SRMP Electric Power Generation SRMP Generator Caterpillar


Rotating Rectifier - Test

Usage:

C18 SSM

Table 1
TOOLS NEEDED 
Part Number  Tool  Quantity 
6V-7070  Multimeter 
243-3134(1)  Tester Group 
(1) Or equivalent.


Illustration 1g00613957
(1) Positive Rectifier Block
(2) Negative Rectifier Block
(3) Rectifier Terminal "AC1"
(4) Rectifier Terminal "AC2"
(5) Rectifier Terminal "AC3"

Note: Verify part number 9Y-0916 rectifier block date code as 0503 or greater. Refer to illustration 2. Rectifiers with a date code of 0503 and greater contain an internal varistor (CR7). Follow testing procedures with internal varistor (CR7).



Illustration 2g01229622
(6) Date code

------ WARNING! ------

Personal injury or death can result from improper troubleshooting and repair procedures.

The following troubleshooting and repair procedures should only be performed by qualified personnel familiar with this equipment.


------ WARNING! ------

Personal injury or death can result from high voltage.

When power generation equipment must be in operation to make tests and/or adjustments, high voltage and current are present.

Improper test equipment can fail and present a high voltage shock hazard to its user.

Make sure the testing equipment is designed for and correctly operated for high voltage and current tests being made.

When servicing or repairing electric power generation equipment:

  • Make sure the unit is off-line (disconnected from utility and/or other generators power service), and either locked out or tagged DO NOT OPERATE.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

------ WARNING! ------

Shut off engine and remove key before performing maintenance or repair work. Failure to do so may result in personal injury due to inadvertant machine operation.

Do not start the engine or move any of the controls if there is a “Do Not Operate” or similar warning tag attached to the start switch or controls.


------ WARNING! ------

Do not connect generator to a utility electrical distribution system unless it is isolated from the system. Electrical feedback into the distribution system can occur and could cause personal injury or death.

Open and secure main distribution system switch, or if the connection is permanent, install a double throw transfer switch to prevent electrical feedback. Some generators are specifically approved by a utility to run in parallel with the distribution system and isolation may not be required. Always check with your utility as to the applicable circumstances.


Procedure - Rectifier

The following procedure tests all six diodes within the block. If any meter reading does not fall within the given ranges, replace the rectifier block .

  1. Set the digital multimeter on the diode range. Remove all leads from the rectifier block.

  2. Place the black test lead on the positive "+" rectifier terminal. Place the red test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). All readings on the meter should be between 0.4 and 1.0.

  3. Place the red test lead on the negative "-" rectifier terminal. Place the black test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). All readings on the meter should be between 0.4 and 1.0.

  4. Place the red test lead on the positive "+" rectifier terminal. Place the black test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). In all cases, the meter should read "OL" (overload).

  5. Place the black test lead on the negative "-" rectifier terminal. Place the red test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). In all cases, the meter should read "OL" (overload).

    Note: A shorted diode can damage the exciter rotor. If a diode is shorted, check the exciter rotor. Refer to the Testing and Adjusting, "Winding - Test" and Testing and Adjusting, "Insulation - Test". Perform these tests.

    Note: For a failed rectifier block, refer to the "Diode Block Troubleshooting Guide", Table 2. The "Diode Block Troubleshooting Guide" consists of a list of items to consider when troubleshooting a failed diode block and/or external varistor (CR7). The purpose of this list is to find a cause for the diode block and/or varistor (CR7) failure which may be external to the exciter system. The purpose of this list is NOT to troubleshoot "no voltage output" from the generator.

  6. Install leads.

    • Terminal connections - 2.35 N·m (20.8 lb in) to 3.36 N·m (29.7 lb in)

    • 9Y-0916 Rectifier Assembly (mounting to heatsink) - 4.07 N·m (36 lb in) to 5.54 N·m (49 lb in)


NOTICE

Do not over-torque. Applying torques greater than the listed torques may cause damage to the components.


Procedure - Internal Varistor (CR7)

Note: Verify rectifier block date code as 0503 or greater. Refer to illustration 2. Rectifiers with a date code of 0503 and greater contain an internal varistor (CR7).

The following procedure tests the ability of the normal state of the varistor (CR7). If any meter reading does not fall within the given ranges, replace the rectifier block.

  1. Remove all leads from the rectifier block.

  2. Place the megohmmeter test leads on the rectifier block as follows:

    • Place the BLACK test lead on the negative "-" terminal.

    • Place the RED test lead on the positive "+" terminal.

    Note: The rectifier block is polarity sensitive. Damage to equipment may result in reverse polarity testing.

  3. If the megohmmeter is not capable of reading DC voltage, hook up a 1000 VDC voltmeter across the negative and positive terminals.

  4. On the megohmmeter, select and apply 1000 VDC to the varistor (CR7).

    Note: Do not apply voltage to the varistor (CR7) for greater than 3 seconds.

  5. Megohmmeter readings should be between 450 VDC and 600 VDC.

    • If the readings are greater than 600 VDC, the varistor (CR7) is OPEN.

    • If the readings are less than 450 VDC, the varistor (CR7) is SHORTED or DEGRADED.

    Note: Do not over torque. Applying torques greater than the listed torques may cause damage to the components.

