G3516B Engines Caterpillar


Oxygen Sensor Buffer Supply

Usage:

G3516B 7EZ
System Operation Description:

The oxygen buffer uses an oxygen sensor in order to measure the concentration of oxygen in the engine exhaust.

The oxygen buffer receives power from terminal P2-13 on the ECM. The return circuit is through terminal P2-23. The buffer provides a power supply of 1.5 amperes and 10.5 volts between the positive VH and negative VH terminals in order to power a resistive type of heater in the oxygen sensor. After this heater raises the temperature of the sensing element to 700 °C (1292 °F), the buffer regulates the current from the positive IP terminal to the negative IP terminal. This keeps the voltage between the positive VS terminal and negative VS terminal relatively constant.

The amount of current is a measure of the concentration of oxygen in the exhaust gases. The current will vary from 0 mA at 0 percent of oxygen to approximately 8.7 mA at 21 percent of oxygen. The oxygen buffer measures this current. The buffer converts the current to a Pulse Width Modulated signal (PWM) with a nominal frequency of 500 Hz. This signal is supplied to terminal P2-67.

The duty cycle of the PWM signal has a range of 30 to 65 percent. The 30 percent corresponds to 0 percent of oxygen and the 65 percent corresponds to 21 percent of oxygen. These values vary slightly between different buffers and sensors. Calibration is required for every new buffer. Calibration of the buffer is also required after every 1500 service hours. Some applications may require more frequent calibration or less frequent calibration.

The oxygen buffer is equipped with a diagnostic circuit that detects the current which is provided to the heating element of the oxygen sensor. If this current is too low, the buffer assumes that the oxygen sensor has failed or the sensor is disconnected from the oxygen buffer. This will cause the PWM signal from the oxygen buffer to change to a duty cycle of approximately 15 percent. The ECM interprets this condition as a diagnostic condition. The ECM will generate a diagnostic code that can be viewed with the Caterpillar Electronic Technician (ET).

The sensor provides a wet reading that is slightly lower than a dry reading. The wet reading is multiplied by a conversion factor of approximately 1.25 in order to obtain the reading that is displayed on Cat ET. This allows oxygen readings from Cat ET to be compared to dry readings from an emissions analyzer. The ECM uses the signal of the percent of oxygen for two functions:

  • Make corrections for variation of fuel BTU.

  • Maintain desired emissions levels.

If an incorrect signal is detected by the ECM, a diagnostic code is activated and compensation for fuel quality is disabled. Problems with the circuit for the oxygen signal must be repaired as soon as possible because of the effects on engine performance and emissions.



Illustration 1g01075330
Schematic of the circuit for the oxygen buffer and the oxygen sensor

Test Step 1. Inspect the Electrical Connectors and Wiring

    ------ WARNING! ------

    During operation, the oxygen sensor may reach temperatures that exceed 700 °C (1292 °F). Severe personal injury and property damage will result from contact with a hot oxygen sensor.

    Do not touch the sensor during engine operation, calibration, or testing. Allow the sensor to cool before moving the sensor. Wear gloves that resist heat. Do not place the sensor on or near any flammable material or any surface that can be damaged by high temperatures.




    Illustration 2g01075275
    Terminal box
    (1) ECM connectors J2/P2
    (2) 16 amp circuit breaker
    (3) J10/P10 connectors for the harness from the oxygen buffer

  1. Set the engine control to the OFF/RESET mode. Switch 16 amp circuit breaker (2) to the OFF position.

    Note: For the following steps, refer to Troubleshooting, "Inspecting Electrical Connectors".

  2. Thoroughly inspect the following connections:

    • J2/P2 connectors

    • J10/P10 connectors on the terminal box

    1. Check the torque of the allen head screw for the ECM connector. The proper torque is 6 ± 1 N·m (55 ± 9 lb in).


      Illustration 3g01075280
      Harness side of the P2 connector
      (P2-13) +24 VDC for the buffer
      (P2-23) Return
      (P2-53) Shield
      (P2-67) Oxygen signal (PWM)


      Illustration 4g00894829
      Harness side of the P10 connector
      (P10-K) +24 VDC for the buffer
      (P10-H) Shield
      (P10-L) Return
      (P10-M) Oxygen signal (PWM)

    2. Perform a 45 N (10 lb) pull test on each of the wires that are associated with the circuit for the oxygen buffer.


      Illustration 5g01075292
      Left side view
      (1) Oxygen sensor
      (2) Connectors for the oxygen sensor
      (3) Oxygen buffer
      (4) P651 connectors for the harness from the terminal box
      (5) P652 connectors for the harness to the oxygen sensor

    3. Check the harness and wiring for abrasion and for pinch points from the oxygen sensor to the ECM.

Expected Result:

All of the connectors, pins, and sockets are connected properly. The connectors and the wiring do not have corrosion, abrasion, or pinch points.

