User Programmable Remote Input Contacts
Each of the six user programmable remote input contacts has an operating parameter. The operating parameter is used in order to configure that contact.
The following list of functions can be assigned to the remote input contacts by entering the parameter in the operating parameter for the associated remote input. The default function assignment is listed in table 2.
Function List for the Input Contact     | |
---|---|
Function     | Description     |
0     | No function     |
1     | On Generator When On Generator different limits can be set for the Transient Voltage Detection, Maximum Input Current and the Walk-in Rate operating parameters     |
2     | Remote switch UPS to Bypass     |
3     | Remote switch UPS On-line (only if no errors are active)     |
4     | Building Alarm 1 - will trigger External Alarm output contact     |
5     | Building Alarm 2 - will trigger External Alarm output contact     |
6     | Building Alarm 3 - will trigger External Alarm output contact     |
7     | Building Alarm 4 - will trigger External Alarm output contact     |
8     | Fire Alarm - will trigger External Alarm output contact     |
9     | Remote Alarm Silence - Silences the buzzer or a Notice or Alarm is active     |
10     | Gen Set Start Breaker Open (i.e., if breaker required by code, notice of no gen set start power) - Prints a breaker open message when input is activated and a breaker closed message when the input is deactivated     |
11     | Room Temperature Abnormal - Prints a message when input is activated and a different message when input is deactivated     |
Default Function Assignments for the Input Contacts     | ||
---|---|---|
Contact     | Function     | Description     |
1     | 1     | On Generator     |
2     | 2     | Remote switch UPS to Bypass     |
3     | 3     | Remote switch UPS On-line (only if no errors are active)     |
4     | 4     | Building Alarm 1     |
5     | 5     | Building Alarm 2     |
6     | 6     | Building Alarm 3     |
User Programmable Remote Output Contacts
Each of the eight user programmable remote output contacts has an operating parameter that is used to configure that contact. The following list of functions can be assigned to the remote output contacts by entering the parameter in the operating parameter for the associated remote output. The default function assignment is listed in table 4.
Function List for the Output Contact     | |
---|---|
Function     | Description     |
0     | No function     |
1-100     | Flywheel Percent Energy - Flywheel has the programmed percentage of usable energy available and the system is on-line.     |
101     | On-line (normal)     |
102     | On Bypass     |
103     | Flywheel Discharging     |
104     | Notice or Alarm Condition is active     |
105     | Alarm Condition is active     |
106     | Overload     |
107     | Cabinet over temperature     |
108     | External Alarm Active - Activated by programming remote inputs to any of the Building Alarms or the Fire Alarm function     |
109     | Aux Generator set Start unavailable     |
110     | Overload Bypass - system is in bypass because of an overload condition     |
111     | DC Bus Capacitor Fusible Link Blown     |
112     | Fan Failure     |
Default Function Assignments for the Output Contacts     | ||
---|---|---|
Contact     | Function     | Description     |
1     | 101     | On-line (normal)     |
2     | 102     | On Bypass     |
3     | 103     | Flywheel Discharging     |
4     | 50     | Flywheel Percent Energy     |
5     | 104     | Notice or Alarm Condition is active     |
6     | 105     | Alarm Condition is active     |
7     | 106     | Overload     |
8     | 107     | Cabinet over temperature     |