24V Power Supply (MMS System Cabinet)
Show/hide table
Illustration 1 | g01273665 |
(1) 24 VDC power supplies |
The two 24 VDC power supplies (1) are located on the left panel of the MMS cabinet. The 24 VDC power supplies (1) are used to power all the circuit boards in the system.
Refer to Systems Operation, Testing and Adjusting, UENR3954, "Internal Component Preremoval Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.
- Remove the seven wires that connect to the power supply. The wires have a labeling as the location of the wire. Verify each labeling on the wire with the location of the wire. Refer to Illustration 2 for wire connections.
- Remove the four mounting screws for the power supply assembly.
- Remove the two screws that attach the power supply to the left panel.
- Remove the power supply from the cabinet.
Show/hide table
Illustration 2 | g01273672 |
Example of a power supply and wire connections |
Show/hide table
Illustration 3 | g03800077 |
Later version of AC to DC power supplies |
- Position the power supply on the left panel. Refer to Illustration 1 for the position of the power supply.
- Attach the power supply to the left panel with the two screws.
- Attach the eight wires to the power supply. Refer to Illustration 2 for wire connections.
Caterpillar Information System:
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Transformer (T1 to T3)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System I/O Daughter PWA (MMS System Cabinet)
C9 Engine Coolant (DEAC) - Change
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System I/O PWA (MMS System Cabinet)
C7.1 Engines Water Temperature Regulator - Remove and Install
C7.1 Engines Water Separator and Fuel Filter (Primary) - Remove and Install
C7.1 Engines Water Pump - Remove
C7.1 Engines Water Pump - Install
C7.1 Engines Wastegate Solenoid - Remove and Install
C7.1 Engines Vibration Damper and Pulley - Remove
C7.1 Engines Vibration Damper and Pulley - Install
C7.1 Engines Valve Mechanism Cover Base - Remove and Install
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Current Transformers (Primary, Secondary)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Circuit Breaker (K3)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies MOV Surge Protector
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Modem (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Bypass Static Switch (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Transformer (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Contactor (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Controller PWA (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Circuit Breaker (MMS System Cabinet)
C3.3B Tier 4 Final Engines for Caterpillar Built Machines Piston and Rings
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Zig Zag Overload Relay (MMS System Cabinet)