Results:

  • OK - The components are in good condition with proper connections. Proceed to Test Step 2.

  • Not OK - The components are not in good condition and/or at least one connection is improper.

    Repair: Perform the necessary repairs and/or replace parts, if necessary. Ensure that all of the seals are properly installed. Make sure that the connections are properly fastened. Verify that the repair has eliminated the problem.

    STOP

Test Step 2. Check for Diagnostic Codes for the Oxygen Buffer

  1. Connect Cat ET to the service tool connector on the terminal box. Refer to Troubleshooting, "Electronic Service Tools".

  2. Switch the 16 amp circuit breaker ON. Set the engine control to the STOP mode.

  3. Access the "Logged Diagnostic Codes" screen on Cat ET. If the following codes are logged, clear the codes:

    • 1088-05 Oxygen Sensor Power Supply open circuit

    • 1088-06 Oxygen Sensor Power Supply short to ground

  4. Access the "Diagnostic Override" screen of Cat ET. Select "Diagnostics/Diagnostic Tests/Override Parameters".

  5. Select "Oxygen Sensor Override" under the "Description" column.

  6. Select "Change" in the lower left corner of the screen. A popup window with the title "Change Parameter Value" will appear.

  7. Select a "New Value" of "On" and then select "OK". Allow a minimum of ten seconds for the diagnostic codes to be activated.

    The oxygen buffer is now ON. The "Value" of the "Oxygen Sensor Override" should change to "On".

    Note: After you exit the "Override Parameters" screen, the "Value" of the "Oxygen Sensor Override" is automatically changed to "OFF" when the engine control is not in the START mode.

  8. Access the "Logged Diagnostic Codes" screen again. Look for the 1088-05 or 1088-06 diagnostic codes again.

Expected Result:

A 1088-05 or 1088-06 diagnostic code is logged.

Results:

  • Logged 1088-05 diagnostic code - The supply for the buffer has an open circuit or a short circuit to the +Battery side. Proceed to Test Step 3.

  • Logged 1088-06 diagnostic code - The supply for the buffer has a short circuit to ground. Proceed to Test Step 5.

  • No codes - The supply for the buffer is OK.

    STOP

Test Step 3. Check the Supply Voltage for the Oxygen Buffer

  1. Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

  2. Disconnect the P651 connector from the oxygen buffer.

  3. Switch the 16 amp circuit breaker ON. Set the engine control to the STOP mode.

  4. Access the "Diagnostic Override" screen of Cat ET. Select "Diagnostics/Diagnostic Tests/Override Parameters".

  5. Select "Change" in the lower left corner of the screen.

  6. Select a "New Value" of "On" and then select "OK".

    The oxygen buffer is now ON. The status of the "Oxygen Sensor Override" should change to "On". Wait for 65 seconds.

    Note: After you exit the "Override Parameters" screen, the status of the "Oxygen Sensor Override" is automatically changed to "OFF" when the engine control is not in the START mode.



    Illustration 6g00894897
    P651 harness connector for the oxygen buffer
    (P651-A) +24 VDC for the buffer
    (P651-B) Return

  7. Measure the voltage between terminals P651-A and P651-B.

Expected Result:

The supply voltage for the oxygen buffer is greater than 18 VDC.

Results:

  • OK - The supply voltage for the oxygen buffer is greater than 18 VDC. The buffer is receiving the correct supply voltage.

    Repair: Reconnect the connectors. Determine whether the diagnostic code recurs. If the problem is not resolved, set the engine control to the OFF/RESET mode and switch the 16 amp circuit breaker OFF. Replace the oxygen buffer. After you replace the buffer, calibrate the oxygen sensor. Follow the instructions in Troubleshooting, "Oxygen Sensor - Calibrate".

    STOP

  • Not OK - The supply voltage is less than 18 VDC. Proceed to Test Step 4.

Test Step 4. Check the Voltage at the Terminal Box

  1. Disconnect the P10 connector from the terminal box.


    Illustration 7g01077015
    Side view of the terminal box and the J10 connector
    (J10-K) +24 VDC
    (J10-L) Return

  2. Measure the voltage between terminals J10-K and J10-L.

Expected Result:

The voltage is greater than 18 VDC.

