Note: This diagnostic code is only applicable to gensets that have an MCS control panel.
The Electronic Control Module (ECM) detects the following conditions:
- The signal frequency from the PWM converter is less than 150 Hz or the signal frequency is greater than 1050 Hz for more than two seconds.
- The ECM has been powered for at least three seconds.
- Diagnostic code 0091-03 is not active.
- Diagnostic code 0091-04 is not active.
- Diagnostic codes for the 8 Volt sensor supplies are not active.
System Response:
The ECM sets the "Throttle Position" to "0%". "DIAG" will be displayed next to the status for "Throttle Position" on the electronic service tool.
A warning will appear on the display on the control panel. The warning lamp or the shutdown lamp may illuminate and the warning horn may sound. If equipped, the diagnostic lamp will flash the diagnostic code. The diagnostic code will be logged if the engine is running. The diagnostic code will not be logged if the engine is cranking.
The engine will remain at low idle while the diagnostic code is active.
Throttle inputs are ignored by the ECM until the fault is repaired.
Throttle inputs will also be ignored by the ECM until the keyswitch has been turned to the OFF position and then back to the ON position.
This diagnostic code indicates that the frequency of the PWM converter is out of the normal range.
Test Step 1.
Refer to the OEM documentation for the PWM converter.
Results:
- OK - STOP