Uninterruptible Power Supply (UPS) 250 Caterpillar


AC Current - Calibrate

Usage:

UPS 250 BEE
Perform this procedure after conducting one of the following procedures: Testing and Adjusting, "AC Interface Board - Remove and Install" and Testing and Adjusting, " System Controller Board - Remove and Install".

Note: If the procedure Testing and Adjusting, "System Controller Board - Remove and Install" is conducted, the following calibration procedures are required: Testing and Adjusting, "Flywheel Telemetry - Calibrate"Testing and Adjusting, "AC Current - Calibrate", Testing and Adjusting, "AC Voltage - Calibrate" and Testing and Adjusting, "DC Bus Voltage - Calibrate".

Table 1
Required Tools    
Part Number     Description    
155-5175     AC Current Probe    
146-4080     Digital Multimeter    
OR    
9U-7330     Digital Multimeter    

  1. Place the keyswitch in the BYPASS position.

  1. Secure the system. Verify that all the high voltage inputs to the system are open. Ensure that the flywheel is at zero rpm.

  1. Remove the lower sheet metal panel and the panel for the System I/O Interface Board. The panel for the System I/O Interface Board is located in the lower left side of the cabinet.



    Illustration 1g00700951

    (1) Serial Terminal "J1"

  1. Connect a PC to the RS-232/RS-485 port ("J1"). The port is located on the bottom back corner of the system's I/O board. This must be accomplished prior to the application of high voltage to the system.

  1. Close the high voltage inputs to the system.

    The system will start. The system will remain in "Bypass". The PC should be communicating with the system.

  1. Click on "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.



    Illustration 2g00697157

    The "Enter User Name / Password" dialog box

  1. Enter a valid "User Name" and then enter a valid "Password".

    After the password has been entered, the menu options will change. The menu bar will contain a "Calibrate" option.




    Illustration 3g00737245

    The "Calibrate" drop-down menu

  1. Click on the "Calibrate" drop-down menu. Select the "AC Currents" option.



    Illustration 4g00737241

    The "Calibration of a channel" window

  1. A "Calibration of a channel" window will appear.

  1. Click on the "View Status" button in the "Calibration of a channel" window.



    Illustration 5g00737259

    "Calibration Group Status" window

  1. A "Calibration Group Status" window will open. Click on the "USE DEFAULTS" button on the "Calibration of a channel" window.

  1. You are prompted to enter the MINIMUM value for "Current In Ph. A".



    Illustration 6g00698435

    (1) Ground Terminal

    (2) Output Terminals

    (3) Neutral Terminal

    (4) AC Input Terminals

  1. Clamp the probe of the meter around the INPUT conductor for "Phase A". Record the meter reading.

  1. Enter the value from Step 13 in the "Enter the value" field of the "Calibration of a channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the field for the MINIMUM value of "Current In Ph. B".

    The "Calibration Group Status" window will display "Minimum value entered for ph. A Current In.".

  1. Clamp the probe of the meter around the INPUT conductor for "Phase B". Record the meter reading.

  1. Enter the value from Step 16 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the field for the MINIMUM value of "Current In Ph. C".

    The "Calibration Group Status" window will display "Minimum value entered for ph. B Current In.".

  1. Clamp the probe of the meter around the INPUT conductor for "Phase C". Record the meter reading.

  1. Enter the value from Step 19 in the "Enter the value" field of the "Calibration of a channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MINIMUM value for the "Current Out Ph. A" field.

    The "Calibration Group Status" window will display "Minimum value entered for ph. C Current In.".

  1. You are prompted to enter the MINIMUM value for "Current Out Ph. A".

  1. Enter the MINIMUM value for "Current Out Ph. A". Enter "0.0".

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MINIMUM value for the "Current Out Ph. B" field.

    The "Calibration Group Status" window will display "Minimum value entered for current out Ph. A".

  1. You are prompted to enter the MINIMUM value for "Current Out Ph. B".

  1. Enter the MINIMUM value for "Current Out Ph. B". Enter "0.0".

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MINIMUM value for the "Current Out Ph. C" field.

    The "Calibration Group Status" window will display "Minimum value entered for current out Ph. B".

  1. You are prompted to enter the MINIMUM value for "Current Out Ph. C".

  1. Enter the MINIMUM value for "Current Out Ph. C". Enter "0.0".

  1. Click on the "OK" button. When you depress the "OK" button, the "Calibration Group Status" window will display "Minimum value entered for current out Ph. C".

