UPSB505 Uninterruptible Power Supply UPS Battery - 50Hz Caterpillar


Troubleshooting

Usage:

UPSB 505 YTM

Identification of Fan Failure Fault on 300kVA and 400kVA

Identification by the LED on the DAFT Board

Table 1
Name     Function     Fault Message in UPS display    
HE1     Choke right box, fan on the back     Inverter Fan fault    
HE2     Choke left box, fan in front of UPS     Inverter Fan fault    
HE5     Fan PFC Phase 1, on the back     PFC Fan Fault    
HE6     Fan PFC Phase 1, on the back     PFC Fan Fault    
HE7     Fan Inverter Phase 1, on the back     Inverter Fan fault    
HE8     Fan Inverter Phase 1, on the back     Inverter Fan fault    
HE9     Not Used always off     /    
HE10     Choke right box, fan in the middle     Inverter Fan fault    
HE13     DC Caps Fan     Inverter Fan fault    
HE14     Fan PFC Phase 2, in the middle     PFC Fan Fault    
HE15     Fan PFC Phase 2, in the middle     PFC Fan Fault    
HE16     Fan Inverter Phase 2, in the middle     Inverter Fan fault    
HE17     Fan Inverter Phase 2, in the middle     Inverter Fan fault    
HE18     DC Caps Fan     Inverter Fan fault    
HE19     DC Caps Fan     Inverter Fan fault    
HE20     Fan PFC Phase 3, in front of UPS     PFC Fan Fault    
HE21     Fan PFC Phase 3, in front of UPS     PFC Fan Fault    
HE22     Fan Inverter Phase 3, in front of UPS     Inverter Fan fault    
HE23     Fan Inverter Phase 3, in front of UPS     Inverter Fan fault    
HE24     Choke left box, fan in the middle     Inverter Fan fault    
HE25     Choke left box, fan on the back     Inverter Fan fault    

Identification by the LED on the DALIT Board

Table 2
Name     Function     Fault Message in UPS display    
HE1     Not Used always off     /    
HE2     Not Used always off     /    
HE3     Not Used always off     /    
HE4     Fan Static switch     AC Bypass static switch fan fault    
HE5     Fan Static switch     AC Bypass static switch fan fault    
HE6     Choke right box, fan in front of UPS     AC Bypass static switch fan fault    

Identification of the Fan Failure by the Message on the Display

Table 3
Fault Message in UPS Display     Function     Name    
PFC Fan Fault     Fan PFC Phase 1, on the back     HE5 on DAFT    
Fan PFC Phase 1, on the back HE6 on DAFT    
Fan PFC Phase 2, in the middle HE14 on DAFT    
Fan PFC Phase 2, in the middle HE15 on DAFT    
Fan PFC Phase 3, in front of UPS HE20 on DAFT    
Fan PFC Phase 3, in front of UPS HE21 on DAFT    
Inverter Fan fault     Choke right box, fan on the back     HE1 on DAFT    
Choke left box, fan in the middle HE2 on DAFT    
Fan Inverter Phase 1, on the back HE7 on DAFT    
Fan Inverter Phase 1, on the back HE8 on DAFT    
Choke right box, fan in the middle HE10 on DAFT    
DC Fan HE13 on DAFT    
Fan Inverter Phase 2, in the middle HE16 on DAFT    
Fan Inverter Phase 2, in the middle HE17 on DAFT    
DC Fan HE18 on DAFT    
DC Fan HE19 on DAFT    
Fan Inverter Phase 3, in front of UPS HE22 on DAFT    
Fan Inverter Phase 3, in front of UPS HE23 on DAFT    
Choke left box, fan in the middle HE24 on DAFT    
Choke left box, fan on the back HE25 on DAFT    
AC Bypass static switch fan fault     Fan Static switch     HE4 on DALIT    
Fan Static switch HE5 on DALIT    
Choke right box, fan in front of UPS HE6 on DALIT    

Identification of Fan Failure Fault on 500kVA

Identification of the Fan Failure by the LED on the VENT Board

Table 4
Name     Function     Fault Message in UPS Display    
HE1     Choke right box     Inverter Fan fault    
HE2     Choke left box     Inverter Fan fault    
HE3     DC Caps Fan     Inverter Fan fault    
HE4     Fan Static switch INV     Inverter Fan fault    
HE5     DC PFC fan Phase 3, in front of UPS     PFC Fan Fault    
HE6     DC PFC fan Phase 2, in the middle     PFC Fan Fault    
HE7     DC PFC fan Phase 1, on the back     PFC Fan Fault    
HE8     Choke right box     Inverter Fan fault    
HE9     Choke right box     Inverter Fan fault    
HE10     DC PFC fan Phase 3, in front of UPS     PFC Fan Fault    
HE11     DC PFC fan Phase 2, in the middle     PFC Fan Fault    
HE12     DC PFC fan Phase 1, on the back     PFC Fan Fault    
HE13     DC Caps Fan     Inverter Fan fault    
HE14     DC Caps Fan     Inverter Fan fault    
HE15     Fan Static switch INV     Inverter Fan fault    
HE16     Fan Static switch INV     Inverter Fan fault    
HE17     Choke left box     Inverter Fan fault    
HE18     DC INV fan Phase 3, in front of UPS     PFC Fan Fault    
HE19     DC INV fan Phase 2, in the middle     PFC Fan Fault    
HE20     DC INV fan Phase 1, on the back     PFC Fan Fault    
HE21     DC INV fan Phase 3, in front of UPS     PFC Fan Fault    
HE22     Choke left box     Inverter Fan fault    
HE23     DC INV fan Phase 2, in the middle     PFC Fan Fault    
HE24     DC INV fan Phase 1, on the back     PFC Fan Fault    

