1994/01/17 Caterpillar


Cold Weather Instructions For Nitrogen Charged Tension Cylinders And Low Nitrogen Pressure Alarm System {4197}

Usage:


Challenger 65C (2ZJ) Challenger 70C (2YL) Challenger 75C (4KK) Challenger 85C (9TK) Tractors

Pneumatic front idlers have been replaced with solid front idlers on C-Series machines. The pneumatic idler supplied a significant amount of recoil. In order to replace this lost recoil, the tension cylinders have been redesigned to combine a nitrogen boost for a longer travel spring. The nitrogen gas compresses when recoil is needed. A thorough understanding of nitrogen and its response to temperature change is necessary to properly service the tension cylinders and to achieve maximum life of the undercarriage components.

Nitrogen charge pressure varies with temperature. As the temperature decreases, the nitrogen pressure decreases. In instances when the ambient temperature is below the temperature referred to in the chart, the nitrogen pressure may decrease such that it is just below the set point of the low pressure alarm system.

The low nitrogen pressure alarm system detects an inadequate nitrogen charge in either tension cylinder. A buffer compares the actual pressure to a set point. If actual pressure falls below this set point, the alarm indicator light on the dash turns on and the alarm horn is activated. Two versions of the buffer exist and their differences are detailed in the following chart.

For example: If the machine is equipped with the 105-2228 Buffer and tension cylinders are properly charged, the dual alarm systems are activated at temperatures at or below -18°C (0°F). If equipped with the 107-3578 Buffer, the dual alarm systems are activated at temperatures at or below -32°C (-25°F).

NOTE: The 107-3578 Buffer may directly replace the 105-2228 Buffer in areas where ambient temperature falls below -18°C (0°F).

In a low temperature situation in which the alarm system is activated, determine that the actual nitrogen pressure is below the set point and confirm that there are no other system problems. Add enough nitrogen to the cylinder to achieve a pressure above the set point. By adding 10 psi of nitrogen to cylinder, the temperature at which the cylinder reaches the set point pressure is lowered approximately 20°F.

For example: At -18°C (0°F) the pressure in the cylinder is 1220 kPa (177 psi), the alarm system set point for 105-2228 Buffer. By adding 10 psi, the machine has the capability to work in temperatures of -18°C (0°F) to -28°C (-20°F).

NOTE: When the ambient temperature INCREASES, the pressure in the cylinder INCREASES.

The extra nitrogen pressure added to the cylinder during cold weather operation is extra system pressure in warmer months that should be discharged, otherwise front idler bearing life might be compromised. See chart below for proper system pressure at a given ambient temperature. Adding more than 20 psi above the pressure shown in chart for a given temperature is not recommended.

For procedures to test and charge the tension cylinder, refer to service manual module SENR5262, for the topic, Test and Charge The Tension Cylinder.

Contact the Agricultural Machinery Unit for operating instructions for temperatures below -40°C (-40°F).

When servicing the nitrogen system, be sure that the nitrogen temperature has stabilized so that it is the same as the ambient temperature, (for example, if the nitrogen was stored in a cold place and was brought into a warm shop, let the nitrogen temperature stabilize so that it is the same air temperature as the shop). The nitrogen gas does increase in pressure as it warms up to the shop temperature. Cold nitrogen gas added to the tensioning cylinder may result in excess pressure when the gas warms.

Caterpillar Information System:

1994/01/10 Clarify Usage Of Parts Service Cylinder Head Gaskets{1124}
1994/01/10 New Idler Pulley Assembly Used In Refrigerant Compressor Group{1802}
1994/01/10 Correct Position Of Clamp Assembly Is Required To Prevent Tie Rod Damage{4318,4329}
1994/01/10 New Rear Wheel Bearing Adjustment Procedures{4208}
1993/12/27 New Flexible Hose Assembly Used in the Exhaust Bypass Group {1057}
1993/12/27 Cleaning SR4 Generators {1404,4450}
1993/12/27 New Lamps For Tachometer And Speedometer {7450}
1993/12/27 New Temperature Switch Assembly And Tube Assemblies Used To Improve Torque Converter Temperature Sensing {7413}
1993/12/27 Air Filter Indicator Failure Due To Excessive Vibration {7452}
1993/12/27 Improved Front Idler Bearings Are Now Available {4159}
1993/12/20 Exhaust Brakes Can Not Be Installed On All Remanufactured 3208 Engine Arrangements {1119}
1993/12/20 Ether Starting Aid System {1456}
1994/01/17 Knocking Noise In Front Suspension Frame Group Can Be Eliminated With Shims {7200,7050}
1994/01/17 Brake System Servicing {4005}
1994/01/17 Improved 24-12 Volt Converters Available {1400,1421}
1994/01/17 List Of Entertainment Radios For Earth Moving And Agriculture Equipment {7300}
1994/01/17 9X6779 Radio Has No Memory {7338}
1994/01/17 New Tube Assembly With Bellows At Each End Used In Engine Air Lines Groups {1058}
1994/01/17 New Flywheel Assembly With Oil Dam Helps Prevent Premature Wear On Internal Splines {1156}
1994/01/17 New Control Assemblies Used In Fuel Injection Control Groups {1298}
1994/01/17 New Valve Cover Gasket Used {1107}
1994/01/17 Low Coolant Level Plate In Radiator May Cause False Coolant Level Readings {1353}
1994/01/24 New Flow Control Knobs Available To Improve Disassembly {5137}
1994/01/24 Heavy Duty Direction Signal Flasher Is Now Used {1430}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.