100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Caterpillar


Display and Keypad

Usage:

C-12 BCY



Illustration 1g00538863

Display And Keypad

(1) Display

(2) Keypad

(3) Function key

(4) Scroll down key

(5) Scroll up key

Note: For a list of parameter codes and the corresponding range of values, see System Operation, "Parameters".

Display (1) and keypad (2) are used to select and manipulate parameter values that control the operation of the digital voltage regulator. Display (1) of the digital voltage regulator has four digits. A colon in the display indicates that the number showing is a parameter code. If a colon is not present, then the number showing is a parameter value. A decimal point in the display is used to indicate the precision of the parameter value.

Keypad (2) has three keys. The keys are listed below.

  • Function key (3)

  • Scroll down key (4)

  • Scroll up key (5)

Display (1) has two modes, parameter code mode and parameter value mode. Function key (3) is used to toggle back and forth between the two modes. Scroll down key (4) and scroll up key (5) are used to decrease and increase the parameter number or value number that is showing on display (1).

Table 1
Parameter Code     Parameter Value    
:01     0480    
0481
0482
0483
:02     0001    
0002
0003
0004
:03     0004    
0003
0002
:04     0100    
0099
0100
0101

The operation of display (1) and keypad (2) can be described as a table. Pressing function key (3) toggles the display back and forth between the two columns of the table (parameter code and parameter value). If a colon is present, the display is in parameter code mode. If a colon is not present, the display is in parameter value mode.

Pressing a scroll up key (5) or scroll down key (4) will increase or decrease the display to the next number within a column. Use of the scroll keys cannot cause the display to change columns of the table.

In order to configure a parameter code (change the value), follow the procedure below.

  1. Select the desired parameter code by pressing scroll key (4) or (5) .

  1. Access the parameter value by pressing function key (3) .

  1. Select the desired parameter value by pressing scroll key (4) or (5) .

  1. Enter the chosen value into the memory of the digital voltage regulator by pressing function key (3) .

Example




Illustration 2g00538864

Example Illustration - Display Shows Parameter Code Of :01

(1) Display

(2) Keypad

(3) Function key

(4) Scroll down key

(5) Scroll up key

This example is a demonstration of scrolling and selection of parameter codes. Also the scrolling and configuration of values is demonstrated.

After the digital voltage regulator is powered up (battery voltage applied) parameter code ":01" is shown on the display. The engine does not have to be running for the digital voltage regulator to show parameter codes. The colon indicates that a parameter code is being shown.

The user has the option of pressing function key (3), scroll down key (4), or scroll up key (5) .

If scroll up key (5) is pressed, the display moves (scrolls) up to the next parameter code, ":02". Again, the colon is on. This is the entry point for parameter code :02.

Then, if scroll down key (4) is pressed, the display moves (scrolls) down to the preceding parameter code, ":01" again.

If scroll down key (4) is pressed again, the display moves (scrolls) to the highest parameter code, ":96".

Note: When scroll key (4) or (5) is held down for more than five seconds, the display will scroll rapidly. Otherwise, the display changes at the rate of one parameter per second.




Illustration 3g00538865

Example Illustration - Display Shows Value Of "0480"

Note: The value of some parameter codes is only for viewing by the user. Such parameters are not configurable. See System Operation, "Parameters". View the value. Then, press function key (3) in order to return the display to showing parameter codes.

If function key (3) is pressed, the display changes to show the value "0480" of parameter code :01. Notice that the colon is off. The value of parameter code :01 can now be changed (configured).

If scroll up key (5) is pressed, the display moves (scrolls) up to the next value, "0481". The colon remains off.

Then if scroll down key (4) is pressed, the display moves (scrolls) down to the preceding value, "0480" again.

To enter (configure) a new value for a parameter code, scroll the display until the desired new value is showing, then press function key (3). Now, the new value is entered into the memory of the digital voltage regulator. The display returns to showing the parameter codes.

Caterpillar Information System:

C27 and C32 Generator Set Engines Cylinder Head - Remove
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Electrical
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Dimensions
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator General Information
C-15, C-16, and C-18 Truck Engines Flywheel
C15 and C18 Engines for Caterpillar Built Machines Flywheel
C13, C15, and C18 Tier 4 Final Engines Flywheel
C27 and C32 Generator Set Engines Housing (Front) - Install
C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Engine Will Not Crank
C27 and C32 Generator Set Engines Housing (Front) - Remove
TH31-E61 and TH35-E81 Petroleum Transmissions Breather (Transmission) - Clean
2005/12/12 Remove Certain 6D-7726 Hose Assemblies from Inventory {0738}
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Startup Profile Function
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Loading and Stopping Profile
C27 and C32 Generator Set Engines Cylinder Head - Install
C15 and C18 Industrial Engines Flywheel Housing
C9 On-highway Engine Air Inlet Heater
C27 and C32 Generator Set Engines Camshaft - Remove
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Voltage Regulation
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Line Loss Compensation
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Reactive Voltage Droop
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Cross Current Compensation
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator KVAR Regulation
100-200 kW Tactical Quiet Generator (TQG) Digital Voltage Regulator Power Factor Regulation
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.