UPS 250, UPS 300, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supply Caterpillar


Operating Parameters

Usage:

UPS 250 APZ

Operating Parameters




Illustration 1g03404404

UPS view

When a valid password has been entered, the "Op. Params." menu displays several groups of operating parameters that can be used to configure the UPS. These parameters will vary according to the firmware that is installed on each individual unit.

Table 1
Name     Min     Max     Default (1)     Field Adjustment     Definition     Level    
Accelerometer Gain     0.1     4     1.67         The "Accelometer Gain" parameter is a scale factor that is applied to the vibration signal in order to achieve accurate vibration readings.     Service    
AHC Enable     0     1     1         The "AHC Enable" parameter turns on the Automatic Harmonic Correction and the "AHC Enable" parameter will improve the UPS's input current THD for various nonlinear loads.     Service    
ATS Cmd Level Off Delay     0     600     0     Yes     The "ATS Cmd Level Off Delay" parameter sets the amount of time that will expire prior to opening (clearing) the ATS command relay (remote output) after the other two conditions are met. The three conditions that must exist to clear this bit: UPS in stand-by, System % energy > ATS Command Level and ATS Stop Delay has expired.     Service    
ATS Command Level     0     100     0     Yes     The "ATS Command Level" parameter is a system (flywheel) % energy setting that controls when the ATS transfer command is given via a remote output relay. The four conditions that must exist to set this bit: UPS in discharge, UPS in discharge for more than 1 second, UPS not in walk-in, and System % energy < ATS Command Level. ( A typical setting is 85%.) Full load testing is recommended to insure sufficient generator start times.     Service    
Auto Load and Start     0     2     1     Yes     The "Auto Load and Start" parameter defines what the UPS will do automatically when power is applied to it after a complete outage. 0 = The UPS will require manual intervention to get the UPS in bypass and online. 1[default] = The UPS will require manual intervention to get the UPS on-line. It will power up in bypass., 2 = The UPS will go to the on-line state without any intervention.     Service    
Bearing Install Day     0     31     0     Yes     The "Bearing Install Day" parameter sets the day when the flywheel was started up or when the most recent bearing change occurred.     Service    
Bearing Install Month     0     12     0     Yes     The "Bearing Install Month" parameter sets the month when the flywheel was started up or when the most recent bearing change occurred.     Service    
Bearing Install Year     0     2031     0     Yes     The "Bearing Install Year" parameter sets the year when the flywheel was started up or when the most recent bearing change occurred.     Service    
Bot. Bearing Force     100     650     150         The "Bot. Bearing Force" parameter sets the amount of magnetic lifting force that is applied to the rotor of the flywheel when it is in standby.     Service    
Bypass Break Duration     0     30     2         When a break-before-make transition occurs, the "Bypass Break Duration" parameter controls the amount of time that no voltage will be applied to the load. The closing time of the bypass contactor or breaker is not taken into account in this timer.     Service    
Bypass Range Checking     0     2     2     Yes     The "Bypass Range Checking" parameter is valid only on UPS's with system cabinets: 0 = off, 1 = on with full messages, 2 = on with message suppression during discharge. When "ON" the UPS will compare output to the bypass source before making a transition. This check is ONLY performed when a transition to bypass is made. Once the UPS is in bypass, this parameter has no function. The items checked are bypass voltage (+/-10%), frequency difference (0.5Hz), and phase difference (15 degrees).     Service    
DC Bus Hi Trip Offset     10     200     70         If the DC bus rises above the DC Bus Voltage setpoint plus this number, the UPS will go into discharge.     Service    
DC Bus Low Trip Offset     10     200     70         If the DC bus falls below the DC Bus Voltage setpoint minus this number, the UPS will go into discharge.     Service    
Def. Data Log Rate     1     7200     3600     Yes     The "Def. Data Log Rate" parameter sets the time in seconds that the telemetry will be sent to the UPSView data log files if a computer is connected. When the UPS is discharging, the log rate is the maximum (two samples per second).     Set.    
Disable +-15V PS Check     0     1     0         The "Disable +-15V PS Check" parameter disables the 15 VDC power supply checking. Newer APCs have some enhanced power supply checks. This check may need to be disabled on older APCs.     Service    
Disch Min. Byp-Inp Lock     0     100     30         The "Disch Min. Byp-Inp Lock" parameter is valid only on UPS's with dual inputs: If the flywheel energy falls below this level when the input returns and the UPS is synchronized to the Bypass source, the output of the UPS will stay synchronized to the bypass source and exhaustively discharge. No interruption to the output will occur.     Service    
Frequency Slew Rate     0.05     2     1     Yes     The "Frequency Slew Rate" parameter controls the speed in which the UPS output voltage will be brought in-phase (phase match) with the input to begin the process of ending a discharge (walk-in).     Service    
Gen Set Dis.Volt. Match     0     1     1     Yes     When the UPS is ready to start a walk-in from a discharge and the "ON Generator" signal from a remote input is high, it will match the input and output voltages before closing the main static switch. If this parameter is set to 0 it will not. Instead it will maintain the Nominal Voltage setpoint throughout the walk-in.     Service    
