100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Caterpillar


General Information

Usage:

C-12 BCY



Illustration 1g01222249

Digital Voltage Regulator

(1) Display

(2) Keypad

(3) J1 connector

(4) Screw terminals

Display (1) of the digital voltage regulator, shows numbers that represent different parameters of the digital voltage regulator system. Keypad (2) is used to change the information that is shown on display (1). J1 connector (3) is used to join the digital voltage regulator to a personal computer. Screw terminals (4) are used to join the digital voltage regulator to the generator and various customer options.

The digital voltage regulator is a microprocessor based voltage regulator. The main purpose of the digital voltage regulator is to regulate output voltage of a generator which is used with an engine generator set. Service personnel can modify (configure) certain regulation characteristics. The modifications will allow the engine generator set performance to be optimized. The digital voltage regulator can also integrate into one package many options that were previously panel mounted. The options include KVAR/PF controller, overexcitation protection, fault detection, overvoltage protection, undervoltage protection, diode monitor, reverse power relay and system parameter monitoring.

The configurable parameters of the digital voltage regulator are listed below.

  • Voltage versus frequency (V/Hz) characteristic

  • Fine voltage level adjustment

  • Droop adjustment

  • Overvoltage trip point with adjustable trip time

  • Undervoltage trip point with adjustable trip time

  • Gain

  • Single-phase or three-phase true RMS sensing

  • Underfrequency trip point

  • Knee frequency

  • Performance gains

  • Generator set parameters

  • Minimum voltage

  • Diode monitor ripple level

  • Reverse VAR trip time

  • Reverse power trip point with adjustable trip time

  • Optional KVAR level

  • Optional power factor level

The protective functions that the digital voltage regulator provides are listed below.

  • Overvoltage protection

  • Undervoltage protection

  • Loss of sensing

  • Rotating diode monitor

  • Overexcitation protection

  • Reverse VAR detection

  • Underfrequency protection

  • Instantaneous field over current trip

  • Optional reverse power relay

  • Loss of frequency

The digital voltage regulator can be set up for a specific application by using the configurable parameters. Parameters are preset at the factory. Parameters may need to be adjusted in order to meet the specific requirements of a site. The digital voltage regulator also detects faults and sets the appropriate alarm or caution. Certain system parameters can also be monitored on the display of the digital voltage regulator.

Caterpillar Information System:

C-15, C-16, and C-18 Truck Engines Flywheel
C15 and C18 Engines for Caterpillar Built Machines Flywheel
C13, C15, and C18 Tier 4 Final Engines Flywheel
C27 and C32 Generator Set Engines Housing (Front) - Install
C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Engine Will Not Crank
C27 and C32 Generator Set Engines Housing (Front) - Remove
TH31-E61 and TH35-E81 Petroleum Transmissions Breather (Transmission) - Clean
2005/12/12 Remove Certain 6D-7726 Hose Assemblies from Inventory {0738}
TH31-E61 and TH35-E81 Petroleum Transmissions Reference Material
C27 and C32 Generator Set Engines Engine Support (Front) - Remove and Install
C6.6 Generator Set E539 High Intake Manifold Air Temperature
C6.6 Generator Set E361 High Engine Coolant Temperature
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Dimensions
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Electrical
C27 and C32 Generator Set Engines Cylinder Head - Remove
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Display and Keypad
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Startup Profile Function
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Loading and Stopping Profile
C27 and C32 Generator Set Engines Cylinder Head - Install
C15 and C18 Industrial Engines Flywheel Housing
C9 On-highway Engine Air Inlet Heater
C27 and C32 Generator Set Engines Camshaft - Remove
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Voltage Regulation
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Line Loss Compensation
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.