Illustration 1 | g01269271 |
View of 4-Wire Zig Zag Transformer (1) Zig Zag Transformer |
The "T5" Zig Zag Transformer is located on the floor of the SMS Cabinet in a 4-wire installation. The "T5" Zig Zag Transformer is located on the rear panel in a 3-wire installation.
The transformer is required for establishing the neutral point of the UPS 3-phase output when the following conditions occur:
- discharge mode of the system
- disconnection of the utility input
Illustration 2 | g01269273 |
View of the 3-Wire Zig Zag Transformer Rear Panel (2) Zig Zag Transformer |
Removal Procedure and Installation Procedure for the Zig Zag Transformer
NOTICE |
---|
Removal of the Zig Zag Transformer and installation of the Zig Zag Transformer are not field service procedures. Contact your Caterpillar technical support. |
There is a
- The switch will close.
- The circuit breaker will trip.
- The circuit breaker will shut down power to the transformer.
There are three circular 5000:1 Current Transformers (CTs) surrounding each of the Zig Zag Transformer Phase cables located at the bottom of the cabinet in a 4-wire installation. These current transformers relay a telemetry signal to the Zig Zag Controller board (ZZC).
Illustration 3 | g01269315 |
View of the 3-Wire Zig Zag Wire Connections |