UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Caterpillar


Current Transformers (Primary, Secondary)

Usage:

UPS 600G DLD

Description



Illustration 1g01273727
Primary current transformer location
(1) Primary current transformers


Illustration 2g01273731
Secondary current transformer location
(2) Secondary current transformers

Primary current transformers (1) are attached to the output of the system cabinet in order to measure the output voltage of the UPS. The primary current transformers (1) convert the current in a 1500:5 ratio. The converted current is sent to the secondary current transformers (2) on the left panel.

The three secondary current transformers (2) are located on the left panel. The secondary current transformers (2) convert the current in a 5:01 ratio. The converted current is sent to the AC Interface board.

Removal Procedure and Installation Procedure for the Primary Current Transformer

Note: Contact the technical communicator at your dealership for the removal procedure and the installation procedure of the primary current transformer (3).



Illustration 3g03371240
(3) Installed primary current transformers


Illustration 4g01273745
Wire connections for the primary current transformer

Removal Procedure for the Secondary Current Transformer

Refer to Systems Operation, Testing and Adjusting, UENR3954, "Internal Component Preremoval Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.



    Illustration 5g01273757
    Wire connections for the secondary current transformer

  1. Remove the four wires that are connected to the following posts of the current transformer (2):

    • H1

    • H2

    • X1

    • X2

    Ensure that the wires have a labeling that match the location of the wire. Refer to Illustration 5.

  2. Remove the four screws that attach the current transformer (2) to the left panel.

  3. Remove the current transformer (2) from the cabinet.

Installation Procedure for the Secondary Current Transformer

  1. Position the current transformer (2) on the left panel. Refer to Illustration 2 for the position of the current transformer (2).

  2. Attach the current transformer (2) to the left panel with four screws.

  3. Attach the four wires to the four posts of the current transformer. Refer to Illustration 5 for wire connections.

Caterpillar Information System:

UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies 24V Power Supply (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Transformer (T1 to T3)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System I/O Daughter PWA (MMS System Cabinet)
C9 Engine Coolant (DEAC) - Change
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System I/O PWA (MMS System Cabinet)
C7.1 Engines Water Temperature Regulator - Remove and Install
C7.1 Engines Water Separator and Fuel Filter (Primary) - Remove and Install
C7.1 Engines Water Pump - Remove
C7.1 Engines Water Pump - Install
C7.1 Engines Wastegate Solenoid - Remove and Install
C7.1 Engines Vibration Damper and Pulley - Remove
C7.1 Engines Vibration Damper and Pulley - Install
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Circuit Breaker (K3)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies MOV Surge Protector
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Modem (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Bypass Static Switch (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Transformer (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Contactor (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Controller PWA (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Circuit Breaker (MMS System Cabinet)
C3.3B Tier 4 Final Engines for Caterpillar Built Machines Piston and Rings
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Overload Relay (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Thyristor (MMS System Cabinet)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.