Illustration 1 | g01293171 |
The "User Parameters" screen allows qualified service personnel to configure remote input and output contact functions. User-defined text messages assigned to the remote input contacts can be edited.
Depending on the parameter being changed, entry of data is made by one of the following input devices:
- a numeric keypad
- an alphanumeric keyboard that is displayed as needed on the Graphical User Interface
You access the "User Parameters" from the Control Tab on the Graphical User Interface. Refer to Illustration 1.
Editing Remote Output Contacts
Perform the following steps to configure remote outputs for the UPS/SMS or MMU.
- Select a remote output by touching the associated output key (For example, Remote Output 1).
The Edit Remote Output dialog appears. Refer to Illustration 2.
Illustration 2 | g01293185 |
- Enter the remote output values by touching the required keypad buttons.
- Touch "Enter" when done.
Output Contact Definitions
The following list of functions can be assigned to the remote output contacts by entering the parameter in the menu for the operating parameter for the associated remote output. Each User Programmable Remote Output Contact provides a Form C connection.
The output contacts have the following ratings:
- 5 A
- 30VDC
- 30VAC
Output Contacts Function List     | ||
---|---|---|
Function     | Description     | Paralleled System Support     |
0     | No Function     | SMS / PCC / MMU     |
1-100     | Flywheel Percent Energy (1)     | SMS / PCC / MMU     |
101     | Online Normal     | SMS / PCC / MMU     |
102     | On Bypass     | SMS / PCC / MMU     |
103     | Discharging     | SMS / PCC / MMU     |
104     | Notice Condition is active or unacknowledged     | SMS / PCC / MMU     |
105     | Alarm Condition is active or unacknowledged     | SMS / PCC / MMU     |
106     | Overload     | SMS / PCC / MMU     |
107     | External Alarm is Active     | SMS / PCC / MMU     |
108     | Overload Bypass     | SMS / PCC     |
109     | Fan Failure     | SMS     |
110     | Run Generator set     | SMS / PCC     |
111     | Pulsed Run Generator set     | SMS / PCC     |
112     | Pulsed Stop Generator set     | SMS / PCC     |
113     | ATS Command     | SMS / PCC     |
114     | Motoring     | SMS / PCC/ MMU     |
115     | Notice Condition is active     | SMS / PCC/ MMU     |
116     | Alarm Condition is active     | SMS / PCC/ MMU     |
117     | Ready to Walk In     | Not Supported     |
Default Function Assignments for Output     | ||
---|---|---|
Contact     | Function     | Description     |
1     | 101     | Online (normal)     |
2     | 102     | On Bypass     |
3     | 103     | Discharging     |
4     | 50     | Flywheel Percent Energy     |
5     | 104     | Notice condition is active or unacknowledged     |
6     | 105     | Alarm condition is active or unacknowledged     |
7 (1)     | 0     | No Function     |
8 (1)     | 0     | No Function     |
9 (1)     | 0     | No Function     |
10 (1)     | 0     | No Function     |
11 (1)     | 0     | No Function     |
12 (1)     | 0     | No Function     |
( 1 ) | This output contact is only available if a second CCI board is installed |
Editing Remote Input Contacts
Perform the following steps to configure remote inputs for the UPS/SMS or MMU.
- Select a remote input by touching the associated input key.
The "Edit Remote Input" dialog appears. Refer to Illustration 3.
Illustration 3 | g01293188 |
- Enter the remote input values by touching the required keypad buttons.
- Touch "Enter" when done.
Input Contact Definitions
The following list of functions can be assigned to the remote input contacts by entering the parameter in the menu for the operating parameter for the associated remote input. Each User Programmable Remote Input Contact provides a Form C connection. The contact is rated for 3 A and .