Gen Set Max. Current     10     400     400     Yes     The "Gen Set Max. Current" parameter sets the maximum input current while the "ON Generator"signal from a remote input is high (closed). This parameter could be used with GS Max. Mtr In Current to prevent a generator overload when the generator rating smaller than the UPS. A successful installation involving an undersized generator requires the transient response of the generator to be very good.     Service    
Gen Set Transient Tol     1     50     25     Yes     The "Gen Set Transient Tol" parameter sets the Transient VAC Tolerance while the "ON Generator" signal from a Remote Input is high (closed).     Service    
Gen Set Walk-in Rate     10     750     85     Yes     The "Gen Set Walk-in Rate"parameter sets the Walk-in Rate while the "ON Generator" signal from a remote Input is high. If this walk-in rate is set too high, the generator voltage can sag or slow down in frequency, causing the input voltage to be disqualified and the UPS to go back into discharge before the walk-in is complete.     Service    
Genset Motoring Delay     0     120     0     Yes     The "Genset Motoring Delay" parameter sets the amount of time the controller will wait after the walk-in before it will start motoring the flywheel. (MMS) This parameter must be set in each MMU. This parameter can also be a different value in each MMU.     Service    
Genset Start Level     0     100     0         The "Genset Start Level" parameter is a system (flywheel) % energy setting that controls when the generator start command is given via a remote output relay. Caterpillar recommends that the ATS Command relay be used to accomplish this function.     Service    
Genset Stop Delay     10     600     60         After the flywheel is at speed and the UPS is being powered from the utility, the remote output relay will de-energize after this time delay. (seconds)     Service    
GS Max Motor Current     10     400     200     Yes     The "GS Max Motor Current" parameter sets the maximum motor current while the "OnN Generator" signal from a remote input is high (closed). A smaller number will reduce the step unload that occurs at the end of flywheel motoring. This reduction is useful on generators with poor transient performance. This parameter should not be set to 0 and be greater than the minimum motoring current.     Service    
GS Max. Mtr In Current     10     440     440     Yes     The "GS Max. Mtr In Current" parameter sets the maximum motoring in current while the "ON Generator" signal from a remote input is high (closed).     Service    
GSC Current Limit     1     94     45         The "GSC Current Limit" parameter is the AC current limit of the Genset Start IGBTs     Service    
GSC Current Limit Hys     1     94     10         Once the GSC current limit is reached, the controller will not turn the Genset start IGBTs back on until the current has fallen below the GSC current limit minus the GSC current limit hysteresis.     Service    
GSC Enable     0     2     0         The "GSC Enable" parameter must be set to 1 if the UPS has the Genset start option. (power electronic version)     Service    
Hard Grounded System     0     1     1         The "Hard Grounded System" parameter is set to 0 when the power distribution system feeding the UPS has a Neutral grounding resistor. (This option has never been implemented.)     Service    
Input Over Volt Trip     1     10     10     Yes     The "Input Over Volt Trip" parameter sets the percent deviation above the Nominal Voltage setpoint in which the system will disqualify the input voltage and the system will enter into discharge.     Service    
Input Under Volt Trip     1     15     10     Yes     The "Input Under Volt Trip" parameter sets the percent deviation below the Nominal Voltage setpoint in which the system will disqualify the input voltage and the system will enter into discharge.     Service    
Internal CAN Enable     0     1     1         The Internal CAN Enable parameter enables the CAN network. This parameter must be turned on in Multi Module [flywheel] Systems (MMS).     Service (Hidden)    
Internal CAN Node ID     1     0x0e     0x01         The "Internal CAN Node ID" parameter is set to identify the MMU number. Each MMU requires a unique ID and should be numbered sequentially 1 to the total number of MMUs in the system.     Service (Hidden)    
KW Compare Setpt 1     0     1000     0     Yes     The "KW Compare Setpt 1" parameter sets the KW levels that will cause the output KW Remote Output to change states. Each setpoint must be at least 10KW apart in order for the output to work. Setting them to zero disables the function. The logic works as follows: 1) If setpoint 1 is less than setpoint 2, then the relay is energized when the output KW is less than setpoint 1 and de-energized when it goes back above setpoint 2. 2) If setpoint 1 is greater than setpoint 2, then the relay is energized when the output KW is greater than setpoint 1 and de-energized when it goes below setpoint 2. To energize relay: Output KW < setpoint 1 < setpoint 2, or Output KW > setpoint 1 > setpoint 2 Once energized, de-energize relay: Output KW < setpoint 2 < setpoint 1, or Output KW > setpoint 2 > setpoint 1     Service    
KW Compare Setpt 2     0     1000     0     Yes     The "KW Compare Setpt 2" parameter sets the KW levels that will cause the output KW Remote Output to change states. Each setpoint must be at least 10KW apart in order for the output to work. Setting them to zero disables the function. The logic works as follows: 1) If setpoint 1 is less than setpoint 2, then the relay is energized when the output KW is less than setpoint 1 and de-energized when it goes back above setpoint 2. 2) If setpoint 1 is greater than setpoint 2, then the relay is energized when the output KW is greater than setpoint 1 and de-energized when it goes below setpoint 2. To energize relay: Output KW < setpoint 1 < setpoint 2, or Output KW > setpoint 1 > setpoint 2 Once energized, de-energize relay: Output KW < setpoint 2 < setpoint 1, or Output KW > setpoint 2 > setpoint 1     Service    
