Electronic Modular Control Panel II (EMCP II) For MUI Engines Caterpillar


CID 444 FMI 12 Starting Motor Relay Failed - Test

Usage:

3304 02B



Illustration 1g00616492

Schematic Of The Starting Motor Relay

The GSC uses the starting motor relay (SMR) to activate the following components: the starting motor magnetic switches ("SMMS1" and "SMMS2"), Start Aid Switch (3500 Only) and the optional prelube pump. The SMR is located within the relay module. "SMMS1" and "SMMS2" are located on the subpanel within the control panel.

Note: On the earlier 103-1582 EMCP II Control Panel (Chart), the SMR NC contacts were used to turn off the optional battery charger during activation of the starting motor magnetic switch.

Note: Whenever the GSC activates the SMR, "K4" is shown on the lower display. "K4" is also shown on the lower display when the GSC attempts to activate the crank terminate relay. When the SMR is not activated, "K4" is not shown.

Procedure

The possible cause of this diagnostic code is an open coil or a shorted coil of the SMR.

The following response is the system response to this fault while the SMR is activated:

  • If a CID 444 occurs, then the following events take place: the engine stops cranking, the prelube pump is disabled and the "AUTO" position of the starting aid switch is disabled. The battery charger will continue to function.

The following response is the system response to this fault while the SMR is not activated:

  • If a CID 444 occurs, then the following events take place: the engine cannot crank, the engine cannot start, the prelube pump is disabled and the "AUTO" position of the starting aid switch is disabled. The battery charger will continue to function. If the engine is already running, then the engine continues to run.

The GSC treats a CID 444 as an alarm fault. Active alarm faults are shown on the display when the alarm codes key is pressed. Also, the active alarm faults are shown when the ECS is in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.

  1. Check the status of the diagnostic code (Active/Inactive).

    1. Turn the ECS to OFF/RESET and then turn the ECS to STOP.

    1. Press the alarm codes key.

    1. Observe the upper display. Check that a CID 444 FMI 12 is showing.

    1. If the diagnostic code is not showing, enter the service mode. View the fault log (OP1). Check that the diagnostic code is showing.

      Expected Result: A CID 444 FMI 12 is showing as a active fault or an inactive fault.

      Results:

      • No - A CID 444 FMI 12 has not occurred (NOT active and NOT inactive). STOP.

      • Yes - A CID 444 FMI 12is active or inactive. Proceed to 2.

  1. Check internal cable of relay module.

    Note: Only open the relay module in a dry environment. If the inspection takes more than twenty minutes replace the desiccant bag in the GSC housing. See Testing And Adjusting, "Relay Module - Replace".

    1. Turn the ECS to OFF/RESET.

    1. Temporarily, remove the relay module from the GSC. See Testing And Adjusting, "Relay Module - Replace".

    1. Check the cable that attaches the relay module to the GSC.

      Expected Result: The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged.

      Results:

      • OK - Reassemble the relay module to the GSC. Proceed to 3.

      • NOT OK - Replace the connector clamp if it is missing. If the cable is damaged, replace the GSC. STOP.

  1. Perform a functional check for the SMR.

    1. Turn the ECS to OFF/RESET.

    1. Disconnect all wires from RM-18 of the relay module.

    1. Remove the fuse "F4" from the relay module.

    1. At the relay module, measure the resistance from RM-18 to RM-6. Resistance should be greater than 5000 ohms.

    1. Prepare to measure the resistance from RM-18 to RM-6 of the relay module.

    1. Turn the ECS to the START position. Quickly measure the resistance before the starting motor relay deactivates because of the crank time. Resistance should be less than 5 ohms.

      Expected Result: For 3.d, the resistance should be greater than 5000 ohms. For 3.f, the resistance should be less than 5 ohms.

      Results:

      • OK - It is likely that a temporary bad electrical connection existed and this troubleshooting procedure corrected it. Check the electrical connectors, terminals and wiring. See Testing And Adjusting, "Electrical Connector - Inspect". STOP.

      • NOT OK - Either one of the resistance measurements are NOT correct. The relay module is faulty. Replace the relay module. See Testing And Adjusting, "Relay Module - Replace". STOP.

Caterpillar Information System:

G3612 and G3616 Engines Actuator (Hydrax) - Assemble
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 443 FMI 12 Crank Termination Relay Failed - Test
G3612 and G3616 Engines Actuator (Hydrax) - Disassemble
G3612 and G3616 Engines Actuator (Hydrax) - Install
G3612 and G3616 Engines Actuator (Hydrax) - Remove
3114, 3116 and 3126 Engines Excessive Blue Smoke
C-15, C-16 and C-18 Truck Engines Engine Oil Pressure Sensor - Remove and Install
3512B Marine Auxiliary Engine Electrical Power Supply
3512B Marine Auxiliary Engine Digital Sensor Supply
3512B Marine Auxiliary Engine CAT Data Link
3512B Marine Auxiliary Engine Analog Sensor Supply
3054 and 3056 Industrial and Generator Set Engines Engine Storage
G3612 and G3616 Engines Caterpillar Ignition System (CIS) Module - Remove and Install
3500B Engines Air Inlet Manifold - Remove and Install
G3612 and G3616 Engines Hydraulic Oil Pump (Hydrax) - Remove and Install
G3612 and G3616 Engines Hydraulic Tank (Hydrax) - Remove and Install
3114, 3116 and 3126 Engines Alternator Noise
Generator Set Load Sensor Phasing - Adjust
C9 On-Highway Truck Engines Unit Injector Hydraulic Pump - Remove
G3612 and G3616 Engines Junction Box (Hydrax) - Remove and Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 445 FMI 12 Run Relay Failed - Test
G3612 and G3616 Engines Air Inlet Choke - Remove
G3612 and G3616 Engines Air Inlet Choke - Disassemble
3114, 3116 and 3126 Engines Engine Misfires, Knocks, or Is Unstable (at Idle Only)