  6. Install leads. Apply the following torques.

  • Terminal connections - 2.35 N·m (20.8 lb in) to 3.36 N·m (29.7 lb in)

Note: If the varistor (CR7) is found to be defective, the varistor (CR7) most likely failed due to a transient voltage surge on the main rotor winding. Varistor failure is not usually a component failure. Root causes of varistor (CR7) failure include:

  • Incorrect paralleling or loss of synchronism

  • Reverse VAR or reverse power event

  • Loss of main rotor field due to voltage regulator failure, diode rectifier failure, or other events

  • High ambient temperature (or other application error)

  • Large sudden load application

3-Diode Rectifier Block



Illustration 3g00610240
3-Diode Rectifier Block (two pieces)


Illustration 4g00613971
3-Diode Rectifier Block (two pieces)

The following procedure tests all three diodes within a block. Check the positive rectifier block and the negative rectifier block. If any meter reading does not fall within the given ranges, replace the rectifier block.

  1. Set the digital multimeter on the diode range. Remove all leads from the rectifier block.

  2. To test the negative rectifier block, follow these steps:

    1. Place the red test lead on the negative "-" terminal. Place the black test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). All readings on the meter should be between 0.4 and 1.0.

    2. Place the black test lead on the negative "-" terminal. Place the red test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). In all cases, the meter should read "OL" (overload).

  3. To test the positive rectifier block, follow these steps:

    1. Place the red test lead on the positive "+" rectifier terminal. Place the black test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). In all cases, the meter should read "OL" (overload).

    2. Place the black test lead on the positive "+" rectifier terminal. Place the red test lead on the following rectifier terminals: "AC1" (3), "AC2" (4) and "AC3" (5). All readings on the meter should be between 0.4 and 1.0.

Note: A shorted diode can damage the exciter rotor. If a diode is shorted, check the exciter rotor. Refer to the Testing and Adjusting, "Winding - Test" and Testing and Adjusting, "Insulation - Test". Perform these tests.

Note: For a failed rectifier block, refer to the "Diode Block Troubleshooting Guide", Table 2. The "Diode Block Troubleshooting Guide" consists of a list of items to consider when troubleshooting a failed diode block and/or external varistor (CR7). The purpose of this list is to find a cause for the diode block and/or varistor (CR7) failure which may be external to the exciter system. The purpose of this list is NOT to troubleshoot "no voltage output" from the generator.

Note: This configuration contains an externally mounted varistor (CR7) block. Refer to Testing and Adjusting, "Varistor - Test" section of this document. Perform the tests in the "Diode Block Troubleshooting Guide".

Table 2
Diode Block Troubleshooting Guide 
  Check For  Measurement  OK/Failed 
Diode checks?  Diode short or open.     
  Internal varistor (CR7) OK or Failed.     
 
External varistor (CR7) check - OK or Failed?  A shorted external varistor can cause diode block failure due to overcurrent.     
  A failed diode block can cause the external varistor to fail due to the loss of the main rotor circuit, overheat, and then become an open circuit.     
 
Exciter end physical inspection?  General conditions     
  Loose or missing wires.     
  Heat transfer compound under diode block.     
 
Measurements?  Exciter rotor winding resistance and insulation resistance measurement     
  Main field rotor winding resistance and insulation resistance measurement.     
  Record ambient temperature when taking winding resistance readings.     
  Record generator stator and rotor metal temperature when taking winding resistance readings.     
 
Voltage regulator functionality?  Loss of field events due to VR malfunction can cause diode block failure.     
  Under certain conditions, startup with shorted diode block can damage certain voltage regulators.     
  Voltage sensing is correctly connected and functional.     
  Voltage sensing potential transformer fuses and wiring for medium voltage and high voltage systems.     
  If applicable, B-phase current transformer (droop VAR sensing).     
  Is the VAR pf control enabled as soon as the main breaker is shut (parallel operation only)? The VAR control setpoint should not be zero.     
  After a loss of sensing, inspect and test the diode block before restarting the unit.     
 
Operating mode at time of failure?  Stand alone operation.     
  Stable load, loading up, shutting down, engine startup?     
  Load swings, motor starting, surges, or transients?     
  Engine operation OK or not?     
  List all faults and warnings from generator, engine, and switchgear.     
  Parallel to other generators?     
 
New installations?  Verify that phase rotation is correct by wiring inspection and instrument measurement.     
  How is VAR shared? Droop or cross current compensation or kVAR or pf controller? Is the VAR share working correctly?     
  How is real load (kW) shared. Is the load sharing working correctly?     
  Is the paralleling control functioning correctly (including dead bus closure).     
  Is the load sharing control functioning correctly.     
  Parallel to utility?     
  Time of day?     
  Utility voltage stable?     
 
ALL faults and alarms (both logged and active)?  Was the unit in stable operation, starting up, shutting down, or paralleling (trying to match voltage and frequency before shutting the breaker)?     
  Confirm that every engine shutdown or voltage regulator shutdown will open the main generator output breaker. How much time does it take to get the breaker open?     
  Confirm kVAR or Power factor set point for voltage regulators.     
  Check set point and correct operation of reverse VAR and reverse kW relays.     
  Check set point and correct operation of minimum excitation limiter.     
  Check set point and correct operation of maximum excitation limiter.     
  Check set point and correct operation of loss of field protection.     
 
Operating parameters at time of failure?  Confirm kW load and kVAR load.     
  Power factor, line current per phase, generator voltage.     
  Voltage regulator output current at the time of failure? (if available)     
  Cross check the kW, kVAR, line current, and power factor . Do the instruments make sense?     
  Cross check generator package instruments against switchgear or other readings to confirm Instrument performance if necessary.     

Caterpillar Information System:

Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.