LC Startup Low Limit     550     600     550         The "LC Startup Low Limit" parameter sets the minimum load cell measured weight that must exist for the flywheel to be motored or discharged.     Service    
LCD Contrast     25     100     70     Yes     The display stores its contrast data in the "LCD Contrast" parameter.     Service    
Load Cell Cal. Constant     1.8     2.2     2     Yes     The "Load Cell Cal. Constant" parameter comes from the load cell certificate. This parameter is unique to each load cell.     Service    
Load Cell Offset     -0.9     0.9     0     Yes     If the load cell zero pound offset is known, then it is recorded in the
Load Cell Offset
parameter. (mV)    
Service    
Load Cell SN(no letters)     0         0     Yes     The "Load Cell SN(no letters)" parameter comes from the load cell certificate. This parameter is unique to each load cell.     Service    
Max Peak Inv. Current     100     1500     900         The "Max Peak Inv. Current" parameter is the maximum inverter current that can go through the utility Skiips (IGBTs) before PWM current limiting occurs.     Service    
Max RMS Inv. Current     10     400     400         The "Max RMS Inv. Current" parameter is the maximum current that can be drawn through the filter inductor when the UPS is Online (not discharging).     Service    
Max Xfer Ph. Angle Diff     0     179     15         The "Max Xfer Ph. Angle Diff" is valid only on UPS's with system cabinets: If Bypass Range Checking is on, this sets maximum allowable phase angle difference between the output and bypass source before a transfer to bypass will be attempted..     Service    
Max. Mtring In Curr.     10     440     440     Yes     The "Max. Mtring In Curr." parameter sets the maximum input current per MMU when the UPS is motoring. If the input voltage (-10%) and load conditions (100% load, 0.8pf lag) exist such that the input current hits this number, the UPS will reduce the amount of voltage correction until the conditions change.     Service    
Maximum Input Current     10     400     400     Yes     The "Maximum Input Current" parameter sets the maximum input current per MMU when the UPS is not motoring. If the input voltage (-10%) and load conditions (100% load, 0.8pf) exist such that the input current hits this number, the UPS will reduce the amount of voltage correction until the conditions change.     Service    
Maximum Motor Current     10     400     200     Yes     The "Maximum Motor Current" parameter sets the peak current that will be applied to the armature while motoring. This ultimately controls the amount of power that will be drawn from the source to motor the flywheel.     Service    
Min. Motoring Current     10     150     100         Whenever the armature motoring current is reduced due to input or filter current limits, the "Min. Motoring Current" parameter is the minimum that the current will be reduced to.     Service    
MMU Serial Number     0         0         The "MMU Serial Number" parameter is a unique number for each MMU that is set by manufacturing. Loading defaults will not change this number. This parameter should never be changed. If the parameter is set to 0, the ethernet option will not work.     Service    
Modbus Baud Rate     9600     19200     9600     Yes     Modbus option setting     Set.    
Modbus TCP/2W/4W     0     2     0     Yes     The "Modbus TCP/2W/4W" parameter determines the Modbus type. 0 = TCP, 1 = 2W, 2 = 4W The TCP type must have the Network option enabled. The 2W/4W types must use the newer SIOD (30126-2) and have its JMPA (on SIOD) in the RS485 position.     Service    
Modbus Unit ID     1     247     1     Yes     Modbus option setting     Set.    
Modbus TCP Timeout     0     7200     0         The "Modbus TCP Timeout"parameter sets the time (seconds) in which inactive Modbus connections will be closed to prevent the UPS Modbus code from locking up due to the maximum number of connections being exceeded.     Service    
Model Index     2     13     2         The "Model Index" parameter sets the model of the system (# of MMUs, Etc.)     Service    
Modem Type     0     4     0     Yes     The "Modem Type" is set based on the modem that is installed (0 = internal, 2 = v.everything, 3=zoom)     Set.    
Monitor S/W Baud Rate     38400     38400     38400         The "Monitor S/W Baud Rate" is the speed in which the UPS communicates serially with a laptop using UPSView.     Set.    
Motor Ramp Down Factor     0     10     5     Yes     The "Motor Ramp Down Factor" sets the rate in which the flywheel charging current will be reduced as the flywheel approaches full speed. This results in a several second (step unload) reduction in the charging power at the input of the UPS. This should minimize the chance of a generator overspeed at the end of motoring. Setting this parameter to a 0 will result in an ~3 cycle step unload of the charging power.     Service    
Motoring Bearing Force     100     650     250         The "Motoring Bearing Force" parameter sets the amount of magnetic lifting force that is applied to the rotor of the flywheel when it is being motored.     Service    
Neutral Connected     0     1     0         The "Neutral Connected" parameter must be set for a 4-wire system.     Service    
No DC Bus Fuses     0     1     1         The "No DC Bus Fuses" parameter is set to 1 for the new fuseless DC bus     Service    
Nominal Voltage     300     600     480     Yes     The "Nominal Voltage" parameter sets the target output voltage for the voltage regulator. The system will regulate to this value unless the conditions are such that the maximum input current or maximum filter current have been reached. In this case it will back off on the regulation to keep the input or filter current limits from being exceeded. This number is also used with parameters 6, 7, 97, & 98.     Service    
