SRMP Electric Power Generation SRMP Generator Caterpillar


Generator - Dry

Usage:

C18 SSM


NOTICE

Do not operate the generator if the windings are wet. If the generator is operated when the windings are wet, damage can occur due to insulation breakdown.


When moisture is present or when moisture is suspected in a generator, the generator must be dried before being energized. For information on drying the generator, refer to Testing and Adjusting, "Insulation - Dry".

If the drying procedure does not restore the insulation resistance to an acceptable value, the winding should be reconditioned.

Note: For additional information, refer to Special Instruction, SEHS9124 .

Drying Methods

The following methods can be used for drying a generator:

  • Self-circulating air method

  • Oven method

  • Controlled current method


NOTICE

Do not allow the winding temperature to exceed 85 °C (185.0 °F). Temperatures that are greater than 85 °C (185.0 °F) will damage the winding insulation.


Self-Circulating Air Method

Run the engine and disconnect the generator load. running the engine will help circulate air. Operate the generator space heaters.

Oven Method

Place the entire generator inside a forced air drying oven for 4 hours at 65 °C (149 °F).


NOTICE

Use a forced air type oven rather than a radiant type oven.

Radiant type ovens can cause localized overheating.


Controlled Current Method



Illustration 1g00614674
External Power Source Circuit
(1) Battery (12 VDC)
(2) Rheostat (15 Ohm 25 W)
(3) Exciter field (stator "L1")

Table 1
TOOLS NEEDED 
Part Number  Tool  Quantity 
225-8266  Clamp-on Ammeter (1200 A) 
  External Power Source Circuit 

Heat can be used in order to dry the generator windings. This heat can be created by allowing a controlled current to flow through the generator. No high voltages are generated during the following procedure. Therefore, insulation breakdown will not occur.

  1. Make an external power source. Refer to Illustration 1.

  2. Disconnect F1+ from the voltage regulator. Disconnect F2- from the voltage regulator. Disconnect the generator load. Connect the generator output leads T0, T1, T2, and T3 together. Install the clamp-on ammeter to generator output lead T1.

    Note: When the line current is measured on multiple lead units, measure the current in each conductor per phase. The currents can then be added.

  3. Refer to Illustration 1. Adjust the rheostat to the maximum resistance value. Connect the external power source to wires F1+ and F2-.

  4. Start the generator set. Run the generator set at idle speed.


    NOTICE

    Do not exceed the rated phase current that is listed on the generator nameplate. Exceeding the rated phase current will easily damage the generator windings.


  5. Monitor the phase current. Gradually increase the engine RPM. Increase the engine RPM until one of the following conditions are met:

    • The rated phase current is obtained.

    • The full generator set speed is obtained.

  6. If more phase current is necessary, slowly turn the rheostat. Turn the rheostat until the rated phase current is reached.

  7. On an hourly basis, stop the drying procedure. Check the insulation resistance. Repeat the above steps until the insulation resistance is acceptable.

Caterpillar Information System:

SRMP Electric Power Generation SRMP Generator Resistor - Test
SRMP Electric Power Generation SRMP Generator Insulation - Test
SRMP Electric Power Generation SRMP Generator Winding - Test
SRMP Electric Power Generation SRMP Generator Rotating Rectifier - Test
SRMP Electric Power Generation SRMP Generator Varistor - Test
SRMP Electric Power Generation SRMP Generator Generator Set - Test
SRMP Electric Power Generation SRMP Generator Troubleshooting
SRMP Electric Power Generation SRMP Generator Service Tools
SRMP Electric Power Generation SRMP Generator General Information
SRMP Electric Power Generation SRMP Generator Glossary
3516C Industrial Engine Product Description
SRMP Electric Power Generation SRMP Generator Generator Operation
SRMP Electric Power Generation SRMP Generator Leads - Connect
SRMP Electric Power Generation SRMP Generator Exciter Field - Flash
SRMP Electric Power Generation SRMP Generator Generator - Remove
SRMP Electric Power Generation SRMP Generator Generator - Install
SRMP Electric Power Generation SRMP Generator Generator - Align
SRMP Electric Power Generation SRMP Generator Lead Connections
525D, 535D, 545D and 555D Wheel Skidders General Information
3516E Generator Set Model View Illustrations
3516E Generator Set Product Description
C15 and C18 Engines for Caterpillar Built Machines Engine Oil Pan - Remove and Install
463-3475 Well Stimulation Pump Crankshaft Lifting Device{0374, 0599, 0632, 0700, 1202} 463-3475 Well Stimulation Pump Crankshaft Lifting Device{0374, 0599, 0632, 0700, 1202}
2015/07/10 An Improved Alternator Mounting Group Is Now Used On Certain C15 And C18 Engines {1405}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.