- Generator Set
- C27 GEN SET (S/N: 2A31-UP)
- C32 GEN SET (S/N: NRC1-UP; JSJ1-UP; TZJ1-UP; FLX1-UP)
Introduction
The problem that is identified below does not have a known permanent solution. Until a permanent solution is found, use the solution that is identified below.
Problem
The power cables may not be properly separated, secured, and protected from sharp edges and damage from vibrations.
Solution
Do not operate or work on this product unless you have read and understood the instruction and warnings in the relevant Operation and Maintenance Manuals and relevant service literature. Failure to follow the instructions or heed the warnings could result in injury or death. Proper care is your responsibility. |
The procedure below secures the power cables with a clearance of at least
Required Parts
New Part Number | Part Name | Quantity |
---|---|---|
Cable Strap | As needed | |
Cable Strap | As needed | |
Mat | As needed |
Rework Procedure
- Route the power cable bundles to provide at least a
2.5 cm (1 inch) clearance from sheet metal, bus bars, Glastic, current transformers, or other harnesses. - Wrap each power cable bundle with mat (4) with the seam on top and the smooth surface inside. Secure the mat to the bundle with two cable straps (3).
Note: The cable straps should only contact the battery mat. Cable straps have sharp edges which easily cut through wiring insulation.
Show/hide tableIllustration 2 g06330490 (1) 329-1293 Cable Strap - When hanging a cable bundle is necessary, proceed with steps 1 and 2. Then, hang the bundles to prevent contact with associated components using two cable straps (1).
Show/hide table
Illustration 3 g06330028 (3) 7K-1181 Cable Strap
(4)7H-8213 Mat - When clearance cannot be maintained between the power cable bundles and associated components, wrap the bundle with battery mat (4) and secure with two cable straps (3).
Illustration 1 | g06329883 |
(1) (2) Upper Ladder Bar (3) (4) |