C9 Marine Auxiliary and Marine Generator Set Engines Caterpillar


CID 0269 FMI 03 Sensor Supply too high

Usage:

C9 C9A
Conditions Which Generate This Code:

The Electronic Control Module (ECM) detects supply voltage that is above 5.16 VDC for one second.

System Response:

The ECM will log the diagnostic code. The ECM flags all analog sensors as invalid data and all analog sensors are set to the respective default values.

Low power

Test Step 1. Perform the following diagnostic procedure: Analog Sensor Supply Circuit - Test

Results:

  • OK - STOP