UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Vacuum Pump Startup - Required Procedure After Extended Storage

Usage:

ES12F CZE
Note: The pump is internally configured for 240 VAC operation. To operate the vacuum pump prior to energizing the UPS, temporarily disconnect the 240 VAC internal wiring to the receptacle on the right side of the pump. Connect a 240 VAC line cord from an external source. Ensure that you have removed the external 240 VAC source. Reconnect the internal 240 VAC wiring to the receptacle for the vacuum pump prior to energizing the input terminal of the UPS. Reconfiguration of the vacuum pump for 120 VAC operation will void the warranty of the pump.

Note: The vacuum pump has a tamperproof label. This prohibits the service technician from reconfiguration of the pump and utilization of a 120 VAC source in order to begin the process of vacuum draw on the flywheel during the commissioning procedure. A tamperproof label that is corrupted will void any warranty claim that is associated with the vacuum pump.

  • When you change the bearing reloaders in order to install bearings, do not run the vacuum pump. The vacuum pump could circulate contaminants from the outside air into the system.

  • When you change the bearing reloaders in order to install bearings, complete the procedure in a timely manner.

  • Perform a thorough inspection of the vacuum lines and connection points. Look for any possible discrepancies that could result in a vacuum leak.

  • To ensure that the vacuum pump oil is clean, change the oil. Contaminants in the oil will extend the time that is required to draw a vacuum. Dirty oil may also prevent a vacuum from being drawn at all.

  • Do not overfill the vacuum pump oil beyond the level/fill line. The pump capacity is 0.7 L. The vacuum pump will leak if the pump oil is overfilled.

  • Remove all of the plugs on the flywheel. Apply grease to the O-rings. A sealed vacuum vessel is crucial in order to avoid problems at start-up mode.

  • To minimize the time for vacuum draw, the flywheel should be recharged with nitrogen. Because the flywheel is a casting, there will be some leakage of the charged nitrogen over time. To ensure that the flywheel stays dry and free from water vapor, charge the flywheel with a slight positive pressure of dry nitrogen. This will ensure that the UPS is able to achieve vacuum levels quickly at start-up mode.

  • Remove the air bubbles from the vacuum system by turning the switch for the ballast from the 0 position to the II position. The switch for the ballast is located on the top middle of the pump behind the exhaust port. Run the pump for 1 hour. Return the switch for the ballast to the 0 position and allow the pump to pull a vacuum.

If a vacuum of less than 35 Millitorr cannot be drawn in a reasonable amount of time (3 hours or less), follow the procedures in the following sections:

  • "Reading of a Vacuum Above 200 Millitorr"

  • "Reading of a Vacuum 35 to 200 Millitorr"

Reading of a Vacuum Above 200 Millitorr

Visually check and torque all fittings, ports, and connections in order to address any obvious faulty workmanship. If no faults are found, the pump needs dead-headed with a gauge. Check the pump in order to determine if the pump can pull 10 millitorr vacuum.

Reading of a Vacuum 35 to 200 Millitorr

The vacuum pump must be operating. With the vacuum pump in operation, spray methanol on the potential vacuum leaks. Carefully eliminate the following possible source of problems:

  • pins (armature)

  • "Comm/Accel" sensor

  • ports on top of flywheel

  • ports on bottom of flywheel

  • sensor port for the vacuum

  • bearing cartridges

  • temperature sensors

  • 9-pin temperature sensor

  • vacuum hoses

  • elbows

Observe the pressure reading for the vacuum with UPSView. If the vacuum rises from 10 millitorr to 30 millitorr, then that location is one source of the vacuum leak. A repair needs made to any sources of vacuum leaks. If no leaks are found, then the vacuum pump needs to be dead headed with a gauge. Check the vacuum pump in order to determine if the vacuum pump can pull a vacuum of 10 millitorr.

Dead Head Testing of the Vacuum Pump

  1. Verify that the system is in bypass mode. Verify that the flywheel is disengaged.

  1. De-energize the vacuum pump.

  1. Disconnect the input vacuum hose and the 90 degree elbow assembly between the flywheel and the right side of the vacuum pump.

  1. Connect the 295-5409 Adapter Plate into the fitting for the vacuum pump. See Step 3.

  1. Connect the 200-8452 Vacuum Sensor to the 295-5409 Adapter Plate .

  1. Wire the ethernet cable from the sending unit to the "J10" connector on the flywheel interface board. The existing ethernet cable that is attached to the board will need to be temporarily removed.

  1. Energize the pump. Observe if vacuum is being pulled to less than 10 millitorr on UPS HMI or UPSView.

  1. If vacuum is pulled, then the pump is good. The vacuum system that is external to the pump has a leak.

If troubleshooting procedures uncover no problem, then the flywheel may be faulty. Contact Caterpillar technical support .

Caterpillar Information System:

3408E and 3412E Engines for Caterpillar Built Machines Engine Has Mechanical Noise (Knock)
C15 and C18 Petrolem Generator Set Engines Coolant Contains Fuel
C15 and C18 Petrolem Generator Set Engines Alternator Problem - Charging Problem and/or Noisy Operation
C27 and C32 Generator Set Engines Radiator Core - Remove
C27 and C32 Generator Set Engines Fuel Filter and Water Separator - Remove and Install
C27 and C32 Generator Set Engines Fuel Temperature Sensor - Remove and Install
C27 and C32 Generator Set Engines Fuel Pressure Sensor - Remove and Install
C15 and C18 Petrolem Generator Set Engines Symptom Troubleshooting
C27 and C32 Generator Set Engines Fuel Filter Base - Install
C27 and C32 Generator Set Engines Fuel Filter Base - Remove
2006/08/01 Improved Support for the Precooler is Now Used {105P, 1380}
C27 and C32 Generator Set Engines Fuel Priming Pump - Remove and Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Low DC Voltage Potentiometer - Calibrate
3176C, 3406E and 3456 Industrial Engines Oil Contains Fuel
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Multidrop Network - Setup
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Remote Input/Output Dry Contact - Setup
C175-16 Locomotive Engine Cylinder Block, Liners and Heads
Troubleshooting Engine Vibration{1000, 1151, 1162, 1206} Troubleshooting Engine Vibration{1000, 1151, 1162, 1206}
3508B, 3512B, and 3516B High Displacement Generator Sets Maintenance Recommendations
Failure To Program Injector 6 Trim Calibration File{1290, 7620} Failure To Program Injector 6 Trim Calibration File{1290, 7620}
3606 and 3608 Engines Engine Oil Pan - Remove
C4.2 and C6.4 Engines for Caterpillar Built Machines Oil Temperature Is High
C175-16 Locomotive Engine Pistons, Rings and Connecting Rods
C13 and C15 On-highway Engines Programmable Parameters
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.