C15 Generator Set Caterpillar


Maintenance Interval Schedule

Usage:

C15 AR2

When Required

Battery - Recycle
Battery - Replace
Battery or Battery Cable - Disconnect
Circuit Breakers - Reset
Coolant Extender (ELC) - Add
Fuel System - Prime
Generator - Dry
Generator Load - Check
Generator Set - Test

Every Week

Battery Electrolyte Level - Check
Coolant Level - Check
Electrical Connections - Check
Engine Air Cleaner Service Indicator - Inspect
Engine Oil Level - Check
Fuel System Primary Filter/Water Separator - Drain
Fuel Tank Water and Sediment - Drain
Generator - Inspect
Generator Lead (Flat Braided Cable) - Check
Jacket Water Heater - Check
Power Factor - Check
Voltage and Frequency - Check
Walk-Around Inspection

Every 200 Service Hours or 1 Year

Engine Oil and Filter - Change

Every 6 Months

Coolant Sample (Level 1) - Obtain
Generator Lead (Round Cable) - Check

Every Year

Alternator - Inspect
Belts - Inspect/Adjust/Replace
Coolant Sample (Level 2) - Obtain
Cooling System Supplemental Coolant Additive (SCA) - Test/Add
Crankshaft Vibration Damper - Inspect
Engine - Clean
Engine Air Cleaner Element (Dual Element) - Inspect/Clean/Replace
Engine Crankcase Breather - Clean
Engine Mounts - Inspect
Engine Oil Sample - Obtain
Engine Protective Devices - Check
Engine Speed/Timing Sensor - Clean/Inspect
Engine Valve Lash - Check
Engine Valve Rotators - Inspect
Fuel System Primary Filter (Water Separator) Element - Replace
Fuel System Secondary Filter - Replace
Generator Set Vibration - Inspect
Grounding Stud - Inspect/Clean/Tighten
Hoses and Clamps - Inspect/Replace
Rotating Rectifier - Inspect/Test
Starting Motor - Inspect
Water Pump - Inspect

Every 3 Years

Coolant (DEAC) - Change
Coolant Temperature Regulator - Replace
Ether Starting Aid Cylinder - Replace
Turbocharger - Inspect

Every 6 Years

Coolant (ELC) - Change

Overhaul

Overhaul Considerations

Commissioning

Generator Set Alignment - Check

Caterpillar Information System:

UPS 250 and UPS 300 Uninterruptible Power Supplies Maintenance Interval Schedule
UPS 250 and UPS 300 Uninterruptible Power Supplies Status Messages
UPS 250 and UPS 300 Uninterruptible Power Supplies Telemetry Parameters
UPS 250 and UPS 300 Uninterruptible Power Supplies Troubleshooting
UPS 250 and UPS 300 Uninterruptible Power Supplies Sight Gauge - Clean
UPS 250 and UPS 300 Uninterruptible Power Supplies Oil Level - Check
UPS 250 and UPS 300 Uninterruptible Power Supplies Oil - Change
UPS 250 and UPS 300 Uninterruptible Power Supplies Flywheel - Clean
UPS 250 and UPS 300 Uninterruptible Power Supplies DC Bus Capacitor - Replace
UPS 250 and UPS 300 Uninterruptible Power Supplies Bearing (3.5 EVD or Greater) - Replace
UPS 250 and UPS 300 Uninterruptible Power Supplies Bearing (Earlier) - Replace
UPS 250 and UPS 300 Uninterruptible Power Supplies Battery - Replace
C15 Generator Set Maintenance Interval Schedule
C7.1 Commercial Marine Engine Crankcase Breather Ejects Oil
C7.1 Commercial Marine Engine Crankcase Fumes Disposal Tube Has Oil Draining
C27 Generator Set Maintenance Interval Schedule - Prime
C27 Generator Set Maintenance Interval Schedule - Standby
C7.1 Commercial Marine Engine Cylinder Is Noisy
C7.1 Commercial Marine Engine Electronic Service Tool Does Not Communicate
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Maintenance Interval Schedule
C7.1 Commercial Marine Engine Engine Cranks but Does Not Start
C7.1 Commercial Marine Engine Engine Does Not Crank
SPF343 and SPF343C Trailer Mounted Pumpers Product Description
C4.4 Marine Generator Set Maintenance Interval Schedule
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.