Usage:
Type 3 3N8900 Control Panels
Introduction
The current 3N5718 Fault Light has been discontinued by the supplier and replaced with a different version. As a result, the wiring for the replacement part will be different than the discontinued part.
Illustration One. Discontinued Version.
Illustration Two. New Version.
The version of the part can be identified by looking at the connection pins located on the back of the part. Illustration One shows the electrical schematic and pin layout for the discontinued part. Illustration Two shows the electrical schematic and the pin layout for the new version.
Installation
- * The electrical wiring for the the discontinued part shown in Illustration One is as follows:
1. Connect control panel wire #2 to 3N5718 terminal #1.
2. Connect control panel wire #93 to 3N5718 terminal #3.
3. Connect control panel wire #92 to 3N5718 terminal #4.
4. Connect control panel wire #3 to 3N5718 terminal #2.
- * The electrical wiring for the the new part shown in Illustration Two is as follows:
1. Connect control panel wire #2 to 3N5718 terminal #2.
2. Connect control panel wire #93 to 3N5718 terminal #5.
3. Connect control panel wire #92 to 3N5718 terminal #4.
4. Connect control panel wire #3 to 3N5718 terminal #1.