- Generator Set
- C15 GEN SET (S/N: LNA1-UP; T4A1-UP; X5M1-UP)
- C18 GEN SET (S/N: X5F1-UP)
The 508-8247 is combination of heated and non-heated insulation wraps are intended to prevent the open crankcase ventilation (OCV) from freezing in cold-weather climates that experience temperatures down to
The kit includes a combination of AC and DC powered heaters. The AC heaters only run when the generator set is running. The DC heaters run when the battery switch is turned.
Note: The heaters run when the battery switch is turned on. Therefore, a battery charger must be operational when the engine is not running.
The new insulation assemblies are adaptable to the above engines back to first production.
Required Parts
Part Number | Part Name | Qty |
---|---|---|
Ring Terminal | 1 | |
Terminal As | 2 | |
Electrical Wire (16 Gauge) | |
|
Sleeve | |
|
Connector Socket | 2 | |
Screw | 1 | |
Sleeve | |
|
Wire End | 7 | |
Circuit Breaker As (10 Amp) | 2 | |
Heat Shrink Tube | |
|
Connecting Plug Kit | 1 | |
Connector Plug As | 1 | |
Wedge | 1 | |
Connector Receptacle As | 1 | |
Wedge | 1 | |
Connector Pin | 2 | |
Connector Socket | 2 | |
Insulation As | 1 | |
Insulation As | 1 | |
Insulation As | 1 | |
Insulation As | 1 | |
Heater As | 1 | |
Insulation | 1 | |
Insulation As | 1 | |
Insulation | 1 |
Illustration 1 | g06156767 |
(1) (2) (3) (4) (5) (6) (7) (8) |
Installing the Heater and Insulation
Illustration 2 | g06156777 |
- Drill an 11/64 inch hole approximately 3/8 inch deep at the location shown in Illustration 2.
Show/hide table
Illustration 3 g06156782 (1) 030-9612 Screw
(2)109-3038 Wire End
(3)8T-7875 Electrical Wire - Cut wire (3) to approximately
3.5 m (11.5 ft) . - Install wire end (2) onto one end of wire (3).
- Secure wire end (2) to wire (3) with
3 cm (1.2 inch) of 125-7874 Heat Shrink Tube. - Attach ring terminal (2) to the valve cover with one screw (1).
Show/hide table
Illustration 4 g06156789 (4) 505-7936 Heater AsNote: The minimum application temperature is
25° C (77° F) . Any attempt to apply the heaters to a part at a temperature below25° C (77° F) will result in a compromise of the bonding. - Use methyl alcohol to clean the part surface so that the surface is free of oil, grease, dirt, rust, or oxides and have a smooth bonding surface.
Note: Do not use any cleaner which leaves an oily film (for example, kerosene, gasoline, Naphtha).
- Attach heater pad (4) to the breather.
- Support the power leads so that the power leads will not pull the heater from the part.
- Peel off the release liner.
- Position edge of heater on the part surface.
- Roll into place to make sure that there are no air pockets between the heater and part surface.
- Route and secure the wires to prevent rubbing and heat exposure.
- Install approximately
305 mm (12 inch) of 109-0887 Sleeve over each lead and secure with cable straps. - Install the 271-5600 Connector Receptacle As, two 271-5604 Connector Pins, and the 271-5602 Wedge on the end of the heater pad wires.
Show/hide table
Illustration 5 g06156797 (5) 505-7934 Insulation As - Install insulation assembly (5) around the breather. Secure insulation clips to the four valve cover bolts at the corners of the valve cover.
Show/hide table
Illustration 6 g06156823 (6) 445-7995 Insulation As
(7)445-8008 Insulation As
(8)445-8004 Insulation As
(9)507-9004 Insulation - Install insulation (9) around the hose. Close the Velcro seam.
- Install insulation assemblies (6), (7), and (8) around the canister. Secure insulation assemblies with the springs and clips.
Show/hide table
Illustration 7 g06156831 (10) 508-8248 Insulation As
(11)508-8250 Insulation - Install insulation assembly (10) around the OCV horizontal fumes hose. Close the Velcro seam.
Note: Before installing the insulation on the OCV horizontal fumes hose, make sure that the hose has a continuous downhill slope to promote drainage and eliminate low spots.
- Install insulation assembly (11) around the OCV drain line. Close the Velcro seam.
Electrical Schematic
Illustration 8 | g06159680 |
(A) T1 (Top of breaker)
(B) T2 (Bottom of breaker) (C) (D) (E) (F) Shore Power Line terminal (SP1L) (G) Shore Power Neutral terminal (SP1N) (H) Ground terminal (Ground wire to breather/valve cover) (1) (2) (3) (4) |
Illustration 9 | g06156844 |
(F) Shore Power Line terminal (SP1L)
(G) Shore Power Neutral terminal (SP1N) (H) Ground terminal (Ground wire to breather/valve cover) |
Note: Callouts (A), (B), (F), (G), and (H) use the 109-3038 Wire Ends.
The heated breather pad has the following specifications:
- 120 V AC
- 150 W maximum
- 6.5 A maximum current draw
Illustration 10 | g06159684 |
(A) T1 (Top of breaker)
(B) T2 (Bottom of breaker) (C) (D) (E) (J) +VE (DC terminal) (K) -VE (DC terminal) (4) (5) (6) |
Illustration 11 | g06157102 |
(J) +VE (DC terminal)
(K) -VE (DC terminal) |
Note: Callouts (A) and (B) use the 109-3038 Wire Ends.
Note: Callouts (J) and (K) use the 2L-8079 Ring Terminals secured with
The heated insulation has a maximum 7.54 Amps at 28 V.