooting procedure is completed.

Test Step 1. CHECK THE GSC.

  1. Disconnect the harness from the GSC.

  1. Turn the ECS to OFF/RESET and then turn the ECS to the STOP position.

  1. Press the "Alarm Codes" key.

  1. Observe the upper display for the CID 0269 FMI 03.

Expected Result:

The CID 0269 FMI 03 should not be showing. The diagnostic code should be inactive.

Results:

  • OK - The CID 0269 FMI 03 is not showing. The GSC is functioning properly. Therefore, the engine harness has a short to "B+".

    Repair: Repair the engine harness or replace the engine harness.

    Stop.

  • NOT OK - The CID 0269 FMI 03 is not showing.

    Repair: The GSC may have failed. It is unlikely that the GSC has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC. See Testing And Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    Stop.

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) GSC CID 0268 - FMI 02
Electronic Modular Control Panel II (EMCP II) GSC CID 0248 - FMI 09 (for EUI Engines)
3500 Generator Set Engines Jacket Water Heater
CPT372 Truck Mounted Pumper Specifications
C12 Marine Engine Engine Valve Lash - Inspect/Adjust
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Recoil Spring - Assemble
Electronic Modular Control Panel II (EMCP II) GSC CID 0190 - FMI 03
Electronic Modular Control Panel II (EMCP II) GSC CID 0190 - FMI 02
SR4 Generator with VR3 or VR4 Voltage Regulator Rotor - Remove and Install
SR4 Generator with VR3 or VR4 Voltage Regulator Generator - Align
3054 and 3056 Marine Generator Set Engines Air Inlet Heater - Remove and Install
Electronic Modular Control Panel II (EMCP II) GSC CID 0168 - FMI 04
Electronic Modular Control Panel II (EMCP II) GSC CID 0269 - FMI 04
3408E and 3412E Industrial Engines Air Starting Motor
Electronic Modular Control Panel II (EMCP II) GSC CID 0333 - FMI 03
C0.5, C0.7, C1.1/3011C, C1.5/3013C, C1.6 and C2.2/3024C/3024CT Industrial Engines and Engines for Caterpillar Built Machines Piston Height - Inspect
Electronic Modular Control Panel II (EMCP II) GSC CID 0333 - FMI 04
C12 Marine Engines Engine Rating Definitions
3054 and 3056 Marine Generator Set Engines Heat Exchanger - Disassemble - 3054 Engine
Electronic Modular Control Panel II (EMCP II) GSC CID 0334 - FMI 03 (for EUI Engines)
3054 and 3056 Marine Generator Set Engines Heat Exchanger - Assemble - 3054 Engine
3500 Generator Set Engines Turbocharger
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Adjuster - Disassemble
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Adjuster - Assemble
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.