Results:

  • OK - The voltage is greater than 18 VDC. There is a problem with the harness between the terminal box and the oxygen buffer.

    Repair: Repair the harness, when possible. Replace parts, if necessary.

    STOP

  • Not OK - The voltage is less than 18 VDC. Proceed to Test Step 6.

Test Step 5. Disconnect the Oxygen Buffer and Check for a Short to Ground

  1. Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

  2. Disconnect the P651 connector from the oxygen buffer.

  3. Switch the 16 amp circuit breaker ON. Set the engine control to the STOP mode.

  4. Access the "Logged Diagnostic Codes" screen on Cat ET. If a 1088-06 diagnostic code is logged, clear the code.

  5. Access the "Diagnostic Override" screen of Cat ET. Select "Diagnostics/Diagnostic Tests/Override Parameters".

  6. Select "Change" in the lower left corner of the screen.

  7. Select a "New Value" of "On" and then select "OK". Wait for a minimum of 65 seconds.

    The oxygen buffer is now ON. The status of the "Oxygen Sensor Override" should change to "On". Wait for 65 seconds.

    Note: After you exit the "Override Parameters" screen, the status of the oxygen sensor is automatically changed to "OFF" when the engine control is not in the START mode.

  8. Access the "Logged Diagnostic Codes" screen again. Look for the 1088-06 diagnostic code.

Expected Result:

There is a logged 1088-06 diagnostic code.

Results:

  • Yes - The supply for the buffer still has a short circuit. Proceed to Test Step 7.

  • No - The supply for the buffer does not have a short circuit when the buffer is disconnected. The harness to the buffer is OK.

    Repair: Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

    Inspect the J651/P651 connectors for corrosion and/or damage. Make repairs, as needed.

    If the condition is not resolved, replace the buffer. Be sure to calibrate the oxygen sensor after you replace the buffer. Refer to Troubleshooting, "Oxygen Sensor - Calibrate".

    STOP

Test Step 6. Create a Short Circuit in the Harness

  1. Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

  2. Disconnect the P651 connector from the oxygen buffer.


    Illustration 8g00894897
    P651 connector on the harness for the oxygen buffer
    (P651-A) +24 VDC for the buffer
    (P651-B) Return

  3. Install the ends of a jumper wire into terminals P651-A and P651-B.

  4. Switch the 16 amp circuit breaker ON. Set the engine control to the STOP mode.

  5. Access the "Logged Diagnostic Codes" screen on Cat ET. If a 1088-05 diagnostic code is logged, clear the code.

  6. Access the "Diagnostic Override" screen of Cat ET. Select "Diagnostics/Diagnostic Tests/Override Parameters".

  7. Select "Change" in the lower left corner of the screen.

  8. Select a "New Value" of "On" and then select "OK". Wait for 65 seconds.

    The oxygen buffer is now ON. The status of the "Oxygen Sensor Override" should change to "On". Wait for 65 seconds.

    Note: After you exit the "Override Parameters" screen, the status of the oxygen sensor is automatically changed to "OFF" when the engine control is not in the START mode.

  9. Access the "Logged Diagnostic Codes" screen again. Look for the 1088-05 diagnostic code.

Expected Result:

The 1088-05 diagnostic code is not logged when the circuit for the supply to the buffer is shorted by the jumper wire.

Results:

  • OK - The 1088-05 diagnostic code is not logged when the circuit for the supply to the buffer is shorted by the jumper wire. The harness and the ECM are OK.

    Repair: Perform the following steps:

    1. Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

    2. Inspect the J651 and P651 connectors for corrosion and other damage. Make repairs, as needed.

      If the condition is not resolved, replace the oxygen buffer. Be sure to calibrate the oxygen sensor after you replace the buffer. Refer to Troubleshooting, "Oxygen Sensor - Calibrate".

    STOP

  • Not OK - The 1088-05 diagnostic code is logged when the circuit for the supply to the buffer is shorted by the jumper wire. The ECM does not detect the short circuit. Proceed to Test Step 7.

Test Step 7. Check the Supply for the Oxygen Buffer at the ECM

  1. Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.


    Illustration 9g01075309
    Terminal box and P2 connector
    (P2-13) +24 VDC for the buffer
    (P2-23) Return

  2. Use a 151-6320 Wire Removal Tool in order to remove terminals P2-13 and P2-23.

    This will create an open circuit between the buffer and the ECM.