The output contacts have the following ratings:
- 5 A
- 250 V
Function     | Description     | System Support     |
---|---|---|
0     | No Function     | SMS / PCC / MMU     |
1     | On Generator - When the On Generator function is activated, individual parameter limits for operation can be set for the Transient Voltage Detection, the Maximum Input Current, and the Walk-in Rate.     | SMS / PCC     |
2     | Remote Switch to the UPS to Bypass     | SMS / PCC     |
3     | Remote Switch to the UPS to On-Line mode     | SMS / PCC     |
4     | Remote Alarm Silencer     | SMS / PCC / MMU     |
5     | External Sync Command     | SMS / MMU     |
6     | Remote Online Inhibit     | SMS / MMU     |
9-Jul     | No Function     | Not Applicable     |
1x     | User Message 1 where x is user message input type (0-9)     | SMS / PCC / MMU     |
2x     | User Message 2 where x is user message input type (0-9)     | SMS / PCC / MMU     |
3x     | User Message 3 where x is user message input type (0-9)     | SMS / PCC / MMU     |
4x     | User Message 4 where x is user message input type (0-9)     | SMS / PCC / MMU     |
5x     | User Message 5 where x is user message input type (0-9)     | SMS / PCC / MMU     |
6x     | User Message 6 where x is user message input type (0-9)     | SMS / PCC / MMU     |
7x     | User Message 7 where x is user message input type (0-9)     | SMS / PCC / MMU     |
8x     | User Message 8 where x is user message input type (0-9)     | SMS / PCC / MMU     |
9x     | User Message 9 where x is user message input type (0-9)     | SMS / PCC / MMU     |
10x     | User Message 10 where x is user message input type (0-9)     | SMS / PCC / MMU     |
11x     | User Message 11 where x is user message input type (0-9)     | SMS / PCC / MMU     |
12x     | User Message 12 where x is user message input type (0-9)     | MMU     |
13x     | User Message 13 where x is user message input type (0-9)     | MMU     |
14x     | User Message 14 where x is user message input type (0-9)     | MMU     |
15x     | User Message 15 where x is user message input type (0-9)     | MMU     |
16x     | User Message 16 where x is user message input type (0-9)     | MMU     |
17x     | User Message 17 where x is user message input type (0-9)     | MMU     |
18x     | User Message 18 where x is user message input type (0-9)     | MMU     |
?19x     | User Message 19 where x is user message input type (0-9)     | MMU     |
20x     | User Message 20 where x is user message input type (0-9)     | MMU     |
21x     | User Message 21 where x is user message input type (0-9)     | MMU     |
22x     | User Message 22 where x is user message input type (0-9)     | MMU     |
23x     | User Message 23 where x is user message input type (0-9)     | MMU     |
24x     | User Message 24 where x is user message input type (0-9)     | MMU     |
250 - 299     | No Function     | Not Applicable     |
300     | Match Output voltage to Input     | MMU     |
301     | Synchronized Walk In Enable     | Not supported     |
302     | Okay to Walk In     | Not Supported     |
303     | Delay/Stagger Flywheel Motoring     | MMU     |
Input Contact Default Function Assignment     | ||
---|---|---|
Contacts     | Function     | Description     |
1     | 1     | On Generator     |
2     | 2     | Remote switch from UPS to Bypass     |
3     | 3     | Remotely switch the UPS to Online status - this is done only if there are no errors active.     |
4     | 10     | User Message 1 Event Message on contact close     |
5     | 20     | User Message 2 Event Message on contact close     |
6     | 30     | User Message 3 Event Message on contact close     |
7 (1)     | 70     | User Message 7 Event Message on contact close     |
8 (1)     | 80     | User Message 8 Event Message on contact close     |
9 (1)     | 90     | User Message 9 Event Message on contact close     |
10 (1)     | 100     | User Message 10 Event Message on contact close     |
11 (1)     | 110     | User Message 11 Event Message on contact close     |
12 (1)     | 120     | User Message 12 Event Message on contact close     |
( 1 ) | This input contact is only available if a second CCI board is installed. |
User Message Input Types     | |
---|---|
Input Type     | Description     |
0     | Generate User Message Event on contact close     |
1     | Generate User Message Notice on contact close     |
2     | Generate User Message Alarm on contact close     |
3     | Generate User Message Event on contact open     |
4     | Generate User Message Notice on contact open     |
5     | Generate User Message Alarm on contact open     |
6     | Generate User Message Event on any contact change     |
7     | Generate User Message Notice on any contact change     |
8     | Generate User Message Alarm on any contact change     |
9     | Reserved     |
Editing User Messages
Perform the following steps to configure user messages sent from the UPS/SMS or MMU.
- Select a user message by touching the associated user message key.
The "Edit User Message" dialog appears. Refer to Illustration 4.
Illustration 4 | g01293228 |
- Enter the user message by touching the required keypad buttons.
- Touch "Done" when finished.