Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


GSC CID 0248 - FMI 09

Usage:

C32 SXC
Conditions Which Generate This Code:

This diagnostic code is associated with the CAT Data Link. The FMI 9 means that the ECM has determined that an abnormal update has occurred.




Illustration 1g01442749

System Schematic For CAT Data Link

On C32 packages, the GSC+P uses the CAT Data Link in order to communicate with the engine ECM. The CAT Data Link consists of two wires that connect the GSC+P to the engine ECM.

The possible causes of a CID 248 FMI 9 are listed below.

  • A short to the positive battery terminal ("BATT+") of either of the two CAT Data Link wires

  • A short to the negative battery terminal ("BATT-") of either of the two CAT Data Link wires

The GSC+P cannot detect an open in the circuit of the CAT Data Link. The GSC+P treats a CID 248 FMI 9 as an alarm fault. Active alarm faults are shown on the display when the "Alarm Codes" key is pressed. The Engine Control Switch (ECS) is in any position except the OFF/RESET position. Troubleshoot and repair the wiring. Refer to Testing And Adjusting, "Schematics And Wiring Diagrams". Clear the fault from the fault log after troubleshooting is complete.

Test Step 1. CHECK THE POSITIVE BATTERY TERMINAL

  1. Ensure that there are not shorts between "BATT+" and either of the CAT Data Link wires.

  1. Turn the ECS to OFF/RESET.

  1. Disconnect both cables from the battery.

  1. Measure the resistance between the positive battery cable and both CAT Data Link wires.

Expected Result:

The resistance between the positive battery cable and both of the CAT Data Link wires should be greater than 5000 ohms.

Results:

  • OK - The resistance between the disconnected positive battery cable and either of the CAT Data Link wires is greater than 5000 ohms. Proceed to Test Step 2.

  • NOT OK - The resistance between the disconnected positive battery cable and either of the CAT Data Link wires is less than 5000 ohms.

    Repair: Troubleshoot and repair the wiring. Repair any shorts between "BATT+" and the CAT Data Link wires. Refer to Testing And Adjusting, "Schematics And Wiring Diagrams".

    STOP

Test Step 2. CHECK THE BATTERY NEGATIVE TERMINALS

  1. Ensure that there are no shorts between the battery negative terminal and either of the CAT Data Link wires.

  1. Turn the ECS to OFF/RESET.

  1. Disconnect both cables from the battery.

  1. Measure the resistance between the negative battery cable and both CAT Data Link wires.

Expected Result:

The resistance between the negative battery cable and both of the CAT Data Link wires should be greater than 5000 ohms.

Results:

  • OK - The resistance between the disconnected negative battery cable and either of the CAT Data Link wires is greater than 5000 ohms. STOP

  • NOT OK - The resistance between the disconnected negative battery cable and either of the CAT Data Link wires is less than 5000 ohms.

    Repair: Troubleshoot and repair the wiring. Repair any shorts between the disconnected negative battery cable and the CAT Data Link wires. Refer to Testing And Adjusting, "Schematics And Wiring Diagrams".

    STOP

Caterpillar Information System:

Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0110 - FMI 02
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0100 - FMI 02
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Fault Identification
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Service Tools
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) General Information
C175-16 and C175-20 Generator Set Engines Coolant Pressure Is Low
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Indicator for Low Coolant Level
G3500 Generator Sets Configuration Parameters
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Oil Pressure Is Low
An Operation and Maintenance Manual Is Now Available for C7, C9, C13, and C15 On-highway Truck Engines with a 2007 Model Year Regarding the Idle Shutdown Mode{1000, 7938} An Operation and Maintenance Manual Is Now Available for C7, C9, C13, and C15 On-highway Truck Engines with a 2007 Model Year Regarding the Idle Shutdown Mode{1000, 7938}
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Oil Filter Differential Pressure Problem
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Inlet Air Is Restricted
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Engine Control Switch - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) General Information
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) EMCP Electronic Control (Generator Set)
C15 Petroleum Generator Set Engines Camshaft
Installation of the Heated Nozzle for the Caterpillar Regeneration System (CRS){107P, 108B, 1408, 1743, 1803, 1901, 7620} Installation of the Heated Nozzle for the Caterpillar Regeneration System (CRS){107P, 108B, 1408, 1743, 1803, 1901, 7620}
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Instrument Panel
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Data Link
Troubleshooting Acceleration Issues on Caterpillar On-highway Truck Engines That Are Equipped with Automatic Transmissions {1000, 3030} Troubleshooting Acceleration Issues on Caterpillar On-highway Truck Engines That Are Equipped with Automatic Transmissions {1000, 3030}
14L Motor Grader Machine Systems Wheel Mounting - AWD
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Sensors
C9 Petroleum Engines Aftercooler - Install
3516C Generator Set Engine CAN Data Link - Test
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.