Output Over Volt Tol.     1     10     10         The "Output Over Volt Tol." parameter sets the percent deviation above the Nominal Voltage setting at which the system will disqualify the output voltage and go to bypass. This allows the system to be overloaded while the Maximum Input Current or the Maximum Filter Current have been reached without causing the output voltage to rise too far out of tolerance with increasing load.     Service    
Output PN Volt Factor     1.2     2     1.3     Yes     The "Output PN Volt Factor" parameter sets the output voltage phase to neutral limit that is used to detect a nonfiring neutral static switch.     Service    
Output Under Volt Tol.     1     15     10         Sets the percent deviation below the Nominal Voltage setting at which the system will disqualify the output voltage and go to bypass. This allows the system to be overloaded while the Maximum Input Current or the Maximum Filter Current have been reached without causing the output voltage to drop too far out of tolerance with increasing load.     Service    
Over Frequency Trip     50     66     62     Yes     Sets the maximum input frequency for which the system will remain in Line Mode operation. Beyond this frequency, the system will enter discharge. A step unload on a generator may cause the generator to speed up and go above this level. This is the maximum frequency which the load will be exposed to unless the system transitions to a bypass source at a higher frequency.     Service    
Overload Transfer Limit     0     3     3         Sets the number of overload transfers to Bypass that can occur within a 10 minute period before Online mode will be disabled without operator intervention.     Service    
Overload Warn Disable     0     1     0     Yes     This provides the ability to turn off overload alarms.     Service    
Redundant Switch Hour     0     24     3         On redundant systems only (model index), the redundant MMU will rotate every 24 hours. This is the hour (0-24) that the redundant MMU will change.     Service (Hidden)    
Remote Input 1     0     25     1     Yes     Defines the programmable remote input number 1.     Set.    
Remote Input 2     0     25     2     Yes     Defines the programmable remote input number 2.     Set.    
Remote Input 3     0     25     3     Yes     Defines the programmable remote input number 3.     Set.    
Remote Input 4     0     25     4     Yes     Defines the programmable remote input number 4.     Set.    
Remote Input 5     0     25     5     Yes     Defines the programmable remote input number 5.     Set.    
Remote Input 6     0     25     6     Yes     Defines the programmable remote input number 6.     Set.    
Remote Output 1     0     120     101     Yes     Defines the programmable remote contact output number 1.     Set.    
Remote Output 2     0     120     102     Yes     Defines the programmable remote contact output number 2.     Set.    
Remote Output 3     0     120     103     Yes     Defines the programmable remote contact output number 3.     Set.    
Remote Output 4     0     120     50     Yes     Defines the programmable remote contact output number 4.     Set.    
Remote Output 5     0     120     104     Yes     Defines the programmable remote contact output number 5.     Set.    
Remote Output 6     0     120     105     Yes     Defines the programmable remote contact output number 6.     Set.    
Single Display     0     1     0         Set to 1 when a MMS only has one display. 2.4 hardware release     Service (Hidden)    
Stepped Phase Match     0     1     0         Sets the stepped phase match instead of a ramped phase match.     Service    
Sweep Field Current     1     12     5         Field Current setpoint used during the start-sweep. (0-60RPM)     Service    
Sweep Motoring Current     10     150     100         Motoring Current Limit used during the start-sweep. (0-60RPM)     Service    
Transient VAC Tolerance     1     50     15     Yes     Sets the percent deviation from the prevailing input voltage in which the system will disqualify the input voltage and enter into discharge. Lowering this parameter causes the system to enter into discharge on small events and improves the output transient performance. Increasing this parameter decreases the likelihood that the system will enter discharge on utility noise events.     Service    
Under Frequency Trip     45     60     58     Yes     Sets the minimum input frequency for which the system will remain in Line Mode operation. Below this frequency, the system will enter discharge. A step load on a generator may cause the generator to slow down below this level. This is the maximum frequency which the load will be exposed to unless the system transitions to a bypass source at a higher frequency.     Service    
UPS Net Enable     0     1     1         Enables the UPS network. It must be turned on in Multi Module Systems (MMS) or system with a system cabinet. It must be turned OFF in an SMS.     Service (Hidden)    
Walk-in Rate     10     750     85     Yes     Sets the rate in which the real part (KW) of the load is transferred from flywheel to the input when the system is transitioning from Discharge mode to Online mode. This rate is used at the system level regardless of the number of MMUs. A fast Walk-in Rate can result nuisance trips back into discharge during the Walk-in due to a sagging input voltage.     Service    
Xtra Disch. VAC Tol.     0     50     10         Sets the % tolerance that is added to the Transient VAC Tolerance (or the Gen Set Transient Tol.) after the UPS goes into discharge. It is removed 1s after the flywheel starts motoring.     Service    
( 1 ) Default values are for general information. Actual defaults may differ depending on system configurations, installation sites, and local codes. Check each individual unit.

