EMCP4.1/EMCP4.2 Caterpillar


Engine Cooldown Warning

Usage:

C18 DTP
System Operation Description:

The following conditions cause the engine to enter a stop mode

  • Loss of a remote initiate signal when in auto mode

  • Activation of the stop signal input

  • A soft shutdown response of the ECMP

  • A data link message calling for an engine shutdown

If the engine is running, the engine will continue to run in cooldown. When the cooldown interval is complete, the engine will stop. An immediate shutdown due to a critical fault will cause the engine to shutdown and the cooldown timer to be bypassed.

Reference: For more information on setting the cooldown duration setpoint, see Testing and Adjusting, "Electronic Control Module (Generator Set) - Configure",

Conditions Which Generate This Code:

The code for the engine cooldown is generated when the EMCP 4 determines that an engine cooldown is in progress. The engine will continue to run until the cooldown duration time has expired.

Test Step 1. TALK TO THE OPERATOR

Note: No repair to the engine is necessary.

  1. Determine the conditions that caused the diagnostic code.

Expected Result:

A shutdown was initiated by the operator or by the software that caused the engine to enter into the cooldown mode.

Results:

  • OK -

    STOP