Specifications
Show/hide table
    | 50 Hz Units     | 60 Hz Units     | ||||
---|---|---|---|---|---|---|
    | UPS 250iE     | UPS 500i     | UPS 750i     | UPS 300E     | UPS 600     | UPS 900     |
Rating     | 250 kVA 2225 kW     |
500 kVA 450 kW     |
750 kVA 675 kW     |
300 kVA 240 kW     |
600 kVA 480 kW     |
900 kVA 720 kW     |
Input Voltage     | 380 VAC 400 VAC 415 VAC     |
480 VAC     | ||||
Output Voltage     | 380 VAC 400 VAC 415 VAC     |
480 VAC     | ||||
AC Input     | ||||||
Nominal Amperage     | 358 A 340 A 328 A     |
709 A 674 A 650 A     |
1064 A 1011 A 974 A     |
302 A     | 599 A     | 898 A     |
Maximum Continuous Amperage     | 400 A     | 800 A     | 1200 A     | 400 A     | 800 A     | 1200 A     |
Maximum Noncontinuous Amperage     | 420 A     | 840 A     | 1260 A     | 420 A     | 840 A     | 1260 A     |
AC Output     | ||||||
Nominal Amperage     | 380 A 361 A 348 A     |
761 A 723 A 696 A     |
1141 A 1084 A 1045 A     |
361 A     | 723 A     | 1084 A     |
Typical System Efficiency     | ||||||
100 Percent load     | 97 Percent     | 98 Percent     | 98 Percent     | 97 Percent     | 98 Percent     | 98 Percent     |
Physical Dimensions and Weight     | ||||||
Height     | 1981 mm (1) (78 in) (1)     |
2438 mm (1) (96 in) (1)     |
||||
Wireway Height     | 452 mm (17.8 in)     |
|||||
Depth     | 865 mm (34 in)     |
|||||
Width     | 3226 mm (2) (127 in) (2)     |
4318 mm (2) (170 in) (2)     |
5410 mm (2) (213 in ) (2)     |
3226 mm (2) (127 in) (2)     |
4318 mm (2) (170 in) (2)     |
5410 mm (2) (213 in) (2)     |
Weight     | 3500 kg (7716 lb)     |
5570 kg (12280 lb)     |
7610 kg (16777 lb)     |
3199 kg (7050 lb)     |
5241 kg (11550 lb)     |
7282 kg (16050 lb)     |
Cable Access     | Top or Bottom     | |||||
Heat Rejection Nominal/Maximum     | ||||||
kW     | 8.21     | 11.68     | 17.53     | 8.67     | 12.30     | 18.44     |
BTU/Hr     | 28028     | 39839     | 59839     | 29612     | 41983     | 62975     |
Specifications for Input     | ||||||
Voltage     | 380 VAC/400 VAC/415 VAC, 3 phase, plus neutral and ground (3)     | 480 VAC, 3 phase plus ground(from grounded wye source) (4-wire optional)     | ||||
Voltage Range     | 480 VAC +10 Percent / −15 Percent (programmable) ± 10 Percent at 380 VAC     | |||||
Power Factor     | 0.99 at rated load and nominal voltage     | |||||
Harmonic Current Distortion     | ||||||
Linear Load     | less than 3 Percent max at 100 Percent linear load     | |||||
Nonlinear Load     | less than 8 Percent with a 100 Percent nonlinear load     | |||||
Input Frequency     | 50 Hz ± 10 Percent max (programmable) ± 3 Percent (default) (4)     | 60 Hz ± 10 Percent max (programmable) ± 3 Percent (default     | ||||
Specifications for Withstanding Surge     | Meets IEEE 587/ANSI C62.41     | |||||
Walk-In Time     | Programmable from 1 second to 15 seconds     | |||||
Specifications for Output     | ||||||
Voltage     | 380/400/415 VAC, 3 phase, plus neutral and ground (from grounded wye source)     | 480 VAC, 3 phase, plus ground (4-wire with optional 4-wire input)     | ||||
Overload Capability (Normal Operation without bypass)     | 1000 Percent for 10 milliseconds     | |||||
500 Percent for 1 second | ||||||
up to 200 Percent for 30 seconds | ||||||
up to 125 Percent for 10 minutes | ||||||
Voltage Regulation     | ||||||
Steady state     | ± 1 Percent of nominal for ± 10 Percent input and balanced or unbalanced load     | |||||
Flywheel Mode     | ± 1 Percent of nominal for steady-state balanced or unbalanced load     | |||||
Transient     | ± 1 Percent within 50 milliseconds for 100 Percent load step     | |||||
Voltage Distortion     | 3 Percent of linear loads 5 Percent of non-linear loads     |
