Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


GSC CID 1170 - FMI 02

Usage:

C32 SXC
Conditions Which Generate This Code:

The Bus Transformer Box (BTB +) reduces the AC line to neutral voltages of phase A and phase C from the bus to usable signal levels for the GSC+P. The GSC+P uses these reduced signals for detecting the phase angle with the generator. The GSC+P also uses these reduced signals for detecting the phase sequence of the bus. The GSC+P will utilize the signal of phase A in order to measure the amplitude of the voltage on the bus. The GSC+P will utilize the signal of phase C in order to measure the frequency of the voltage on the bus.

The possible cause of a CID 1170 FMI 02 is a short between the input of phase A and the input of phase B of the BTB+. This would cause a phase angle of approximately 0°.

Test Step 1. CHECK THE PHASE ANGLE OF THE INPUTS TO THE BUS TRANSFORMER BOX (BTB +)




    Illustration 1g00603288

    Bus transformer box

  1. Stop the engine. Turn the Engine Control Switch (ECS) to "STOP".

  1. Remove the two fuses from the BTB +.

  1. Measure the resistance of the fuses with a digital multimeter.

Expected Result:

The resistance should be less than 1.0 ohms.

Results:

  • OK - The resistance is less than 1.0 ohms. The fuses have not failed. Install the fuses. Proceed to Test Step 2.

  • NOT OK - The fuses are blown. Replace the fuses. Proceed to Test Step 2.

Test Step 2. CHECK THE VOLTAGE ON THE INPUT OF THE BTB+

  1. Start the engine and run the engine at rated speed.

  1. The Bus must be live. Close the breaker of the generator.

  1. Use a digital multimeter and measure the voltage between "B1" and "B2" on the BTB+.

Expected Result:

The voltage between "B1" and "B2" of the generator is the same as the line to line voltage.

Note: If external potential transformers for medium and high voltage generators are present, the voltage will be the same as the secondary of the potential transformer.

Results:

  • OK - The voltage is correct. Proceed to Test Step 4.

  • NOT OK - The voltage is not correct. Proceed to Test Step 3.

Test Step 3. CHECK THE BTB+ INPUT CIRCUIT

  1. Stop the engine. Turn the ECS to "STOP". Ensure that no other source is connected to the bus.

  1. Disconnect the wires labelled "E486" and "E488" from the BTB+ terminals.

  1. Measure the resistance between "E486" and "E488" and on the BTB+.

Expected Result:

The resistance should be 2140 ohms ±400 ohms.

Results:

  • OK - The resistance is correct. There is a failure in the wiring between the BTB+ and the generator.

    Repair: Use the System Schematic for the BTB+ and the AC schematic in order to troubleshoot the wiring and find the exact cause of the diagnostic code. Refer to Testing And Adjusting, "Schematics And Wiring Diagrams".

    STOP

  • NOT OK - The resistance is not correct. BTB+ has failed.

    Repair: The BTB+ has failed. Replace the BTB+. Refer to Testing And Adjusting, "EMCP Electronic Control (Bus Transformer Box) - Replace".

    STOP

Test Step 4. CHECK VOLTAGE ON GSC+P INPUT

  1. Stop the engine.

  1. Install cable probes on the GSC+P pins 17 and 18 of the 40-pin connector.

  1. Start the engine. The engine is running at rated speed.

  1. Measure the voltage between pin 17 and pin 18 of the GSC+P connector.

Expected Result:

The voltage should be equal to the voltage measured in Test Step 2 divided by 15 ± 2% (14.7 to 15.3).

Results:

  • OK - The voltage is correct. CID 1170 FMI 2 is still active. The GSC+P may have failed.

    Repair: It is unlikely that the GSC+P has failed. Exit this procedure and perform this entire procedure again. If the result is the same, replace the GSC+P. Refer to Testing and Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    STOP

  • NOT OK - The voltage is not correct. Proceed to Test Step 5.

Test Step 5. CHECK VOLTAGE ON BTB+ OUTPUT

  1. Stop the engine.

  1. Install cable probes between pin A and pin B of three terminal connector "J1" on the BTB+.

  1. Start the engine and run the engine at rated speed.

  1. Measure the voltage between pin A and pin B of "J1".

Expected Result:

The voltage should be equal to the voltage measured in Test Step 2 divided by 15 ± 2% (14.7 to 15.3).

Results:

  • OK - The voltage is correct. There is a wiring failure between the GSC+P and the BTB+.

    Repair: Use the System Schematic for the BTB+ and the AC schematic in order to troubleshoot the wiring and find the exact cause of the diagnostic code. Testing And Adjusting, "Schematics And Wiring Diagrams".

    STOP

  • NOT OK - The voltage is not correct. Proceed to Test Step 6.

Test Step 6. CHECK THE BTB+ OUTPUT CIRCUIT

  1. Stop the engine.

  1. Disconnect three terminal connector J1 on the BTB+.

  1. Measure the resistance from pin A to pin B of J1.

Expected Result:

The resistance should be 14.6 ohms ± 3.0 ohms.

Results:

  • OK - The resistance is correct. There may be an intermittent problem.

    Repair: The system may need to be reset. Shut down the system by turning the ECS to the OFF/RESET position. Then, restart the genset and verify that the genset is operating properly. Watch the genset for any recurrence of the problem.

    STOP

  • NOT OK - The resistance is not correct. The BTB+ is faulty.

    Repair: The BTB+ has failed. Replace the BTB+. Refer to Testing and Adjusting, "EMCP Electronic Control (Bus Transformer Box) - Replace"

    STOP

Caterpillar Information System:

Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1169 - FMI 02
2008/01/01 An Improved Three-Piece Oil Pan Gasket is Now Used {1302, 7555}
2008/01/07 An Improved Three-Piece Oil Pan Gasket is Now Used {1302, 7555}
C175-16 Engine for 795F Series AC Off-Highway Trucks Connecting Rod - Type 1
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1168 - FMI 04
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1168 - FMI 03
2008/01/21 A New Lubricator for the Air Starting Motor is Now Used {1451}
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1167 - FMI 04
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1038 - FMI 04
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1038 - FMI 03
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0858 - FMI 03
G3520C and G3520E Generator Set Engines Fuel Control Valve - Remove and Install
3516C Generator Set Engine Air Shutoff - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1170 - FMI 04
2007/12/24 An Improved Method of Mounting the Air Compressor Is Now Used {1803}
TH55-E70 and TH55-E90 Petroleum Transmissions Gear Pump (Torque Converter and Transmission) - Remove
TH55-E70 and TH55-E90 Petroleum Transmissions Gear Pump (Torque Converter and Transmission) - Install
C7 and C9 On-highway Engines Monitoring System - Additional Information for Caterpillar Model Year 2008 On-highway Engines Regulated by the California Air Resources Board
C13T-TH35 and C15T-TH35 Petroleum Packages Monitoring System - Additional Information for Caterpillar Model Year 2008 On-highway Engines Regulated by the California Air Resources Board
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 1170 - FMI 08
G3600 Engines Cylinder Combustion - Test
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Sensor Supply - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) AL Fault Code
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) SP Fault Code
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.