Changing Parameters




Illustration 2g03404405

  1. To change any parameter, select the operating group (parameter) from the list that is shown in illustration 1.

  1. Enter the new value in the "Request Operating Parameter Change" window.

    Refer to the example in illustration 2.

  1. Click on "Send".

Caterpillar Information System:

CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Travel Brake Valve - Disassemble
3126B and 3126E On-highway Engines Fuel Level Sensor Circuit - Test
C0.5, C0.7, C1.1/3011C, C1.5/3013C, C1.6 and C2.2/3024C/3024CT Industrial Engines and Engines for Caterpillar Built Machines General Information
Electronic Modular Control Panel II (EMCP II) GSC CID 0590 - FMI 09
Electronic Modular Control Panel II (EMCP II) GSC CID 0560 - FMI 11
3054 and 3056 Industrial and Generator Set Engines Fuel System - Prime
3054 and 3056 Engines 550 Generator Set Control Panel Control Module - Configure
385B Excavator Machine System Specifications Stick Lines
Electronic Modular Control Panel II (EMCP II) GSC CID 0444 - FMI 12
385B Excavator Machine System Specifications Stick Lines
2002/04/01 Improved Spark Plug Adapters Help Prevent Seizures of the Spark Plugs {1555}
3054 and 3056 Engines 550 Generator Set Control Panel Control Module
3126 HEUI Industrial Engine Flywheel - Remove
3126 HEUI Industrial Engine Flywheel - Install
Electronic Modular Control Panel II (EMCP II) GSC CID 0248 - FMI 09
Electronic Modular Control Panel II (EMCP II) GSC CID 0330 - FMI 07
Electronic Modular Control Panel II (EMCP II) GSC CID 0331 - FMI 02
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Travel Brake Valve - Assemble
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Travel Motor - Remove
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Travel Motor - Disassemble
3126 Truck Engine Military Engine Oil Filter Base - Remove
Power Module Switchgear (Low Voltage and Medium Voltage) General Hazard Information
Power Module Switchgear (Low Voltage and Medium Voltage) Electrical System
Power Module Switchgear (Low Voltage and Medium Voltage) Reference Material
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.