UPSB130 Uninterruptible Power Supply UPS Battery - 60Hz Caterpillar


Configuration - Check

Usage:

UPSB 130 XTC
Use the following steps to verify the configuration parameters and the personalization parameters. Some situations may require variations to the default.

Contact Product Support to discuss any abnormal requirements that you are unsure or unclear about.

  1. Connect a laptop to the UPS and launch the UPS tuner service tool.

  1. Verify that Q4S breaker is in the ON (closed) position

  1. Verify that the UPS Tuner reports the status of the board as "Personalization STATUS 1" for MIZNUS and CHAN.

  1. Configure the parameters for the MIZNUS PCA, CHAN PCA, and the GDEN PCA,

  1. Run the test for the LED lights to verify that the LED lights will illuminate and cycle through the available color changes twice.

  1. Verify the correct date and time.

  1. Close the maintenance bypass switch for the Maintenance Bypass Cabinets (MBC), if available.

  1. Open the UPS Output isolation switch for the MBC, if available.

Applications that have the 3-CB external maintenance bypass cabinet complete the following steps:

  1. Open the UPS input isolation switch on the MBC.

  1. Follow normal operating procedures and continue powering down the UPS system.

  1. Place the MAINS 1 (Q1) and the MAINS 2 (Q4S) input switches to the OFF (open) position to de-energize the switches

Caterpillar Information System:

UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Configuration - Adjust
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Communication - Check
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Cabinet - Check
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz System Shutdown
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Metering - Check
797F and 797F XQ Off-Highway Trucks Machine Systems Hood (Front) - Remove and Install
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Unit Initial Check
3516C Locomotive Engines Air Inlet Manifold - Remove and Install
C27 and C32 Engines for Caterpillar Built Machines Idle Speed Is High
3500 Engines Turbocharger - Assemble
3500 Engines Turbocharger - Disassemble
Inspection of Rear Engine Mounts on 3500 Family of Engines {1152, 1154} Inspection of Rear Engine Mounts on 3500 Family of Engines {1152, 1154}
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz DC Bus Voltage - Test
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Input Power - Test
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Manual Transfer - Check
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz On-Battery - Check
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Power Supply - Check
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz System Startup
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Unit Final Check
797F and 797F XQ Off-Highway Trucks Machine Systems Hood (Rear) - Remove and Install
C4.4 Industrial Engine Turbocharger - Inspect
797F and 797F XQ Off-Highway Trucks Machine Systems Gear Pump (Brake, Hoist) - Remove and Install
UPSB130 Uninterruptible Power Supply UPS Battery - 60Hz General Information
UPSB130 Uninterruptible Power Supply UPS Battery - 60Hz IGBT for CSIEN-CSION-CSPEN Circuit Board - Replace
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.