  3. Switch the 16 amp circuit breaker ON. Set the engine control to the STOP mode.

  4. Access the "Logged Diagnostic Codes" screen on Cat ET. If a 1088-05 or 1088-06 diagnostic code is logged, clear the code.

  5. Access the "Diagnostic Override" screen of Cat ET. Select "Diagnostics/Diagnostic Tests/Override Parameters".

  6. Select "Change" in the lower left corner of the screen.

  7. Select a "New Value" of "On" and then select "OK". Wait for a minimum of 65 seconds.

    The oxygen buffer is now ON. The status of the "Oxygen Sensor Override" should change to "On". Wait for 65 seconds.

    Note: After you exit the "Override Parameters" screen, the status of the oxygen sensor is automatically changed to "OFF" when the engine control is not in the START mode.



    Illustration 10g01075312
    Jumper wire on the harness side of the P2 connector
    (P2-13) +24 VDC for the buffer
    (P2-23) Return

  8. Install a jumper wire into terminals P2-13 and P2-23. Pull on the jumper wire in order to verify proper installation.

    This will create a short circuit between the supply and the return of the buffer circuit.

  9. Access the "Logged Diagnostic Codes" screen again. Allow a minimum of ten seconds for any diagnostic codes to be activated. Look for the 1088-05 or 1088-06 diagnostic code.

Expected Result:

When an open circuit was created, a 1088-05 diagnostic code was activated.

When a short circuit was created, a 1088-06 diagnostic code was activated.

Results:

  • Yes - When an open circuit was created at the P2 connector, a 1088-05 diagnostic code was activated. When a short circuit was created at the P2 connector, a 1088-06 diagnostic code was activated. The ECM is OK. There is a problem in the harness between the ECM and the oxygen buffer.

    Repair: Perform the following procedure:

    Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

    Use a 151-6320 Wire Removal Tool to remove the jumper wire from the P2 connector.

    Reinstall the terminals into P2-12 and P2-23. Pull on the wires in order to verify proper installation of the terminals.

    Repair the harness, when possible. Replace parts, if necessary.

    STOP

  • No - The ECM did not detect an open circuit and/or a short circuit. There may be a problem with the ECM.

    Repair: Perform the following procedure:

    Set the engine control to the OFF/RESET mode. Switch the 16 amp circuit breaker OFF.

    Use a 151-6320 Wire Removal Tool to remove the jumper wire from the P2 connector.

    Reinstall the terminals into P2-12 and P2-23. Pull on the wires in order to verify proper installation of the terminals.

    It is unlikely that the ECM has failed. Exit this procedure and perform this procedure again. If the problem is not resolved, perform the following steps:

    Temporarily install a new ECM. Refer to Troubleshooting, "Replacing the ECM".

    If the problem is resolved with the new ECM, install the original ECM and verify that the problem returns. If the new ECM operates correctly and the original ECM does not operate correctly, replace the original ECM. Refer to Troubleshooting, "Replacing the ECM".

    STOP

Caterpillar Information System:

JF Series Starting Motor Component Description
3126B and 3126E On-highway Engines Cooling Fan Circuit and A/C High Pressure Switch Circuit - Test
JF Series Starting Motor Normal Operation
3306C Truck Engine Fuel Injection Timing - Check
JF Series Starting Motor General Information
PM3516 Power Modules Safety Messages
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0858 - FMI 04
3306C Truck Engine Fuel Injection Nozzle - Test
Electronic Modular Control Panel II+ (EMCP II+) Engine Does Not Shutdown (for MUI 3306B, 3406C Engines)
3306C Truck Engine Finding Top Center Position for No. 1 Piston
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0444 - FMI 12 (for MUI and EUI Engines)
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0858 - FMI 03
PM3412C Power Modules Roading
EMCPII+ for Gas Engines GSC CID 0111 - FMI 03
3524B Engines for Off-Highway Trucks Electronic Service Tool Will Not Communicate with ECM
3306C Truck Engine Fuel Ratio Control - Adjust
Electronic Modular Control Panel II+ (EMCP II+) Starting Motor Remains Engaged (for EUI and PEEC Engines)
3306C Truck Engine Fuel Setting - Adjust
37-MT, 41-MT, and 42-MT Series Starting Motors Starting Motor - Disassemble - 37-MT and 41-MT
3306C Truck Engine Engine Speed - Check
3306C Truck Engine Governor - Adjust
3406E On-Highway Engine Gear Group (Front) - Install
PM3516 Power Modules Model View Illustrations
Electronic Modular Control Panel II+ (EMCP II+) Indicator for Overcrank (for MUI and EUI Engines)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.