Identification of the Fan Failure by the LED on the DALIT Board

Table 5
Name     Function     Fault Message in UPS Display    
HE1     Fan Static switch AC Bypass N°1     AC Bypass static switch fan fault    
HE2     Fan Static switch AC Bypass N°1     AC Bypass static switch fan fault    
HE3     Fan Static switch AC Bypass N°1     AC Bypass static switch fan fault    
HE4     Fan Static switch AC Bypass N°2     AC Bypass static switch fan fault    
HE5     Fan Static switch AC Bypass N°2     AC Bypass static switch fan fault    
HE6     Fan Static switch AC Bypass N°2     AC Bypass static switch fan fault    

Identification of the Fan Failure by the Message on the UPS Display

Table 6
Fault Message in UPS Display     Function     Name    
PFC Fan Fault     DC PFC fan Phase 3 (in front of UPS)     HE5 on VENT    
DC PFC fan Phase 2 (in the middle) HE6 on VENT    
DC PFC fan Phase 1 (on the back) HE14 on VENT    
DC PFC fan Phase 3 (in front of UPS) HE10 on VENT    
DC PFC fan Phase 2 (in the middle) HE11 on VENT    
DC PFC fan Phase 1 (on the back) HE12 on VENT    
DC INV fan Phase 3 (in front of UPS) HE18 on VENT    
DC INV fan Phase 2 (in the middle) HE19 on VENT    
DC INV fan Phase 1 (on the back) HE20 on VENT    
DC INV fan Phase 3 (in front of UPS) HE21 on VENT    
DC INV fan Phase 2 (in the middle) HE23 on VENT    
DC INV fan Phase 1 (on the back) HE24 on VENT    
Inverter Fan fault     Choke right box     HE1 on VENT    
Choke left box HE2 on VENT    
DC Caps Fan HE3 on VENT    
Fan Static switch INV HE4 on VENT    
Choke right box HE8 on VENT    
Choke right box HE9 on VENT    
DC Caps Fan HE13 on VENT    
DC Caps Fan HE14 on VENT    
Fan Static switch INV HE15 on VENT    
Fan Static switch INV HE16 on VENT    
Choke left box HE17 on VENT    
Choke left box HE22 on VENT    
AC Bypass static switch fan fault     Fan Static switch AC Bypass N°1     HE1 on DALIT    
Fan Static switch AC Bypass N°1 HE2 on DALIT    
Fan Static switch AC Bypass N°1 HE3 on DALIT    
Fan Static switch AC Bypass N°2 HE4 on DALIT    
Fan Static switch AC Bypass N°2 HE5 on DALIT    
Fan Static switch AC Bypass N°2 HE6 on DALIT    

Fault Menu Trees




Illustration 1g02597098



Illustration 2g02597668



Illustration 3g02598376



Illustration 4g02598378



Illustration 5g02599358



Illustration 6g02599359



Illustration 7g02599361



Illustration 8g02599363



Illustration 9g02602085



Illustration 10g02602088



Illustration 11g02602090



Illustration 12g02602092



Illustration 13g02602093

Caterpillar Information System:

Cat Water Delivery System (WDS) System Pressure Release
3500 Engines Engine Oil Pan
C175-16 and C175-20 Generator Set Engines Air Cleaner
C4.4 Industrial Engine Fuel Filter Base - Remove and Install - Twin Secondary Fuel Filter
330D, 336D, 336D2, 340D and 340D2 Excavators Machine System Specifications Stick Lines - Quick Coupler
C4.4 Industrial Engine Fuel Temperature Sensor - Remove and Install
3500 Engines Piston and Rings - Two-Piece Piston
Cat Water Delivery System (WDS) Serial Number Location
Cat Water Delivery System (WDS) Water Pump Bearing - Lubricate
TA19 and TA22 Transmissions Power Train Electronic Control System Transmission
TA19 Agriculture Transmission Electronic Control System Event Code List
TA19 Agriculture Transmission Electronic Control System Connector Locations
UPSB505 Uninterruptible Power Supply UPS Battery - 50Hz Basic Preventive Maintenance
UPSB505 Uninterruptible Power Supply UPS Battery - 50Hz Advanced Preventive Maintenance
C32 Marine Generator Set Alarms and Shutoffs
Crimping Caterpillar 1E294, 1E716, 1E844 Hose and Couplings {0374, 0599, 0684, 0738, 5057} Crimping Caterpillar 1E294, 1E716, 1E844 Hose and Couplings {0374, 0599, 0684, 0738, 5057}
336F MHPU Mobile Hydraulic Power Unit Machine System Specifications Relief Valve (Main) - Heavy Lift
3500B Engines and 776D, 777D, 784C, 785C, 789C, 793C and 793D Off-Highway Truck/Tractors Engine Oil Scavenge Pump
C3.4B Industrial Engine Engine Oil and Filter - Change
C3.4B Industrial Engine Fuel System Primary Filter (Water Separator) Element - Replace
C32 Marine Generator Set Refill Capacities
3512C Oil Well Service Engines Configuration Parameters
3512C Oil Well Service Engines Aftercooler Core - Inspect/Clean/Test
C32 Marine Generator Set Engine Oil Sample - Obtain
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.