Digital Voltage Regulator Caterpillar


Instantaneous Trip Shutdown - Troubleshoot

Usage:

SR4B 1BN
Instantaneous trip shutdown is fault 801.

Note: Electromagnetic noise spikes can create an erroneous instantaneous trip. Such spikes are often the result of breaker closure. If the digital voltage regulator or any wiring to the digital voltage regulator is in close proximity to a circuit breaker (particularly a medium voltage breaker), this condition may occur. Uninterrupted power systems (UPS), motor drives, and other equipment that generates electromagnetic interference (EMI) spikes or switches large currents must also be avoided. Install the digital voltage regulator in the generator terminal box or in another location away from the offending equipment.

  1. Check the wiring.

    1. Stop the generator set.

    2. Check the wiring.

      Expected Result: The wiring is correct.

      Results:

      • OK: Go to Step 2.

      • NOT OK: Shorted F1 and F2 wires will cause the instantaneous trip shutdown fault. Megger the exciter stator. See the proper wiring diagram for details. Refer to Testing And Adjusting, "Wiring Diagrams". STOP.

  2. Check the accessory.

    1. Disconnect all accessory wiring from terminals 3, 5, 6, 7, 40, 41, 42, 43, 44, 45, and 50. Remove the serial data link, if installed.

    2. Start the generator set. Operate the generator set with the same conditions that caused the problem previously.

      Expected Result: The generator set operates properly.

      Results:

      • OK: The generator set operates properly. There is a problem with an accessory which has been disconnected. Reconnect one accessory. Operate the generator set again. Continue this process of reconnecting one accessory at a time until the faulty accessory is found. STOP.

      • NOT OK: The generator set does not operate properly. Go to Step 3.

  3. Check the nearby equipment.

    1. Identify nearby equipment that could generate EMI spikes.

    2. Move the digital voltage regulator and the wiring to a temporary location away from the offending equipment and operate the generator again.

      Expected Result: The problem has been resolved.

      Results:

      • OK: The problem has been resolved. Find a new permanent home for the digital voltage regulator away from the offending equipment. Shielded wiring should always be used for rheostat inputs when the regulator and/or rheostat are located off the generator. Connect the shield drain wire to regulator terminal 45. Insulate the wiring shield from touching all other objects, including Earth ground.

      • NOT OK: The digital voltage regulator is being subjected to other sources of EMI. On methods to reduce EMI, refer to Systems Operation, "Customer Options", section Remote Installation Notes.

Caterpillar Information System:

Challenger 65C, Challenger 65D, Challenger 65E, Challenger 70C, Challenger 75C, Challenger 75D, Challenger 75E, Challenger 85C, Challenger 85D, Challenger 85E and Challenger 95E Agricultural Tractors Machine Monitor System Relays
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems Service Operations
3524B Engine for Caterpillar Built Machines Accessory Drive (Rear) - Install
554 Forwarder and 574 Forwarder Gate Cylinders - Lubricate
D400E Series II Articulated Truck Hoist Control Valve - Remove
554 Forwarder and 574 Forwarder Cab Door Hinges - Lubricate
797 Off-Highway Truck Power Train Gear Pump (Transmission Charging and Scavenge)
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems F341 Transmission Speed Sensor - Failed Low
CB-534C and CB-634C Vibratory Compactors Vibratory System Visual Inspection
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Oil Step Speed Calibration
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems F340 Transmission Speed Sensor - Failed High
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems Diagnostic Operation
AP-1000B and BG-260C Asphalt Pavers Manual Propel Override Control
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Magnetic Pickup Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Diode Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Engine Oil Pressure Switch Test
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems Mode 1 - Operator Calibrations
3512B and 3516B Engine Supplement for and 784C,, 785C and and 785C HAA Off-Highway Truck/Tractors Crankshaft Front Seal - Install
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems F342 Engine RPM Sensor - Failed High
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Slave Relay Test
Challenger 35, Challenger 45 and Challenger 55 Agricultural Tractors Electronic Systems F343 Engine RPM Sensor - Failed Low
D350E Series II Articulated Truck Power Train Rear Drive Shaft - Remove and Install
D400E Series II Articulated Truck Hoist Control Valve - Install
CP-563D, CS-563D, CS-573D and CS-583D Vibratory Compactors Vibratory System Controller (Variable Frequency) - If Equipped
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.