Illustration 1 | g00559078 |
Control Panel (AC Power) |
Power Disconnect
Illustration 2 | g00559495 |
Rotary Switch (Disconnect) |
(1) 128-8084 Rotary Switch (Disconnect)
- Current Rating ... 60 Amp
- Voltage Rating ... 600 VAC or 250 VDC
- Wire Size ... #14 to #4
- Terminal Torque ... 3.95 N·m (35 lb in)
- Voltage Rating ... 600 VAC or 250 VDC
(2) Fuses
Part Number     | Capacity     | Use     |
---|---|---|
144-0434     | 25 Amp     | without Jacket Water Heater     |
128-8074     | 40 Amp     | with Jacket Water Heater     |
Circuit Breakers
Illustration 3 | g00559122 |
Single Pole Circuit Breaker |
125-9963 Circuit Breaker
- Current Rating ... 16 Amp at 25 °C (77 °F)
- Wire Size ... #18 to #4
128-8063 Circuit Breaker
- Current Rating ... 13 Amp at 25 °C (77 °F)
- Wire Size ... #18 to #4
Illustration 4 | g00559185 |
2 Pole Circuit Breaker |
128-8062 Circuit Breaker
- Current Rating ... 16 Amp at 25 °C (77 °F)
- Wire Size ... #18 to #4
128-8065 Circuit Breaker
- Current Rating ... 10 Amp at 25 °C (77 °F)
- Wire Size ... #18 to #4
Illustration 5 | g00559213 |
3 Pole Circuit Breaker |
128-8066 Circuit Breaker
- Current Rating ... 10 Amp at 25 °C (77 °F)
- Wire Size ... #18 to #4
Motor Starters
Illustration 6 | g00559219 |
Motor Starter Contactor |
128-8070 Motor Starter Contactor
- Voltage Rating ... 600 Volts
- Current Rating ... 25 Amp
- Wire Size ... #10 to #16
- Terminal Torque ... 2.26 N·m (20 lb in)
- Current Rating ... 25 Amp
Contactors
Illustration 7 | g00559254 |
Contactor |
Illustration 8 | g00559749 |
Internal Diagram of the Contactor Terminal (A1) and Terminal (A2) are for the Coil. Terminal (L1), Terminal (L2), and Terminal (L3) are the Line Terminals. Terminal (T1), Terminal (T2), and Terminal (T3) are the Load Terminals. |
128-8077 Contactor
- Coil Voltage ... 24 VDC
- Wire Size ... #18 to #10
- Maximum Inductive Current ... 9 Amp
- Maximum Resistive Current ... 20 Amp
- Wire Size ... #18 to #10
128-8080 Contactor
- Coil Voltage ... 120 VAC
- Wire Size ... #18 to #10
- Maximum Inductive Current ... 9 Amp
- Maximum Resistive Current ... 20 Amp
- Wire Size ... #18 to #10
128-8083 Contactor
- Coil Voltage ... 24 VDC
- Wire Size ... #18 to #10
- Maximum Inductive Current ... 18 Amp
- Maximum Resistive Current ... 35 Amp
- Wire Size ... #18 to #10
Transformer
Illustration 9 | g00559304 |
Transformer |
Power Rating ... 3 kVA
Voltage     | Connect     | Line     | |
---|---|---|---|
High     | Low     | ||
480     |     | H2-H3     | H1-H4     |
240     |     | H1H3-H2H4     | H1-H4     |
240     | X2-X3     | X1-X4     | |
120     | X1X3-X2X4     | X1-X4     |