Power Module Switchgear (Low Voltage and Medium Voltage) Caterpillar


Contactors

Usage:

PM3508 BLM

Low Voltage




Illustration 1g00845479

Motor Contactors

(1) Motor contactor for the crankcase breather (gas engine only)

(2) 100 hp motor control starter for the radiator fan (3516B engines only)

(3) Auxiliary contacts for the contactor for the fan motor

(4) Overload relay for the crankcase breather motor contactor (heater type relay)

(5) Overload relay for the contactor for the fan motor (heater type relay)

The motor contactor for the crankcase breather (1) is optional equipment for gas engines. This motor contactor is used only on gas engines.

Motor contactors are equipped with thermal type overloads. These thermal type overloads protect against the following failures: motor, cables for the motor and switchgear. The thermal type overloads have a factory preset value for overcurrent. If the overload trips the overload must be manually reset.

------ DANGER! ------

The motor starter compartment should not be accessed unless the equipment is de-energized. Personal injury and/or damage to the switchgear could occur if the motor starter compartment is accessed when the equipment is energized. Do not operate the power module if the cover for the motor starter compartment is not installed. Ensure that the cover for the motor starter compartment is installed. Bodily contact with electrical potential will cause personal injury or death.


Medium Voltage




Illustration 2g00850969

Motor Contactor

(6) Motor fuses (5 kV)

(7) Vacuum interrupter/contactor (5 kV)

(8) Door operated safety switch

(9) Metallic guard (not shown)

(10) Terminal board and circuit board

A metallic guard (9) attaches with six bolts in order to enclose the 5 kV equipment.

------ DANGER! ------

The metallic guard is installed on the equipment before the equipment is shipped. Do not operate the equipment if the metallic guard is not properly installed. Use the bolts that are provided in order to reinstall the metallic guard if the guard is removed. Operating the equipment without the metallic guard installed may result in personal injury or death by electrocution. Bodily contact with electrical potential will cause personal injury or death.


Note: The door operated safety switch (8) is the limit switch for the left top door. The door operated safety switch trips the generator circuit breaker and the door operated safety switch commands the genset to shut down.

Caterpillar Information System:

TK711, TK721, TK722 and TK732 Track Feller Bunchers Mounting and Dismounting
Power Module Switchgear (Low Voltage and Medium Voltage) Safety Signs and Labels
2001/11/01 Methods For Submitting Feedback For Service Information {1000}
3054 and 3056 Marine Generator Set Engines Fuel System - Prime
SCT673 Truck Mounted PumperPOD Hydraulic System Oil Filter - Replace
312C Excavator Machine System Specifications Travel Motor Guard
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Recoil Spring - Assemble
3054 and 3056 Marine Generator Set Engines Fuel Injection Timing - Check
3054 and 3056 Marine Generator Set Engines Cooling System
Electronic Installation Guide{1000} Electronic Installation Guide{1000}
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Recoil Spring - Disassemble
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Front Idler - Assemble
3054 and 3056 Engines 520 Generator Set Control Panel Control Module - Replace
Power Module Switchgear (Low Voltage and Medium Voltage) Model View Illustrations
Power Module Switchgear (Low Voltage and Medium Voltage) Control Panel
Power Module Switchgear (Low Voltage and Medium Voltage) Power Distribution Panel
Power Module Switchgear (Low Voltage and Medium Voltage) Protective Relays
Power Module Switchgear (Low Voltage and Medium Voltage) Switches
Power Module Switchgear (Low Voltage and Medium Voltage) Indicators
3054 and 3056 Engines 550 Generator Set Control Panel General Information
3054 and 3056 Engines 520 Generator Set Control Panel Service Tools
G3500B Engines Ignition System Spark Plugs - Inspect/Adjust/Replace - Spark Plugs with Adjustable Electrode Gaps
Power Module Switchgear (Low Voltage and Medium Voltage) Display Overview
Power Module Switchgear (Low Voltage and Medium Voltage) Main Screen
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.