  1. Click on the "MAXIMUM" button.

  1. Add the approximate full load to the system, while the system remains in the "Bypass" mode.

  1. You are prompted to enter the MAXIMUM value for "Current In Ph. A".



    Illustration 7g00698435

    (1) Ground Terminal

    (2) Output Terminals

    (3) Neutral Terminal

    (4) AC Input Terminals

  1. Clamp the probe of the meter around the INPUT conductor for "Phase A". Record the meter reading.

  1. Enter the value from Step 45 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MAXIMUM value for the "Current In Ph. B" field.

    The "Calibration Group Status" window will display "Calibration complete but not saved for current in Ph. A".

  1. You are prompted to enter the MAXIMUM value for "Current In Ph. B".

  1. Clamp the probe of the meter around the INPUT conductor for "Phase B". Record the meter reading.

  1. Enter the value from Step 49 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MAXIMUM value of the "Current In Ph. C" field.

    The "Calibration Group Status" window will display "Calibration complete but not saved for current in Ph. B".

  1. Clamp the probe of the meter around the INPUT conductor for "Phase C". Record the meter reading.

  1. Enter the value from Step 52 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MAXIMUM value for the "Current Out in Ph. A" field.

    The "Calibration Group Status" window will display "Calibration complete but not saved for current in Ph. C".

  1. You are prompted to enter the MAXIMUM value for "Current Out Ph. A".



    Illustration 8g00698435

    (1) Ground Terminal

    (2) Output Terminals

    (3) Neutral Terminal

    (4) AC Input Terminals

  1. Clamp the probe of the meter around the OUTPUT conductor for "Phase A". Record the meter reading.

  1. Enter the value from Step 45 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MAXIMUM value for the "Current Out Ph. B" field.

    The "Calibration Group Status" window will display "Calibration complete but not saved for current out Ph. A".

  1. You are prompted to enter the MAXIMUM value for "Current Out Ph. B".

  1. Clamp the probe of the meter around the OUTPUT conductor for "Phase B". Record the meter reading.

  1. Enter the value from Step 49 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the window will automatically change to the MAXIMUM value of the "Current Out Ph. C" field.

    The "Calibration Group Status" window will display "Calibration complete but not saved for current out Ph. B".

  1. Clamp the probe of the meter around the OUTPUT conductor for "Phase C". Record the meter reading.

  1. Enter the value from Step 52 in the "Enter the value" field of the "Calibration of a Channel" window.

  1. Click on the "OK" button. When you depress the "OK" button, the "Calibration Group Status" window will display "Calibration Complete But Not Saved".

  1. Click on the "Save" button.

  1. Remove the load from the system.



    Illustration 9g00737371

  1. When the message from illustration 9 is displayed, the procedure is complete.

Caterpillar Information System:

3126B Marine Engine Engine Electronics
3618 Engine Fuel Conservation Practices
2000/08/01 New Components in Jacket Water Heater Groups Provide Improved Sealing {1383}
2000/06/01 A New Inlet Valve is Released for use in 3116 and 3126 Truck Engines with the Two Valve Configuration. {1105}
G3516B Engines System Configuration Parameters
3126B and 3126E On-highway Engines System Overview
2003/01/01 Two Strainers are Available to Protect the Bearings in Turbochargers {1052}
3512B Petroleum Engine Radiator - Clean
Electronic Modular Control Panel II (EMCP II) Instrument Panel
3512B Petroleum Engines Testing the Radiator and Cooling System for Leaks
2000/05/01 Water Lines Groups (ECM Coolant Lines) Have Been Removed {1380}
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options General Information (All Except SR4B for 3500 Engines)
Uninterruptible Power Supply (UPS) 250 AC Voltage - Calibrate
Uninterruptible Power Supply (UPS) 250 DC Buss Voltage - Calibrate
2000/04/10 Special Instruction, REHS0440 is Available for an Index of Electrical System Schematics {7566}
Uninterruptible Power Supply (UPS) 250 Flywheel Telemetry - Calibrate
3126B Marine Engine Self-Diagnostics
3114, 3116, and 3126 Engines Basic Engine
C-10, C-12, C-15 and C-16 Industrial Engines CID 0320 FMI 02 Speed/Timing Sensor Loss of Signal
G3500 Industrial Engines Electronic Service Tools
2000/04/01 Low NO<SUB>X</SUB> Program Now has an Automatic Service Information Management System (SIMS) Entry for 3126B Truck Engines {1000, 1088}
3003, 3013, 3014 and 3024 Engines for Caterpillar Built Machines Engine Oil Pump - Inspect
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options General Information (SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Generator Wiring Diagrams (SR4B for 3500 Engines)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.