|||||
Output Frequency     | 50 Hz ± 3 Percent (utility synchronized-normal operation) nominal ± 0.2 Percent free running     | 60 Hz ± 10 Percent (utility synchronized-nominal operation) nominal ± 0.2 Percent free running     | ||||
Slew Rate     | Maximum of 1 Hz per second     | |||||
Environmental Specifications     | ||||||
Audible Noise     | less than 72 dBA at 1 m (3.28 ft)     |
less than 75 dBA at 1 m (3.28 ft)     |
less than 72 dBA at 1 m (3.28 ft)     |
less than 75 dBA at 1 m (3.28 ft)     |
||
Operating Temperature     | 0 °C (32 °F) to 40 °C (104 °F)     |
|||||
Storage Temperature     | −25 °C (−13 °F) to 70 °C (158 °F)     |
|||||
Humidity     | 5 Percent to 95 Percent (non-condensing)     | |||||
Altitude     | Up to 914 m (3000 ft) (derate operating temperature by 1.2° C (34.2° F) for every 305 m (1000 ft) above this limit)     |
|||||
Emissions and Immunity     | FCC Class A, Subpart J of Part 15 and EN 50091-2     | |||||
Minimum Floor Load Capacity     | 147.4 kg (325 lb)per square foot     |
Show/hide table
( 1 ) | This dimension excludes the wireway. |
( 2 ) | The N+1 option adds an additional 1092 mm (42.99 inch). |
( 2 ) | |
( 3 ) | Except at 10 percent of maximum at 380 VAC. |
( 4 ) | Also available with 60 Hz nominal voltage. |
Show/hide table
480 V Systems     | |
Percent of Load     | Ride-Through Time     |
100 Percent     | 14.3 seconds     |
75 Percent     | 18.8 seconds     |
50 Percent     | 27.8 seconds     |
25 Percent     | 52 seconds     |
380/400/415 V Systems     | |
Percent of Load     | Ride-Through Time     |
100 Percent     | 15 seconds     |
75 Percent     | 20 seconds     |
50 Percent     | 30 seconds     |
25 Percent     | 56 seconds     |
Caterpillar Information System:
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Electrical System
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fire Prevention and Explosion Prevention
C6.6 Marine Generator Set Engine Oil and Filter - Change - Duplex Oil filters
3412, 3412C, and 3412E Generator Set Engines Indicator Lamp - Test
C6.6 Marine Generator Set Engine and Generator Mounting Group
2015/07/17 A New Cylinder Pack Is Now Used {1225, 1239}
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Safety Signs and Labels
Reuse and Salvage for 3500 Engine Cylinder Blocks {0672, 0705, 0762, 1201, 1217} Reuse and Salvage for 3500 Engine Cylinder Blocks {0672, 0705, 0762, 1201, 1217}
CX28 On-Highway Transmission General Information
C6.6 Marine Generator Set Alternator
C6.6 Marine Generator Set Air Starting Motor
325 VARIABLE UNDERCARRIAGE VH Undercarriage/VM Undercarriage Hydraulic System Pressure Reducing Valve (Travel Parking Brake) - Test and Adjust - VM Undercarriage
2008/09/01 The Torque Specification on the Rocker Arm Bolts has Changed {1102, 1123}
3512B Generator Set Engine Speed Control (Switch) - Test
2008/09/01 New AccuGrade® 900 MHz and 2400 MHz Radios are Now Available {733T}
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Information Plate
C6.6 Marine Generator Set Fuel Priming Pump - Remove and Install - MCS Fuel Priming Pump
3512B Generator Set Engine Speed/Timing - Test
3412, 3412C, and 3412E Generator Set Engines ECM/Personality Module - Test
3512B Generator Set Engine Starting - Test
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Site Preparation
3508B, 3512B, 3516B, 3512C and and 3516C Auxiliary Engines, Generator Set Engines, and Generator Sets Generator Lead Connections
3412, 3412C, and 3412E Generator Set Engines Shutdown - Test
The Use of Unsupported Software Could Cause Unexpected Shifting on Certain TH48-E80 Oil/Gas Transmissions{3168, 7620} The Use of Unsupported Software Could Cause Unexpected Shifting on Certain TH48-E80 Oil/Gas Transmissions{3168, 7620}